
11
COMFORT 600 BY NILAN
Functions overview + Standard
- Accessories
Alarms Description of errors indicated with alarms. Alarm log displaying the latest 16 alarms. +
Joint alarm The CTS602 control system has an output signal that is activated in the case of an alarm. It can be con-
nected to, for example, external automation.
Filter monitor Filter alarm with timer that can be set to 30/90/180/360 days. +
Data display An overview of the current operation with regards to temperatures, fan speed level etc. +
Week program The CTS602 control system has 3 week programs that can be set individually (the default setting is “off”). +
Humidity control system Enables a higher or lower degree of ventilation at a high/low level of humidity. +
Air quality Enables you to adjust the degree of ventilation depending on the CO2level in the air. -
Winter low You can prevent a low level of humidity in the dwelling by activating low ventilation at low outdoor
temperatures.
+
Temperature regulation Enables you to control the operation of the unit in accordance with the room temperature. +
Summer/winter mode You can set the unit to operate in summer or winter mode.
Language You can choose from more than 10 languages in the control panel. +
User levels The menu in the control panel is divided into 3 user levels: User/Installer/Factory. +
User selection 1 Enables you to override the operating mode via an external potential free signal. +
User selection 2 Enables you to override the operating mode as well as user selection 1 via an external potential free
signal.
-
Electrical after-heating
element
An electrical after-heating element allows you to control the supply air temperature. In this way the unit
can help heat the dwelling.
-
Water after-heating element A water after-heating element allows you to control the supply air temperature. In this way the unit can
help heat the dwelling.
-
Frost protection In order to protect a potential water after-heating element against frost damage, the unit will stop and
display an alarm if the temperature in the water after-heating element becomes too low.
-
Air exchange Stepless setting of four fan speed levels. The supply air and the extract air can be set individually. +
De-icing Based on temperature, this automatic function de-ices the counterflow heat exchanger if ice has formed
within it.
+
Room low Safety function that will cause the ventilation unit to stop if the heating system for the dwelling fails. This
will prevent the unit from cooling the dwelling even further.
+
External heating The ventilation unit can control an external heat supply in accordance with the current room temperature. +
External fire automation
system
You can connect the ventilation unit to an external fire automation system or to a fire thermostat. This will
signal to the unit whether to stop or continue operation.
+
Integral fire automation
system
The ventilation unit is available with an integral fire automation system that can control fire and smoke
dampers.
-
Pressure sustaining
regulator
You can install a pressure sustaining regulator on the side of both the extract air and the supply air. -
Delayed start-up You can activate a delayed start-up of the fans if you install, for instance, a shut-off damper. +
Restore settings You can save the current settings and subsequently restore them if, for instance, the user has altered the
settings on the unit. You can also reinstall the default settings.
+
Manual operation Different functions can be tested manually. +
Energy saving function You can activate a power saving function of the operation. +
Modbus You can set the Modbus address of the unit. The default setting is 30. +
Data logging It is possible to log the operational data of the unit every 1 - 120 min. Alarms are logged when they occur. +
Control panel You can choose from 2 different images for the main screen. +
You can find further information about all the functions in the Software and Installation instructions for the unit.