Reset of detectors and signal-receiving circuits (by the reset switch)
Cut-off of alarm and trouble output signals (by the signal cut-off switch)
Silence of the control panel (by the alarm silence switch)
Silence of the control panel and local audible devices during
the maintenance (by pressing the alarm silence switch 5 seconds)
Silence of the local audible devices (by the local alarm silence switch)
Alarm verificaon release: Alarm noficaon without verificaon
(by the alarm verificaon release switch)
● A dedicated control panel for transmission system is also available. Please contact us for details.
Note) The detector may operate in response to sparks of arc welding.
This product is non-explosion proof. For explosion-proof products, please contact us.
Reset
Signal cut-off
Alarm silence
Local alarm silence
Detector
operaon test
Baery test
PAPJ002-R-4L
Manual operaon test of the detector
(by the test switch)
Maintenance
alarm silence
Alarm verificaon
release
Non-Explosion-Proof-Type
Infrared Three-Wavelength Flame Detector
High sensitivity eyes catch fire quickly.
Type
Number of circuits
Mounng type
Main power supply
Power consumpon
Panel sound
Input (terminal symbol)
End-of-line resistor
Main material
Paint color
Weight
Maximum number
of devices
Number of local
alarm circuit
Maximum number of
local alarm devices
Trouble noce
funcon
Environmental
condion
Maximum cable
length
Dedicated control panel
4 / 8 / 12 zones
Wall mounng, indoor use
100 VAC±10%, 50/60Hz
21VA (Monitoring), 100 VA (Alarm)
PDCJ001-D, PDCJ002-E
Infrared Three-Wavelength Flame Detector: 1 unit/circuit
Built-in electronic buzzer (Alarm: Constant, Trouble: Intermient)
Detector monitoring (C, L)
Operang temperature: 0〜40℃
Operang humidity: 20〜85%(RH), No condensaon
560 m (when the cable size is φ0.9),
990 m (when the cable size is φ1.2)
10 kΩ, 1/2 W (Connected to the terminal in the detector)
Steel plate t1.2
White
1
15 units (10mA/unit in acve condion)
Detector line open, Device fault,
AC power fault, Circuit valtage fault,
Fuse blown, Alarm receiving circuit fault
Detector line open, Device fault, AC power
fault, Circuit valtage fault, Fuse blown,
Alarm receiving circuit fault, baery fault
General Alarm: 2 points (Dry A contact, 24VDC/1A)
Trouble: 1 point (Dry C contact, 24VDC/1A)
Zone: 2 points (Dry A contact, 24VDC/1A)
Type
Model
Detecon wavelength band
Detecon sensivity
Rated voltage
Delay me
Indicator light
Main material
Finish
Dimensions
Weight
Infrared Three-Wavelength Flame Detector
PDCJ001-D
Three wavelength bands between 4.0 μm and 5.0 μm
33 ㎠ Normal Heptane Flame Detecon at 60m Front Distance
24 VDC
Monitoring & Alarming: 15 mA, Tesng: 95 mA,
Transming: 100 mA plus to the value on the above
Approximately 3 seconds (default), Changeable by seng
Red LED
Aluminum alloy
Urethane paint
H118×W118×D84(mm)
Approximately 1.3 kg
Connecon cable
specificaons
Signal output
InfraredThree-WavelengthFlameDetector Dedicatedcontrolpanel
Environmental condion Operang temperature: −20 to 60℃
Operang humidity: 0 to less than 100% (RH), No condensaon
General purpose terminals: φ0.9 〜 1.6 shielded
communicaon cable (Recommendaon: Heat-resistant
shielded cable)
Transmission purpose terminals: φ0.9 shielded twisted pair
cable (Recommendaon: N-300-SB0.9-1P manufactured
by Nippon Electric Wire & Cable Co., Ltd.)
FLAME DETECTOR
PDCJ001-D
4L:H 550×W 450×D 125(mm)
8L・12L:H 840×W 450×D 145(mm)
4L: 13 kg, 8L: 18 kg, 12L: 19 kg 4L: 15 kg, 8L: 20 kg, 12L: 21 kg
Dimensions
PAPJ002-R-□L (□:Number of
zones) Without baery
PAPJ002-R-□L-P (□:Number of
zones) With baery
Manual test of the baery
(by the aux. power test switch)
Horizontal and vercal 90 °(The angle at which the monitoring
distance is 1⁄2 to the front direcon)
The internal circuit is constantly checked, and if an error
occurs, a trouble signal is transmied.
When the power supply voltage drops below specified value,
a trouble signal is transmied.
Test funcon
Consumpon current
Detecon viewing angle
5 VDC: Microprocessor, IC,
display circuit, and switching circuit
24 VDC: Others
5 VDC: Microprocessor, IC, display
circuit, and switching circuit
56 VDC: Baery charging circuit
(Half-wave recficaon)
24VDC: Others
190905D -F-24000YO1
Safety cautions
●For safety purposes, carefully read the instrucon manual before use and
properly maintain the system.
●This product is different from the fire detecon system defined in the Fire
Service Act.
●This product is a fire detecon device. Do not use it for any other purpose.
●The appearance and specificaons of this product are subject to change without
noce.
●The color of the product in this brochure may be slightly different from the actual
product color due to prinng concerns.
●For maintenance of your important fire detecon system, please contact our
authorized distributor.
●The contents of this brochure are correct as of September 2019.
Head Oce: 4-7-3 Kudan-Minami, Chiyoda-ku, Tokyo 102-8277, Japan
https://www.nohmi.co.jp/english/
Tel: +81-3-3265-0231 Fax: +81-3-3265-5348
The contaminaon of the light-receiving window and the
operang status of the internal circuit are checked by the
pseudo-fire light, and a trouble signal is transmied in case of
an abnormality
Self-diagnosis funcon
Power supply voltage
monitoring funcon
Model
Circuit voltage
Test & maintenance funcon