SSS-1000 Series 1 Installation Guide
Installation Guide
Differential Pressure Flow Sensors
SSS-1000 Series
Mounting
1. Determinetheduct’sowdirectionandinstallthe
SSS-1000basedontheunit’sowarrowimprint.
NOTE: Thesensormustbemountedwiththe
arrowpointinginthedirectionoftheair
ow.
2. Cuta7/8"holeintheducttoaccepttheunit.
3. Aachusingtwoself-tappingscrewsinsertedin
the3/16"mountingholes.
Connections
Connectionsuse3/8"ODpolyethylenetubing.Check
thattherearenosharpbendsinthetubingatany
connection.Bendsandcreasesmayleakastubing
ages.
1. ConnectthePort“H”tothe“High”inputonthe
VAVcontroller.
2. ConnectthePort“L”tothe“Low”inputontheVAV
controller.
NOTE: WithCSC-3000series,CSP-4000/5000
series,KMD-7000series,andBAC-7000
seriescontrollers,useanHFO-01083/8"to
1/4"barbunionadapterandappropriate
polyethylenetubingtothesensorand
controller.Formaximumaccuracyinthe
CSP-5000series,KMD-7000series,and
BAC-7000seriescontrollers,the3/8"OD
tubingbetweenthesensorandtheadapter
shouldbeasshortaspossible,andthe
1/4"ODtubingfromtheadaptertothe
controllershouldbe24"long(onboththe
HighandtheLowsides).
Mounting 1
Connections 1
Specifications 2
Accessories 2
Maintenance 2