Ocean Breeze OBZ-09NPH User manual

OBZ-09NPH
Read this owner’s manual thoroughly before operating the appliance and keep it handy for reference at all times.
WWW.OCEANBREEZECOMFORT.COM

Troubleshooting Tips
Read This Manual
Inside you’ll find many helpful hints on how to use and maintain your air conditioner
properly. Just a little preventive care on your part can save you a great deal of time
and money over the life of your air conditioner. You’ll find many answers to common
problems in the troubleshooting tips - you should be able to fix most of them quickly
before calling service. These instructions may not cover every possible condition of
use, so common sense and attention to safety is required when installing, operating,
and maintaining this product.
1
2
3
15
16
20
23
24

FRONT REAR
Control panel
Handle
(both sides)
Horizontal louver
control lever(adjust
manually)
Vertical louver
control lever
(adjust manually)
Panel
Caster Bottom tray
drain outlet
Air filter
Upper air intake
air outlet
Lower air intake
Drain outlet
Design Notice: In order to ensure the optimal performance of our products, the design specifications of the unit and remote
control are subject to change without prior notice.
2

Please read through these instructions before you start the
installation process. Improper installation can cause
damage to the unit, your personal property, and also poses
a personal safety hazard.
- DO NOT share a single outlet with other electrical appliances.
Improper power supply can cause fire or electrical shock.
- DO NOT install your air conditioner in a wet room such as
a bathroom or laundry room. Too much exposure to water
can cause electrical components to short circuit.
- DO NOT install the unit in a location that may be exposed
to combustible gas, as this could cause a fire.
- The unit has wheels to facilitate movement. Make sure not
to use the wheels on thick carpet or to roll over objects, as
this could cause the unit to fall.
- DO NOT operate the unit that has been dropped or damaged.
- DO NOT allow children to play with the air conditioner.
Children must be supervised around the unit at all times.
- During a thunderstorm, the power must be cut off to avoid
damage to the machine due to lightning.
- If the air conditioner is knocked over during use, turn off the
unit and unplug it from the main power supply immediately.
Visually inspect the unit to ensure there is no damage. If you
suspect the unit has been damaged, contact a technician or
customer service for assistance.
3

4
WARNING: (for using R290/R32 refrigerant only)
- Do not use means to accelerate the defrosting process or to clean, other than those recommended by
the manufacturer.
- DO NOT modify the length of the power cord or use an extension cord to power the unit.
DO NOT share a single outlet with other electrical appliances. Improper power supply can cause fire or
electrical shock.
- The appliance shall be stored in a room without continuously operating ignition sources (for example:
open flames, an operating gas appliance) and ignition sources (for example: an operating electric heater)
close to the appliance. The appliance shall be stored in a room without continuously operating ignition
sources (for example: open flames, an operating gas appliance, or an operating electric heater).
- Do not pierce or burn.
- Be aware that the refrigerants may not contain an odor.
- Compliance with national gas regulations shall be observed.
- Keep ventilation openings clear of obstruction.
- The appliance shall be stored so as to prevent mechanical damage from occurring.
- A warning that the appliance shall be stored in a well-ventilated area where the room size corresponds
to the room area as specified for operation.
- Any person who is involved with working on or breaking into a refrigerant circuit should hold a current
valid certificate from an industry-accredited assessment authority, which authorizes their competence to
handle refrigerants safely in accordance with an industry recognized assessment specification.
- Servicing shall only be performed as recommended by the equipment manufacturer.
Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the
supervision of the person competent in the use of flammable refrigerants.

5
WARNING This symbol shows that this appliance used a flammable refrigerant. If the refrigerant is leaked and exposed to an external ignition source,
there is a risk of fire.
This symbol shows that the operation manual should be read carefully.
This symbol shows that a service personnel should be handling this equipment with reference to the installation manual.
This symbol shows that information is available such as the operating manual or installation manual.
CAUTION
CAUTION
CAUTION
- Please follow the instruction carefully to handle, install, clear, service the air conditioner to avoid any
damage or hazard. Flammable Refrigerant R32 is used within air conditioner.
When maintaining or disposing the air conditioner, the refrigerant (R32 or R290) shall be recovered
properly, shall not discharge to air directly.
- No open fire or device like switch which may generate spark/arcing shall be around air conditioner to
avoid causing ignition of the flammable refrigerant used.
Please follow the instruction carefully to store or maintain the air conditioner to prevent mechanical
damage from occurring.
- Flammable refrigerant -R32 is used in air conditioner. Please follow the instruction carefully to avoid
any hazard.
IMPORTANT NOTE: Read this manual carefully before
installing or operating your new air conditioning unit.
Make sure to save this manual for future reference.
Caution: Risk of fire/
flammable materials
(Required for R32/R290 units only)

1. Transport of equipment containing flammable refrigerants
See transport regulations
2. Marking of equipment using signs
See local regulations
3. Disposal of equipment using flammable refrigerants
See national regulations.
4. Storage of equipment/appliances
The storage of equipment should be in accordance with the manufacturer's instructions.
5. Storage of packed (unsold) equipment
Storage package protection should be constructed such that mechanical damage tothe equipment
inside the package will not cause a leak of the refrigerant charge. The maximum number of pieces of
equipment permitted to be stored together will be determined by local regulations.
6. Information on servicing
1) Checks tothe area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to
ensure that the risk of ignition is minimised. For repair tothe refrigerating system, the following
precautions shall be complied with prior to conducting work on the system.
2) Work procedure
Work shall be undertaken under a controlled procedure so as to minimise the risk of aflammable gas
or vapour being present while the work is being performed.
6

3) General work area
All maintenance staff and others working in the local area shall be instructed on the nature of work
being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be
sectioned off. Ensure that the conditions within the area have been made safe by control of flammable
material.
4) Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure
the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment
being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately
sealed or intrinsically safe.
5) Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate
fire extinguishing equipment shall be available on hand. Have a dry powder or CO2fire extinguisher
adjacent tothe charging area.
6) No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing any pipe
work that contains or has contained flammable refrigerant shall use any sources of ignition in such
a manner that it may lead tothe risk of fire or explosion. All possible ignition sources, including
cigarettesmoking, should be kept sufficiently far away from the site of installation, repairing, removing
and disposal, during which flammable refrigerant can possibly be released tothe surrounding
space. Prior to work taking place, the area around the equipment is to be surveyed to make sure
7

7) Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system
or conducting any hot work. A degree of ventilation shall continue during the period that the work is
carried out. The ventilation should safely disperse any released refrigerant and preferably expel it
externally into the atmosphere.
8) Checks tothe refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and tothe correct
specification. At all times the manufacturer's maintenance and service guidelines shall be followed. If
indoubt consult the manufacturer's technical department for assistance. The following checks shall be
applied to installations using flammable refrigerants:
The charge size is in accordance with the room size within which the refrigerant containing parts are
installed;
The ventilation machinery and outlets are operating adequately and are not obstructed;
If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence
of refrigerant; Marking tothe equipment continues to be visible and legible. Markings and signs that
are illegible shall be corrected;
Refrigeration pipe or components are installed in a position where they are unlikely to be exposed
to any substance which may corrode refrigerant containing components, unless the components are
constructed of materials which are inherently resistant to being corroded or are suitably protected
against being socorroded.
that there are no flammable hazards or ignition risks. No Smoking signs shall be displayed.
8

7. Repairs tosealed components
9) Checksto electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component
inspection procedures. If afault exists that could compromise safety, then no electrical supply shall be
connected tothe circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately
but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be
reported tothe owner of the equipment so all parties are advised.
Initial safety checks shall include:
That there are no live electrical components and wiring exposed while charging, recovering, or purging
the system; That there is continuity of earth bonding.
1) During repairs tosealed components, all electrical supplies shall be disconnected from the equipment
being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an
electrical supply to equipment during servicing, then a permanently operating form of leak detection
shall be located at the most critical point to warn of a potentially hazardous situation.
2)Particular attention shall be paid tothe following to ensure that by working on electrical components,
the casing is not altered in such a way that the level of protection is affected. This shall include damage
to cables, excessive number of connections, terminals not made to original specification, damage to
seals, incorrect fitting of glands, etc. Ensure that apparatus is mounted securely. Ensure that seals or
sealing materials have not degraded such that they no longer serve the purpose of preventing the
ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer's
specifications.
9

NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection
equipment. Intrinsically safe components do not have to be isolated prior to working on them.
8. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads tothe circuit without ensuring that this will
not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe
components are the only types that can be worked on while live in the presence of aflammable
atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts
specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere
from a leak.
9. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or
any other adverse environmental effects. The check shall also take into account the effects of aging or
continual vibration from sources such as compressors or fans.
10. Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or detection
of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.
11. Leak detection methods
The following leak detection methods are deemed acceptable for systems containing flammable
refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity
may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a
refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for
the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant
10

12. Removal and evacuation
When breaking into the refrigerant circuit to make repairs or for any other purpose conventional
procedures shall be used. However, it is important that best practice is followed since flammability is a
consideration. The following procedure shall be adhered to:
Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge again with inert gas; Open the
circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed
with OFNto render the unit safe. This process may need to be repeated several times. Compressed air or
The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed
with OFNto render the unit safe. This process may need to be repeated several times. Compressed air or
oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system
with OFN and continuing tofill until the working pressure is achieved, then venting to atmosphere, and
finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system.
When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable
work totake place. This operation is absolutely vital if brazing operations on the pipe-work are totake
and shall be calibrated tothe refrigerant employed and the appropriate percentage of gas (25 %
maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of
detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and
corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/ extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from
the system, or isolated (by means of shut off valves) in a part of the system remote from the leak.
Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the
brazing process.
11

13.Charging procedures
In addition toconventional charging procedures, the following requirements shall be followed. Ensure
that contamination of different refrigerants does not occur when using charging equipment. Hoses or
lines shall be as short as possible to minimise the amount of refrigerant contained in them.
Cylinders shall be kept upright.
Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it
shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior
to commissioning. A follow up leak test shall be carried out prior to leaving the site.
14. Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the
equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely.
Prior tothe task being carried out, an oil and refrigerant sample shall be taken in case analysis is
required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before
the task is commenced.
a) Become familiar with the equipment and its operation. b) Isolate system electrically. c) Before
attempting the procedure ensure that: Mechanical handling equipment is available, if required, for
handling refrigerant cylinders;All personal protective equipment is available and being used correctly;
The recovery process is supervised at all times by a competent person; Recovery equipment and
place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is
ventilation available.
12

15. Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The
label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment
contains flammable refrigerant.
16. Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended
good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders,
ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct
number of cylinders for holding the total system charge is available. All cylinders to be used are
designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the
recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off
valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before
recovery occurs. The recovery equipment shall be in good working order with a set of instructions
concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants.
cylinders conform tothe appropriate standards. d) Pump down refrigerant system, if possible. e) If a
vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the
system. f) Make sure that cylinder is situated on the scales before recovery takes place. g) Start the
recovery machine and operate in accordance with manufacturer's instructions. h) Do not overfill cylinders.
(No more than 80 % volume liquid charge). i) Do not exceed the maximum working
pressure of the cylinder, even temporarily. j) When the cylinders have been filled correctly and the
process completed, make sure that the cylinders and the equipment are removed from site promptly
and all isolation valves on the equipment are closed off. k) Recovered refrigerant shall not be charged
into another refrigeration system unless it has been cleaned and checked.
13

In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall
be complete with leak-free disconnect couplings and in good condition. Before using the recovery
machine, check that it is in satisfactory working order, has been properly maintained and that any
associated electrical components are sealed to prevent ignition in the event of a refrigerant release.
Consult manufacturer if in doubt. The recovered refrigerant shall be returned tothe refrigerant supplier
in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants
in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed,
ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant
does not remain within the lubricant. The evacuation process shall be carried out prior to returning the
compressor tothe suppliers. Only electric heating tothe compressor body shall be employed to
accelerate this process. When oil is drained from a system, it shall be carried out safely.
14

- This appliance is not intended for use by persons (including children) with reduced physical, sensory or
mental capabilities or lack of experience and knowledge, unless they have been given supervision or
instruction concerning the use of the appliance by a person responsible for their safety.
- Children should be supervised to ensure that they do not play with the appliance.
-If the power cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly
qualified persons in order to avoid a hazard.
- Prior to cleaning or other maintenance, the appliance must be disconnected.
- Do not run cord under carpeting. Do not cover cord with throw rugs, runners, or similar coverings. Do
not route cord under furniture or appliances. Arrange the cord away from the traffic area and where it
willnot be tripped over.
- Never attempt to operate this appliance if it is damaged, malfunctioning, partially disassembled, or has
missing or broken parts, including a damaged cord or plug.
- To reduce the risk of fire or electric shock, do not use this unit with any solid-state speed control device.
- The appliance shall be installed in accordance with national wiring regulations.
- Contact the authorized service technician for repair or maintenance of this unit.
- Contact the authorized installer for the installation of this unit.
- When there are significant differences between features or operation implied by the remote control
illustration and the actual functions described in the USER MANUAL, the descriptions in the USER
MANUAL shall prevail.
15

Your installation location should meet the following requirements:
- Make sure that you install your unit on an even surface to minimize noise and vibration.
- The unit must be installed near a grounded outlet, and the Collection Tray Drain (found on the back of the unit) must be accessible.
- The unit should be located at least 19.7 inches from the nearest wall to ensure proper air conditioning.
- DO NOT cover the Intakes, Outlets, or Remote Signal Receptor of the unit, as this could cause damage to the unit.
Note About Fluorinated Gasses
- This air-conditioning unit is a hermetically sealed unit that contains fluorinated gasses. For specific information on the type of gas and the amount,
please refer to the relevant label on the unit itself.
- Service, maintenance, or repair of this unit must be performed by a certified technician.
- Product uninstallation and recycling must be performed by a certified technician according to local regulations.
NOTE:
All the illustrations in the manual are for explanation purposes only. Your air conditioner may be slightly different. The actual shape
shall prevail.
19.7inch
19.7inch
19.7 inch
16

Step Two: Install the exhaust hose assembly tothe unit
Step Three: Preparing the adjustable window slider
Align the unit adaptor of the exhaust hose assembly to the groove of the
air outlet opening on the back of the unit. Slide the exhaust hose
assembly along the direction indicated by the arrow for installation.
1. Depending on the size of your window, adjust the size of the window
slider.
2. If the length of the window requires two window sliders, use the bolt to
fasten the window sliders once they are adjusted to the proper length.
Press the exhaust hose into the window slider adaptor and the unit
adaptor. Each adaptor will snap into the exhaust hose automatically with
plastic clips.
Step One: Preparing the exhaust hose assembly.
- Medium Phillips screwdriver;
Suggested Tools
Accessories (Installation Kit)
-Tape measure or ruler;
-Knife or scissors;
-Saw (optional, to shorten window adaptor for narrow windows)
Your Window Installation Kit fits windows 26.5 – 48
"
and can be shortened
for smaller windows.
Unit adaptor Window slider
adaptor
Exhaust hose Exhaust hose assembly
17

Foam seal B (Short adhesive
foam seal for right and left sides)
Insert the window slider assembly
on the bottom sash channel. Use
care when installing the window
slider assembly, which will now
fit very tightly in the opening.
Close the sash tightly against the
top of the window slider assembly.
Insert the window slider assembly on the
left or right sides of the sash channel. Use
care when installing the window slider
assembly, which will now fit very tightly in
the opening. Close the sash tightly against
the other side of the window slider assembly.
Foam seal A
(Long adhesive
foam seal for top
and bottom sides)
Foam seal A
(Long adhesive
foam seal for
right and left
sides)
Foam seal B (Short adhesive
foam seal for top and bottom sides)
Window slider A
Window slider B
(if required)
18

inches the exhaust system to work
purposes
In order to ensure the optimal performance of our products, the design
specifications of the unit and remote control are subject tochange without
prior notice.
19
Note: This air conditioner exhausts hot air from the back of the unit
• While operating in cool mode, the exhaust hose will become warm to
the touch (this is normal).
• Having the exhaust hose overextended can cause radiant heat into the
room causing ineffective operation.
• The exhaust hose and adaptors must be installed according to the
installation instructions so the warm air from the exhaust is vented
outside.
Table of contents
Other Ocean Breeze Air Conditioner manuals

Ocean Breeze
Ocean Breeze OBZ-12NPF User manual

Ocean Breeze
Ocean Breeze OBZ-06CR User manual

Ocean Breeze
Ocean Breeze OBZ-06CR3 User manual

Ocean Breeze
Ocean Breeze OBZ-05CM User manual

Ocean Breeze
Ocean Breeze OBZ-10ESN User manual

Ocean Breeze
Ocean Breeze OBZ-08NPE User manual

Ocean Breeze
Ocean Breeze OBZ-08CM User manual

Ocean Breeze
Ocean Breeze OBZ-05CMN3 User manual

Ocean Breeze
Ocean Breeze OBZ-10PE User manual

Ocean Breeze
Ocean Breeze OBZ-14PE User manual