STANDARD FEATURES
CABINET
The CAC1211 Series spot cooler has a cabinet that is constructed of 18 gauge steel with
a polyester powder coated finish. The matte black finish compliments any surrounding
space, and the cabinet is lined with sound-absorbing insulation for cool, quiet comfort.
The CAC1211 comes equipped with handles and premium swivel casters for portability
and convenient set-up.
DELUXE ELECTRONIC CONTROLLER
The CAC1211 unit is equipped with deluxe electronic controller. When power is connect-
ed to the unit, the thermostat will control the unit to cool a space to the desired tempera-
ture. The thermostat is also capable of controlling the fan to operate automatically (when
needed) or continuously.
AUTO RESTART (FEATURE)
The controller has auto-restart capability. A built-in memory retains the settings, and the
unit will restart to the last set point automatically, after a power failure.
FAN SPEED CONTROL
One of the features of the electronic controller is that the unit supply fan can be controlled
automatically or manually. In AUTO mode, the evaporator blower will adjust air flow auto-
matically for added comfort and performance Or if desired, the fan speed can be set to
MANUAL mode and the evaporator blower will run continuously at one of six levels of fan
speed.
CONDENSATE RESERVOIR/TANK
The CAC1211 unit comes equipped with a Condensate Reservoir Tank for handling the
condensate generated during the cooling process. When the tank is full, the word CON
will be displayed. The tank can be easily removed from the unit and emptied as required.
FILTERS
CAC1211’s are equipped with washable filters at the air intakes. Electrostatic mesh air
filters located behind the evaporator return air grill serve to filter the air before it is cooled,
and behind the condenser return air grill to prevent dust build-up. Both filters can be
easily removed and cleaned.
HIGH PRESSURE SAFETY SWITCH
Located on the back of the CAC1211 is a manual re-set high pressure switch, used for
the protection of the compressor. If the condensing pressure exceeds the limit setting, the
cut-out shuts down the compressor, while the evaporator fan remains running. The dis-
play will indicate CON. The compressor can be re-started, once the condensing pressure
has lowered, by depressing the “RESET” button.
POWER CORDS
CAC1211 units come with a 10 ft. power cord, allowing for convenient connection and
portability. The power cord is equipped with a Leakage Current Detection Interrupt
(LCDI) device for added safety.
3