The OmniMetrix (OMNI) TrueGuard PRO monitor, with Modbus TCP functionality,
comes with default network configurations, and since it is easy to configure the
network settings on the PowerZone (PZ) control in the field, please configure the PZ
as follows:
The OMNI unit is configured for these network values:
IP Address: 10.0.1.202
Subnet Mask: 255.255.0.0
Gateway: 10.0.1.1
For a single PZ control, set the following:
Modbus Slave ID = 1
IP Address: 10.0.1.101
Subnet Mask: 255.255.0.0
Gateway: 10.0.1.1 (this is not important)
If multiple PZ controls are to be connected, such as in an MPS
configuration, use the following: