
Section
3.
DC
Control
CONTROL
DESCRIPTIONS
The following function and operation descriptions
includesoptions. Refertothoseapplicabletoyour spe-
cific controlgroup. See Figure
3-1.
OilPressure Gauge: Indicatespressure of lubricating
oil in engine (wired to a sensor unit located on the
engine).
Water Temperature Gauge: Indicates temperature of
circulating coolant in engine (wired to a sensor unit
locatedon the engine.
BatteryChargeRateDCAmmeter: Indicatesthebattery
charging current.
OilTemperatureGauge:Indicates temperatureof lubri-
catingoilinengine(wiredtoasensorunitlocatedonthe
engine).
Tachometer: Provides constant monitoring of engine
r/min.
Speed
Adjust
Potentiometer: Operator control for
adjusting engine r/min (used with electronicgovernor
only).
Run-Stop-Remote Switch: Starts and stops the unit
locally, or from a remote location wired to the control
enginemonitor board.
Reset, LampTest, PanelLampSwitch: Resetsthefault
circuitonlywhenthe Run-Stop-Remoteswitchisinthe
Stop (Reset) position. Tests fault lamps (except
2
light
control)and turns on the control panel lamp.
Preheat Switch: Used with diesel engines to provide
momentary warm-up of glow plugs.
Running Time Meter: Registers the total number of
hoursthat the unit has run. Use itto keepa recordfor
periodicservicing.Time iscumulative;meter cannot be
reset.
ControlPanelLamp: Conveniencelightfor operator.
lndicator Lamps: Refer to the following control group
descriptions.
Detector
2
Control
The standard control panel has two monitor system
indicatorlamps.
ThegreenRUNlampcomesonassoonasbothprimary
and secondary starter disconnect circuits are opened
after unit starting. The red FAULT lamp will come on
when-an emergency shutdown of the generator set
occursfrom oneof thefollowing conditions:
0
Low oil pressureduring unitoperation
0
Highenginetemperature during unitoperation
0
Overspeedof engineduring unitoperation
0
Overcrankconditionduring starting
Detector
12
Control
The twelve monitor system option features indicator
lampsfor thefollowing:
0
RUN (green) lamp comes on when both starter dis-
connectcircuits are opened after unitstarting.
0
PRE LO
OIL
PRES(yellow)indicatesengineoil pres-
sure is marginallylow.
0
PREHIENGTEMP(yellow)indicatesenginetemper-
ature is marginallyhigh.
0
LO OIL PRES (red)indicatesengine has shut down
becauseof critically low oil pressure;
0
HI ENG TEMP (red)indicatesengine has shut down
becauseof critically hightemperature.
0
OVERSPEED (red) indicates engine has shut down
becauseof excessivespeed.
0
OVERCRANK (red) indicates the starter has been
lockedout becauseof excessivecrankingtime.
0
FAULT
1
(red)anundedicatedfault. Mightbefactory
programmedasashutdownornon-shutdown,andas
atimedornon-timedfault.(Normallysetfortimedshut-
down.)
0
FAULT
2
(red)samefeaturesas Fault
1.
(Normallyset
for immediateshutdown.)
0
LO ENG TEMP (yellow) enginetemperatureismar-
ginally lowfor starting.Indicatesinoperativecoolant
heater.
1
0
LOFUEL (yellow) indicates fuel supply is margi-
0
SWITCHOFF(flashingred)indicatesgeneratorsetis
nallylow.
not
in
automatic startoperationmode.
0
RUN(green)
0
FAULT(red)
3-1
Redistribution or publication of this document,
by any means, is strictly prohibited.