
Frost protection system JVA/JVS
Temperature and humidity sensors | Data sheet No. 20670 | Version 04-2014 | 1| 4
S1
TE 1000
Sensor
S2
S3
* Pt 1000
Ni 1000-LG
*Factory setting
S1 on, S4 off = TE2000
Range setting possible with jumpers.
Jumpers S1 – S3 are located directly behind the front panel,
which is removed from the front.
Jumper S4 is located on the mother board next to the terminal
block.
Technical Data
JVA JVS
Power supply: 24 V AC/DC
Power rating: 2 VA
Alarm setpoint: 0 – +16 °C
Output: 0 – +10 V
Controller input: 0 – +10 V
Sensor input: NI 1000 LG
Starting point of
restriction: 3 °C > alarm 3 – 16 °C
Rate of increase (P range): 2 °C xed 1 – 8 °C
Sensor range
for warming: – 0 – 50 °C
Blower relay
contact load: 6 A, 230 V
Alarm for DDC input: 1 A, 60 V
Ambient temperature: 0 – 40 °C
Dimensions: 53 x 90 x 61 mm (L x W x D)
• 2-phase freeze protection - analog / digital
• Control unit in the control panel
• Average sensor TA-NI1000LG-I-... / TA-PT1000-I-...
or insertion sensor T-NI1000LG-I-... / T-PT1000-I-...
connectible
• Warming and startup circuit for type JVS
• Independent of controller manufacturer
• Temperature-output signal 0 – 10 V
• On short circuit or broken cable →
frost protection status
Applications
The 2-phase frost protection controller is an electronic monitor
for heating registers in ventilation systems to prevent freezing
at low outside temperatures.
Function
When a temperature behind the heating register or the return
ow water drops below a threshold, the control valve (0 – 10 V)
opens as a rst sequence (the green„Restriction“ LED blinks). If
the temperature continues to decline, the second sequence of
the relay switches the blower o (in hardware circuit). The red
LED lights up and the control unit is locked. Reset is only pos-
sible by pressing the internal reset button or by briey cutting
power. An additional relay contact signals„Risk of Freezing“ to
the automation station.
A second potentiometer on type JVS is used to set the warming
temperature to 0 – 50 °C if the blower is switched o. This is also
advantageous when restarting in cold outside temperatures
(startup circuit).
Attention!
The control unit triggers a freeze alarm if the temperature
sensor has a defect, on short circuit or a broken cable: Valve
open – locking – message to DDC. The blower is switched o
during a power outage - the control valve closes.