RS422
Option Module B supports both 2-wire (simplex) and 4-wire (duplex) RS422 communications. RS422 is a
differential communications scheme and uses the polarity difference between the + and – leads to transmit
the data bits. The signals input on pins 1 and 2 at one end of the link are transmitted to the other end of the
link and are output on pins 3 and 4.
Different manufacturers mark their RS422 devices in different ways and there is no consistent common
terminal marking scheme. In RS422, when there is no data activity, the system is said to be in a mark state.
During data transmission, the system toggles between mark and space states. During idle (mark state), when
no data is being transmitted, the output + terminal will be positive with reference to the output – terminal.
Care must be taken to ensure that external equipment has its output terminals connected to the external
equipment input terminals. Connect + to + (plus) and – to – (minus).
RS422 is a “one-to-many” type system, permitting up to 10 receivers to be electrically connected to one
transmitter. Refer to the “Termination Rules for RS422, RS485, and Manchester” on page 15 for more details
on terminations to ensure you have terminated multiple connections correctly. Fiber connections isolates
each end of a system, effectively creating more than one electrical buss. A system controller for Pan, Tilt, and
Zoom (PTZ) could connect to up to 10 B-type Option Module inputs, with only the last input having the
termination enabled. At the other end of each link, each RS422 output could drive 10 more inputs. Since this
end of the link is optically isolated from the transmit end, it must be treated as a separate system and should
have the last input in the daisy chain terminated.
Although RS422 and RS485 are differential input communications standards and are more immune to noise
caused by poor grounding and electrical noise, the shielding and grounding of the signal wires is still important.
Signal grounds and shields should be connected at both ends on most signal runs. When the ground potential
of one end of the electrical connection is at a different potential than the other, the voltage differential can
exceed the maximum common mode immunity of the input circuits and cause improper operation of the
equipment. If this voltage should become exceedingly large due to lightning or static buildups, damage to the
signal inputs is possible. Connecting the ground (and shield) connections on both ends reduces this potential.
Data connections in outdoor locations (traffic and external security systems, for example) are especially
vulnerable to these kinds of problems and should have grounds connected at both ends of the wiring. In
addition, power, data, and video signals should have noise and surge protection modules installed in the lines
ahead of the communications equipment.
Refer to the section on “Termination Rules’ for more details on RS422 termination.
8
TABLE B-4 — OPTION MODULE B RS422 SIGNALS AND CONNECTIONS
Pin Number Function
1 Input +
2 Input –
3 Output +
4 Output –
5 Signal Common