AC810 Series LCD on-off Thermostat
Only cooling
2 pipe system controls fan coil and 2-wire motorized valve.
n Cooling mode: When reaching set-point, the valve closes
in fan auto mode
,
the fan turns to low; n fan manual mode, the fan will stay at the manual position.
5. Keys
: Power, turn on/off the system
M: Press it for 3 seconds to select sleeping function
: Adjust auto, high, mid, low fan speed.
: Temperature up or adjusting work mode
: Temperature down or adjusting work mode
6. Operating Instruction
6-1
:
::
:
Set the temperature
Press “▲” and “▼” to set the temperature
6-2: Fan spee
Press Fan to adjust high, mid, low fan speed and auto
6-3: Sleep function
Press “M” for 3 seconds, it flashes, press “▲” to confirm, press “▼”to cancel.
f thermostat has been powered off, the sleep mode setting will be canceled. Once thermostat is powered on,
sleep mode has to be set reset if needed.
How the sleep mode works:
Mode Set-point
Sleep hours and energy-saving temp
0h
~
1h 1h
~
2h 2h
~
8h > 8h
Cooling mode
22
℃
22
℃
23
℃
24
℃
22
℃
Heating mode 22
℃
21
℃
20
℃
19
℃
22
℃
For example: n cooling mode, when the set-point is 22
℃
and you choose sleep mode:
n 0-1 hour, the set-point is still 22
℃
,
n 1-2 hours, the set-point would be 23
℃
,
n 2-8 hours, the set-point would be 24
℃
,
After 8 hours, the set-point would go back to the 22
℃
.
(Note: When in sleep mode, the LCD would always show the set-point at 22
℃
.)
7.Data setting
During power off, press” M” and “ ” in the same time for 5 sec to enter adjustment mode. Then press” M”
button to select between mode 1 and mode 2
mo e1: Room Temperature Calibration A justment:
“▲”UP for increase the temperature compensation
“▼”DOWN for decrease the temperature compensation
Temperature compensation settings range are from -9
℃
~9
℃
(the best operation is at -1
℃
)
Adjust the temperature you want, and then confirm by turn-on.