Initial Operation:
Before cycling the weir gate, make sure there are no foreign deposits or materials on the seals, guides or sealing
area. Gate seals could be damaged if the area is not cleaned and coated with a light grease. Please refer to section
“
Materials needed for maintenance and seal replacement
” for detailed information about the grease type.
•Manual
Apply a light grease on the stem before initial operation after the installation. If the operation is difficult due
to high torque, stop operation of the gate and check stem alignment.
•Electric actuator
oRefer to the electric actuator manufacturer instruction manual before commissioning the weir gate
oElectric actuators must be limited with limit and torque switches. Electric actuators without these limiters shall
not be used with ORBINOX weir gate. Electric actuators must be adjusted at the time of installation on site
(except in the case of a self-contained frame and yoke-mounted actuators; in this case the motor is factory-
set). To adjust the limit switches, follow the next instructions using values of the GAD:
▪Position the slide in the nearly closed position (leave 10mm /0,40” open). From this
position, manually (using the handwheel) operate the slide until it is completely closed
(check tightness with a 0,05mm/0,002” gauge). In this position, set the limit switch for the
CLOSED position
▪Position the slide in the nearly open position (leave 10mm /0,40” closed). From this
position, manually (using the handwheel) operate the slide until it is completely open. In
this position, set the limit switch for the OPEN position
oBe aware when the gate is almost fully OPEN or CLOSED. If the gate does not stop once the fully open or
fully closed position is reached, stop immediately and correct adjusting again the limit and torque switches
Operation:
•CAUTION! Do not force the operator to close the gate, as it may cause damage to the stem and it does not
improve the sealing system. The maximum applicable force on the handwheel is 25 kg /55 lbs
• The RB weir gate is closed by a clockwise rotation, and opened (downwards) by a counter-clockwise rotation of
the operator
• The RB weir gate is designed to be self-locking, so that the slide maintains its position in open, close or
intermediate positions