5
Operation description
After switching on, controller is in , , which is signaled by adequate diode. Operation
starts after pressing or automatically, when boiler’s temperature increases above operating
threshold – temperature difference between set temperature and DT parameter set in the service
menu. Status is automatically activated after 30 minutes since temperature decrease
below operating threshold. CONTROL socket which is located at the back panel of the controller
is for connection of remote control EKOSTER CONTROL.
Buttons and służą do zmiany nastaw. During boiler operation, pressing or causes
possibility to change desired boiler’s temperature. Pressing and withholding button causes
increase of speed of temperature changing
Pressing button causes:
• temperature below operating threshold:turning on/off of the controller signaled with diodes
or ,
• at temperature above operating threshold:fan operation blockade signaled by blinking
, diode, which makes possible to stoke the boiler. Return to automatic operation after
pressing button.
A T T E N T I O N !
Displaying „Er” on the controller informs about temperature increase above 99 °C,
below -9 °C or boiler sensor damage. To secure the boiler till sensor replacement,
pump will be automatically activated.
COMFORT SYSTEM
COMFORT SYSTEM function in controller prevents pump’s rotor from stone deposition.
Controller automatically activates pump after heating season for 30 seconds every 14 days.
Pump operation in this mode is signaled with ashing POMPA diode. Function activates after
1 minute since controller’s activation. Pump activation in this mode causes that 14 days period is
counted at the beginning.
Freezing and overheating function
Controller enables to turn on circulation pump In case if temperature drops to 4 °C or lower.
Exceeding 97°C causes fan to turn off and circulation pump activation. Boiler overheating is
signaled with ashing diode. In such a case it is recommended to determine cause
of overheating, eliminate and turn on the boiler pressing button. Pump is activated
permanently In case of boiler sensor damage.
Blow-through
• Press and hold for 3 s till diode starts blinking,
• przyciskami , are for blow-through time setting in seconds,
• Press dtill diode starts blinking,
• With buttons , set blow- through pause in minutes,
• Press .
From now on controller at temperatures higher than set one will activate blow-through.