OUMAN TCR-10 User manual

TCR-10
Room unit
Technical information
Accuracy of measurement:
Measuring element:
Display:
Power supply:
Power consumption:
Protection class:
Dimensions:
+0.5 °C
NTC-10
LCD
24 VAC +10%, 50 Hz / 60 Hz
1 VA
IP 20 (dry conditions)
H = 86 mm
D = 23 mm
W = 86 mm
H
W
D
M
TCR-10 is a smart room unit that has been developed to operate together with Ouman Plus home au-
tomation system.The room unit makes it possible to monitor and control the temperature of specic
rooms and also change a room’s “Normal temperature” setting. You can also use the room-specic
unit to increase ventilation and change the home state control to “Night” and to ”Home”. A maximum
number of Ouman TCR-10 room units is 8 and they can be connected to Ouman Plus.
Connection of Ouman TCR-10
Image 1. Connection of OumanTCR-10
Installation and connection of Ouman TCR-10
Flip the Dip switch 1 of the
last TCR-10 on the bus to
the ON position (= ter-
minating resistor 120 Ω).
Make this change even if
there is only one room unit
on the system.
ON
1 2 3 4 5
DIP
Open the Ouman
TCR-10’s rear panel
with a screwdriver.
Phase 1 Phase 2
Make the necessa-
ry connections (see
image 1 and 2).
Phase 3
Attach the cover to
the wall with
screws.
Phase 4 Phase 5
Press the front panel
in place and proceed
to phases 6 and 7. The
sensor element must
be perpendicular to the
circuit board in relation
to (avoid refraction).
Refraction causes a
measurement error!
Connect Ouman TCR-10 to Ouman Plus centre’s 24 VAC strip
connectors to obtain operating voltage.
Connect TCR-10 to Ouman Plus’s A1 and B1 Modbus connec-
tors.
TMF-3M oor sensor connection to TCR-10. Ouman Plus sys-
tem can utilize the oor sensor’s measurement information to
limit the temperature of the oor (minimum and maximum).
COM
~
A
B
Input
RS
24 VAC
Modbus
(Nomak 2x2x0,5+0,5)
TMF-3M
Room unit
OUMAN TCR-10
OUMAN OY
www.ouman.fi
ouman@ouman.fi
Southern Finland sales office
Upseerinkatu 3 C Tel. +358 424 840 202
FI 02600 Espoo Fax +358 9 4780 1030
Factory and headquarters
Voimatie 6 Tel. +358 424 8401
FI 90440 Kempele Fax +358 8 815 5060

TCR-10
Room unit
Setting bus addresses for OumanTCR-10
Each Ouman TCR-10 room-specic unit must have its own bus
address. If two or more bus devices have the same address, the
bus connection will not work. Change bus addresses of room-
specic units as follows:
Note! Follow the instructions carefully! Changing the wrong
device parameter may cause the device to operate incorrectly.
Press the On/Off button ( ) to turn off the power to the TCR- 10 unit.
Hold the Mbutton down until the power is turned on.
The unit is now in the programming mode and the display will look
like image 3 on the left.
Press the Mbutton so many times that the display looks like ima-
ge 4 on the left. The bus address parameter’s serial number is 12.
Use the and buttons to change the bus address.
When the bus address has been changed, the room-specic unit
will automatically switch to a powerless state if the keyboard is not
touched.
Press the button to turn on the power to the room-specic unit.
Bus address parameter
Bus address
Modbus connection of Ouman TCR-10
When you connect severalTCR-10 units to Ouman Plus system, you must make the bus connection according to
the diagram 2. Room-specic temperatures are controlled via the I/O expansion unit connected to Ouman Plus.
Connect relay 1 (R1) of the I/O extension unit (= EH-686) so that it controls heating of the room whose room-
specic Modbus address is 1. Using the same principle, connect Modbus addresses 2-8 to relays 2-8.
Image 4. OUMAN TCR-10 bus
address setting.
Image 3. OUMANTCR-10
room unit is in programming
mode.
Phase 6
*) Flip the Dip switch 1 of the last TCR-10 on the bus to the ON position (= terminating resistor 120 Ω). Make
this change even if there is only one room-specic unit. See the image 2 on the top.
NOTE! Normally the bus addresses of the room units are set to at the factory (see label indicated on the packaging).
*
Image 2. Connection of OumanTCR-10 to Ouman Plus system via Modbus.
OUMAN TCR-10
A
A1
B
B1
~
24 ~
OUMAN TCR-10
A B ~
24 ~
OUMAN TCR-10
A B ~
24 ~
NOMAK 2x2x0,5+0,5
OUMAN PLUS
MODBUS
OUMAN TCR-10
A B ~
24 ~
OUMAN TCR-10
A B ~
24 ~
OUMAN TCR-10
A B ~
24 ~
OUMAN TCR-10
A B ~
24 ~
OUMAN TCR-10
A B ~
24 ~
Room 1 Room 2 Room 3 Room 4 Room 5 Room 6 Room 7 Room 8
Terminating resistor1
120 Ω

User interface of Ouman TCR-10
The rst time you press any button, only the display backlight will light up (settings will not change).
TCR-10
Room unit
Phase 7
= night state control is active Press the Mbutton. A symbol indicating the “Night” state cont-
rol will appear in the display. Press the Mbutton again to go from
“Night” state control back to ”Home” state control.
Night state control
When you press the On/Off ( ) button to turn off the power to the
room unit, the temperature level in that room will swicth to ”Big tem-
perature drop” (specied in Ouman Plus).
Room-specic big temperature drop
= automatic, ventilation control
according to home state control
= ventilation boost 0.5 h
= ventilation boost 1.0 h
= ventilation boost 1.5 h
Press the ventilation boost button ( ).
The symbol appearing in the display indicates in half-hour increments
how much ventilation enhancement is left.
Ventilation boost
You can lock the keyboard so that you can not use the Ouman
TCR-10 room-specic unit in question to make any changes. Press
the and buttons at the same time for 10 seconds to al-
ternately lock and unlock the keyboard.
Locking the unit
The TCR-10 room-specic unit can be used to change a room’s ”Nor-
mal temperature” setting. Press the or button to go to the
setting’s edit mode. Use the and buttons to change the set-
ting. To change the room temperature settings ”Small temperature
drop” and ”Big temperature drop” you need to go to Ouman Plus UI.
Changing room temperature settings
Idle mode
The room unit requests more heat
The symbol appearing in the display indicates that room tempe-
rature is at the desired level.
If the symbol appears in the room-specic unit’s display, the
unit is requesting more heat from the heating controller.

OUMAN OY
www.ouman.fi
ouman@ouman.fi
Southern Finland sales office
Upseerinkatu 3 C Tel. +358 424 840 202
FI 02600 Espoo Fax +358 9 4780 1030
Factory and headquarters
Voimatie 6 Tel. +358 424 8401
FI 90440 Kempele Fax +358 8 815 5060
TCR-10_UK_20140507
Popular Thermostat manuals by other brands

Honeywell Home
Honeywell Home RTH7500 Series Quick installation guide

Young Regulator
Young Regulator T-720 Series installation manual

Interlogix
Interlogix IS-ZW-TSTAT-300 Operation guide

OJ Electronics
OJ Electronics MSW4-10 Instruction

OERTLI
OERTLI OEtroSmart technical information

Siemens
Siemens RDF300.02/SRL Mounting instructions

Johnson Controls
Johnson Controls TEC2102-3 installation instructions

KingShield
KingShield TH90 installation instructions

Full Gauge Controls
Full Gauge Controls Microsol Ri manual

Enerset
Enerset Cube instructions

Lux Products
Lux Products PSDH121 SERIES Installation and operating instructions

Vaillant
Vaillant VRT 392f OPERATING AND INSTALLATION Manual