Outback EnergyCell User manual

EnergyCell Battery
Owner’s Manual

About OutBack Power Technologies
OutBack Power Technologies is a leader in advanced energy conversion technology. OutBack products include true
sine wave inverter/chargers, maximum power point tracking charge controllers, and system communication
components, as well as circuit breakers, batteries, accessories, and assembled systems.
Audience
This manual is intended for use by anyone required to install and operate this battery. Be sure to review this manual
carefully to identify any potential safety risks before proceeding. The owner must be familiar with all the features and
functions of this battery before proceeding. Failure to install or use this battery as instructed in this manual can result
in damage to the battery that may not be covered under the limited warranty.
Grid/Hybrid™
As a leader in off-grid energy systems designed around energy storage, OutBack Power is an innovator in Grid/Hybrid
system technology, providing the best of both worlds: grid-tied system savings during normal or daylight operation,
and off-grid independence during peak energy times or in the event of a power outage or an emergency. Grid/Hybrid
systems have the intelligence, agility and interoperability to operate in multiple energy modes quickly, efficiently, and
seamlessly, in order to deliver clean, continuous and reliable power to residential and commercial users while
maintaining grid stability.
Contact Information
Address:
Corporate Headquarters
17825 – 59th Avenue N.E.
Suite B
Arlington, WA 98223 USA
European Office
Hansastrasse 8
D-91126
Schwabach, Germany
Telephone:
+1.360.435.6030
+1.360.618.4363 (Technical Support)
+1.360.435.6019 (Fax)
+49.9122.79889.0
+49.9122.79889.21 (Fax)
Email:
Support@outbackpower.com
Website:
www.outbackpower.com
Disclaimer
UNLESS SPECIFICALLY AGREED TO IN WRITING, OUTBACK POWER TECHNOLOGIES:
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER
INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT, INDIRECT, CONSEQUENTIAL
OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION
WILL BE ENTIRELY AT THE USER’S RISK.
Information included in this manual is subject to change without notice.
Notice of Copyright
EnergyCell Battery Owner’s Manual © December 2013 by OutBack Power Technologies. All Rights Reserved.
Trademarks
OutBack Power is a registered trademark of OutBack Power Technologies. The ALPHA logo and the phrase “member
of the Alpha Group” are trademarks owned and used by Alpha Technologies Inc. These trademarks may be registered
in the United States and other countries.
Date and Revision
December 2013, Revision C
Part Number
900-0127-01-00 Rev C

900-0127-01-00 Rev C 3
Table of Contents
Important Safety Instructions ........................................................................4
Additional Resources ..........................................................................................................................................................4
EnergyCell Batteries......................................................................................5
Welcome to OutBack Power Systems ...........................................................................................................................5
EnergyCell GH Front Terminal .........................................................................................................................................5
EnergyCell RE.........................................................................................................................................................................6
Top Terminal........................................................................................................................................................................................... 6
Front Terminal ....................................................................................................................................................................................... 6
Materials Required...............................................................................................................................................................7
Tools........................................................................................................................................................................................................... 7
Accessories.............................................................................................................................................................................................. 7
Storage and Environment Requirements....................................................................................................................7
Temperatures ......................................................................................................................................................................................... 7
Self-Discharge ........................................................................................................................................................................................ 7
Capacity ...................................................................................................................................................................................8
State of Charge......................................................................................................................................................................8
System Layout .......................................................................................................................................................................9
Battery Configurations ....................................................................................................................................................................... 9
DC Wiring ............................................................................................................................................................................. 11
Commissioning .................................................................................................................................................................. 13
Charging (EnergyCell GH) .............................................................................................................................................. 13
Float Charge .........................................................................................................................................................................................13
Freshening Charge.............................................................................................................................................................................14
Charging (EnergyCell RE)................................................................................................................................................ 14
Bulk Stage..............................................................................................................................................................................................14
Absorption Stage................................................................................................................................................................................14
Float Stage.............................................................................................................................................................................................15
Freshening Charge.............................................................................................................................................................................15
Notes on EnergyCell RE Charging ................................................................................................................................................15
Temperature Compensation......................................................................................................................................... 15
Remote Temperature Sensor.........................................................................................................................................................16
Improper Use ...................................................................................................................................................................... 16
Troubleshooting and Maintenance ..............................................................17
Periodic Evaluation........................................................................................................................................................... 18
Specifications .............................................................................................19

Safety Instructions
4 900-0127-01-00 Rev C
Important Safety Instructions
READ AND SAVE THESE INSTRUCTIONS!
This manual contains important safety instructions for the EnergyCell battery. These instructions are in addition
to the safety instructions published for use with all OutBack products. Read all instructions and cautionary
markings on the EnergyCell battery and on any accessories or additional equipment included in the installation.
Failure to follow these instructions could result in severe shock or possible electrocution. Use extreme caution at
all times to prevent accidents.
WARNING: Personal Injury
Some batteries can weigh in excess of 100 lb (45 kg). Use safe lifting techniques
when lifting this equipment as prescribed by the Occupational Safety and Health
Association (OSHA) or other local codes. Lifting machinery may be recommended
as necessary.
Wear appropriate protective equipment when working with batteries, including
eye or face protection, acid-resistant gloves, an apron, and other items.
Wash hands after any contact with the lead terminals or battery electrolyte.
WARNING: Explosion, Electrocution, or Fire Hazard
Ensure clearance requirements are strictly enforced around the batteries.
Ensure the area around the batteries is well ventilated and clean of debris.
Never smoke, or allow a spark or flame near, the batteries.
Always use insulated tools. Avoid dropping tools onto batteries or other
electrical parts.
Keep plenty of fresh water and soap nearby in case battery acid contacts skin,
clothing, or eyes.
Wear complete eye and clothing protection when working with batteries. Avoid
touching bare skin or eyes while working near batteries.
If battery acid contacts skin or clothing, wash immediately with soap and water.
If acid enters the eye, immediately flood it with running cold water for at least
20 minutes and get medical attention as soon as possible.
Never charge a frozen battery.
Insulate batteries as appropriate against freezing temperatures. A discharged
battery will freeze more easily than a charged one.
If a battery must be removed, always remove the grounded terminal from the
battery first. Make sure all devices are de-energized or disconnected to avoid
causing a spark.
Do not perform any servicing other than that specified in the installation
instructions unless qualified to do so and have been instructed to do so by OutBack
Technical Support personnel.
Additional Resources
These references may be used when installing this equipment. Depending on the nature of the installation, it
may be highly recommended to consult these resources.
Institute of Electrical and Electronics Engineers (IEEE) guidelines: IEEE 450, IEEE 484, IEEE 1184, IEEE 1187, IEEE
1188, IEEE 1189, IEEE 1491, IEEE 1578, IEEE 1635, and IEEE 1657 (various guidelines for design, installation,
maintenance, monitoring, and safety of battery systems)

900-0127-01-00 Rev C 5
EnergyCell Batteries
Welcome to OutBack Power Systems
Thank you for purchasing the OutBack EnergyCell battery. EnergyCell is a series of absorbed glass-mat (AGM)
batteries with a valve-regulated lead-acid (VRLA) design. They are designed to provide long, reliable service with
minimal maintenance. Several versions are available, including front-terminal and top-terminal designs.All
have high recharge efficiency and a compact footprint for higher energy density. All have a thermally welded
case-to-cover bond to eliminate leakage, all are 100% recyclable, and all are UL-recognized components.
EnergyCell GH Front Terminal
The EnergyCell GH (Grid/Hybrid) Series uses pure lead plates. It is intended to receive continuous float charging
under normal conditions when utility power is present.
Intended for use with Grid/Hybrid™ systems, particularly grid-interactive or grid-backup (float service) applications
with occasional interruptions but minimal cycling
Pure lead plates for long float service life in battery backup applications
Extended shelf life
Figure 1 EnergyCell GH Front Terminal Battery
4.9” (12.6 cm)
22.1” (56.1 cm)
11.1”
(28.3 cm)
EnergyCell
200GH
12.4”
(31.6 cm)
EnergyCell
220GH

Installation and Operation
6 900-0127-01-00 Rev C
EnergyCell RE
The EnergyCell RE (Renewable Energy) Series uses pasted lead-calcium-tin plates. It is designed for regular
discharge/charge cycles. The EnergyCell RE is available in both top-terminal and front-terminal designs.
Intended for use in backup, off-grid, and renewable energy (RE) sites with OutBack inverters, charge controllers,
and other devices that require the use of deep-cycle batteries
Lead-calcium-tin alloy plates for long life in both cycling and float applications
High-density pasted plates for high cycle life
Top Terminal
Figure 2 EnergyCell RE Top Terminal Battery
Front Terminal
Figure 3 EnergyCell RE Front Terminal Battery
13.4” (34.1 cm)
8.5”
(21.6 cm)
6.8”
(17.3
EnergyCell RE Top Terminal Dimensions
Model
Length Height Width
34RE
6.8” (17.3 cm) 7.8” (19.7 cm) 5.2” (13.2 cm)
52RE
8.1” (20.5 cm) 9.0” (22.9 cm) 5.5” (13.9 cm)
78RE
8.0” (20.3 cm) 10.8” (27.3 cm) 6.8” (17.3 cm)
95RE
8.1” (20.5 cm) 12.5” (31.8 cm) 6.8” (17.3 cm)
106RE
(shown)
8.5” (21.6 cm) 13.4” (34.1 cm) 6.8” (17.3 cm)
4.9” (12.6 cm)
11.1” (28.3 cm)
EnergyCell 170RE
12.6” (32.0 cm)
EnergyCell 200RE
22.1” (56.1 cm) EnergyCell 170RE
22.0” (55.9 cm) EnergyCell 200RE

EnergyCell Batteries
900-0127-01-00 Rev C 7
Materials Required
Tools (use insulated tools only)
Torque wrenches
Voltmeter
Accessories
Interconnect bar (provided with front terminal batteries only)
Terminal cover (provided with front terminal batteries only)
Hardware kit
Interconnect cables as needed
CAUTION: Fire Hazard
Install properly sized battery cabling and interconnect cables. The cable
ampacity must meet the needs of the system, including temperature, deratings,
and any other code concerns.
Storage and Environment Requirements
Temperatures
EnergyCell batteries should not be operated in an environment where the average ambient
temperature exceeds 85°F (27°C). The peak temperature of the operating environment should not
exceed 110°F (43°C) for a period of more than 24 hours. High operating temperatures will shorten a
battery’s life (see page 8).
Do not allow batteries to freeze, as this will damage them and could result in leakage.
Do not expose batteries to temperature variations of more than 5°F (3°C). This leads to voltage
imbalance between multiple batteries (or between battery cells if there is a temperature differential).
Batteries should be stored in a cool, dry location. Place them in service as soon as possible. The best
storage temperature is 77°F (25°C), but a range of 60°F (16°C) to 80°F (27°C) is acceptable.
Self-Discharge
All EnergyCell batteries will discharge over time once charged, even in storage. Higher storage temperatures
increase the rate of self-discharge. The EnergyCell GH has a longer shelf life than other VRLA batteries,
including the EnergyCell RE. At room temperature (77°F or 25°C), the EnergyCell GH has a shelf life of 18 months
before self-discharging to unacceptable levels. Figure 4shows the rate of EnergyCell GH self-discharge at
various temperatures.
Fully charged, the natural (“rest”) voltage of all
EnergyCell batteries is approximately 12.8 Vdc.
A battery should have a freshening charge (see
pages 14 and 15) if its rest voltage is below
12.5 Vdc per battery (2.08 Vdc per cell).
A battery should not be used if its rest voltage
is 12.0 Vdc or lower upon delivery. Contact the
vendor upon receiving a battery in this state.
No EnergyCell should ever be permitted to
self-discharge below 70% state of charge
(SoC). Such as condition is highly detrimental
and will shorten battery life. (This situation is
not the same as discharging to 70% SoC or
lower under load. See page 8.)
Figure 4 EnergyCell GH Shelf Life
0 6 12 18 24 30 36 42 48
Months
2.17
2.16
2.15
2.14
2.13
2.12
2.11
2.10
Rest Volts per cell
Approximate %
State of Charge
100
96
91
87
83
79
74
70
40°C
10
4°F
30°C
86°F
25°C
77°F
20°C
68°F
10°C
50°F

Installation and Operation
8 900-0127-01-00 Rev C
Figure 5 Battery Life
70°F 80°F 90°F 100°F 110°F 120°F 130°F
21°C 27°C 32°C 38°C 43°C 49°C 54°C
Temperature
100
90
80
70
60
50
40
30
20
% of Expected Life
Storing EnergyCell GH Batteries
The EnergyCell GH must be kept in storage no longer than the shelf life indicated in Figure 4 for a particular
temperature. At the end of this time it must be given a freshening charge. That is, a battery stored at 104°F
(40°C) should be stored no longer than six months, while it can be stored up to 48 months at 50°F (10°C) without
a charge.
Stored batteries should be checked for open-circuit voltage at intervals. Any time the battery voltage is less than
2.10 volts per cell (12.6 volts per battery), it should be given a freshening charge regardless of the storage time.
At 104°F (40°C), the EnergyCell GH voltage should be checked every 2 months. At 86°F (30°C), the interval is 3
months. At 77° to 68°F (25° to 20°C) the interval is 4 months. At temperatures lower than 59°F (15°C), the
voltage only needs to be checked every 6 months.
Storing EnergyCell RE Batteries
The EnergyCell RE must be given a freshening charge every six months when stored at 77°F (25°C). The charge
should be every three months if stored at temperatures of up to 92°F (33°C). If stored in higher temperatures,
the charge should be every month.
Capacity
Battery capacity is given in ampere-hours (amp-hours). This is a current draw which is multiplied by the duration
of current flow. A draw of Xamperes for Yhours equals an accumulation of XY amp-hours.
Because the battery’s chemical reaction constantly releases energy, it tends to replenish its own charge to a
minor degree. Smaller loads will deplete the batteries less than larger loads because of this constant
replenishment. This means that effectively the battery has more capacity under lighter loads.
For example, if the EnergyCell 170RE is discharged at the 48-hour rate to a voltage of 1.75 volts per cell (a load
expected to effectively drain 100% of its capacity in 48 hours), it will be measured to have 163.9 amp-hours.
However, at the 4-hour rate, a heavier load, only 120.6 amp-hours will be measured. For discharge rates and
amp-hours of all EnergyCell batteries, see the tables on page 20.
The EnergyCell models are named after their capacity at the 100-hour rate when discharged to 1.75 volts per cell.
State of Charge
The EnergyCell SoC can be determined by two methods. One is to
measure its voltage. This is accurate only if the batteries are left
at rest (no charging or loads) for 24 hours at room temperature
(77°F or 25°C). If these conditions are not met, then voltage checks
may not yield usable results. If they are met, then on average, a
battery at 12.8 Vdc will be at 100% SoC. A rest voltage of 12.2 Vdc
represents roughly 50% SoC.
The more accurate method is to use a battery monitor such as the
OutBack FLEXnet DC. Using a sensor known as a shunt, the monitor
observes the current through the battery. It keeps a total of amp-hours
lost or gained by the battery and can give accurate SoC readings.
The EnergyCell can be discharged and recharged (cycled) regularly
to a level as low as 50% depth of discharge (DoD). This is common in a cycling application such as an off-grid
system. However, for optimal battery life, the best practice is to avoid regular discharge below 50%. The battery
can be occasionally discharged as low as 80% DoD (20% SoC), as is common in emergency backup systems.
However, the best practice is to avoid ever discharging below 80% DoD.
If operated in the recommended range, the EnergyCell will typically have a life of hundreds of cycles. With
consistently lighter discharge, the battery may have thousands of cycles. For the anticipated cycle life of a
particular model, see the OutBack data sheet for that battery. (The cycle life can be affected by temperature.
Figure 5shows the effect of ambient temperature on typical battery life.)

EnergyCell Batteries
900-0127-01-00 Rev C 9
System Layout
CAUTION: Fire Hazard
Failure to ventilate the battery compartment can result in the buildup of
hydrogen gas, which is explosive.
The battery enclosure or room must be well-ventilated. This protects against accidental gas buildup.
All EnergyCell batteries are sealed and do not normally emit noticeable amounts of gas. However, in
the event of accidental leakage, the enclosure must not allow gas to become concentrated.
The battery enclosure or room must have adequate lighting. This is necessary to read terminal
polarity, identify cable color, and view the physical state of the battery as required.
The battery should be installed with a minimum 36” (91.4 cm) clearance in front. This allows access for
testing, maintenance, and any other reasons.
If multiple batteries are installed, they should have a minimum of ½” (12.7 mm) clearance on
either side.
Battery Configurations
Figure 6 Series String Configurations
Figure 7 Parallel String Configuration
Series String (24 Vdc)
Series String (48 Vdc)
Load +
Load –
Load +
Load –
Batteries are placed in series (negative to positive) for additive voltages. Batteries in series are known as a
“string”. A string
of two EnergyCell batteries has a nominal voltage of 24 Vdc and can be used for 24-volt
loads. A string of four has a nominal voltage of 48 Vdc. Other voltages are possible.
However, batteries in
series do not have additive amp
-hours. A single string of any voltage (as shown above) has the same
amp
-hours as a single battery.
When replacing batteries, a new battery should not be placed in series with old batteries. This wil
l cause
severe stress and shorten the life of all batteries. All batteries in a string should be replaced at the same time.
Batteries are placed in parallel (positive to positive,
negative to negative) for additive amp
-hour capacity.
Three
batteries in parallel have three times the
amp
-hours of a single battery. However, batteries in
parallel do not have additive voltages. A
single set of
batteries in parallel
(as shown in this figure) have the
same voltage as a
single battery.
NOTE:
Use caution when designing or building systems
with
more than three batteries or strings in parallel.
The extra conductors and connections used in larger
paralleled systems can lead to unexpected resistances
and i
mbalances between batteries. Without proper
precautions, these factors
will reduce the system
efficiency and shorten the life of all batteries.
Parallel Batteries
Load Bus +
Load Bus –

Installation and Operation
10 900-0127-01-00 Rev C
Figure 8 Series/Parallel String Configurations
Load Bus –
Load Bus +
Load Bus –
Load Bus +
Batteries are placed in both series and parallel for both additive voltage and amp-hour capacity.
Series strings placed in parallel have the same nominal voltage as each string. They have the same
amp
-hour capacity of each string added together. Two parallel strings of two EnergyCell batteries in
series have a nominal voltage of 24 Vdc, twice the no
minal voltage. They also have double the amp-hour
capacity of a single battery. Two parallel strings of four batteries in series have a nominal voltage of
48
Vdc at double the amp-hour capacity of a single battery.
In a series
-parallel bank, it is not recommended to connect the load to the positive and negative
terminals of a single string. Due to cable resistance, this will tend to put more wear on that string.
Instead, it is recommended to use “reverse
-return” or “cross-corner” wiring, where the positive cable is
connected to the first string and the negative is connected to the last. This will allow current to flow
evenly among all strings.

EnergyCell Batteries
900-0127-01-00 Rev C 11
DC Wiring
CAUTION: Equipment Damage
Never reverse the polarity of the battery cables. Always ensure correct polarity.
CAUTION: Fire Hazard
Always install a circuit breaker or overcurrent device on the DC positive
conductor for each device connected to the batteries.
CAUTION: Fire Hazard
Never install extra washers or hardware between the mounting surface and the
battery cable lug or interconnect. The decreased surface area can build up heat.
Terminal Hardware
EnergyCell batteries use one of two terminal types: A threaded stud which receives a nut, or a threaded hole
which receives a bolt. The terminal type, hardware sizes, and torque requirements may be different between
battery models. See Table 4 and Table 5 on page 19 for the requirements of a particular model. However, all
terminal hardware is assembled as shown in either Figure 9 or Figure 10.
NOTE: Install the cable lugs (or interconnects) and all other hardware in the order illustrated. The lug or
interconnect should be the first item installed. It should make solid contact with the mounting surface. Do not
install hardware in a different order than shown.
NOTE: To avoid corrosion, use plated lugs on cable terminations. When multiple cables are terminated, use
plated terminal bus bars.
Figure 9 Stud Terminal Assembly
Figure 10 Bolt Terminal Assembly
Lock Washer
Battery
Terminal
Surface
Battery Terminal Stud
Cable Lug or
Interconnect
Flat Washer
M6 Nut
Battery
Terminal
Surface
UNC Bolt
Lock Washer
Flat Washer
Cable Lug or
Interconnect

Installation and Operation
12 900-0127-01-00 Rev C
Figure 11 Connecting Batteries
IMPORTANT:
Before using the battery bank, commission the batteries as described on the next page.
To make the DC connections:
1. If installing batteries in a rack or cabinet, always begin with the
lowest shelf for stability. Place all batteries with terminals facing
to the most accessible side of the rack. If terminal protectors are
present, remove and save them.
2. Clean all terminals and contact surfaces.
3. In common configurations, the battery on
one end will be the positive (+) output for that
string. This battery should be designated .
Proceeding to the other end, adjacent batteries in
that string should be designated , , and so on.
4. If more than one string is present, designate the first string as A, the second as B, and so on.
This should be done regardless of whether the strings are on the same shelf or higher shelves.
Number the batteries in subsequent strings just as was done in step 3.
5. Install series connections. If an interconnecting bar was supplied with a front-terminal battery, it
should connect from the negative (left) side of battery 1 to the positive (right) side of battery 2 as
shown above. Top-terminal batteries require short interconnecting cables to be provided. Tighten
interconnect hardware “hand tight” only.
6. Repeat the process as appropriate for batteries 2, 3, and any others in the string. Connect the
proper number of batteries in series for the nominal voltage of the load.
7. If multiple series strings will be used, repeat this process for strings B, C, and so on.
8. Install parallel connections. Parallel connections are made from the positive terminal of one
battery or string to the positive of the next; negative connections are made similarly. (See Figure 7
on page 9.) External cables or bus bars must be provided. The interconnecting bar included with
front-terminal batteries cannot make parallel connections.
9. Use a digital voltmeter (DVM) to confirm the nominal system voltage and polarity. Confirm that no
batteries or strings are installed in reverse polarity.
10. Install cables or bus bars for DC loads. Size all conductors as appropriate for the total loads. See the
manual for the battery rack or cabinet if necessary.
11. Before making the final battery connection, ensure the main DC disconnect is turned off. If this is
not possible, then do not make the final connection within the battery enclosure. Instead, make it
at the load or elsewhere in the cable system so that any resulting spark does not occur in the
battery enclosure.
12. Once hardware is installed and batteries are properly aligned, torque all connections to the
appropriate value for the battery model. (See the requirements on page 19.) Lightly coat the
surfaces with battery terminal grease. Reinstall the terminal covers if present.
2
1

EnergyCell Batteries
900-0127-01-00 Rev C 13
Commissioning
Before commissioning batteries:
1. Measure and record inter-battery connection resistances and open circuit voltages. These measurements
should be used as a reference for future maintenance requirements.
2. Perform a visual inspection of all terminals, components, and connections.
3. Verify that the charger’s set points are adjusted to the correct values for the battery and the application.
To commission batteries before initial use:
1. Send the batteries through a complete charge cycle (see next section) according to these instructions:
∼The batteries should be held at the specified absorption voltage for 24 hours.
∼Following this stage, the batteries should be held at the specified float voltage for three to seven days.
2. Clean all battery terminals to ensure reliable electrical connections.
3. Install a DC load which draws a continuous 25 Adc. This allows the results to be correlated to the specified
capacity. The load may be used on either a single battery or a full string.
4. The load test unit wires must be sized correctly. For load testing all wiring should have a minimum ampacity
of 150% of the load current.
5. With this load, discharge the batteries until they have reached 10.5 Vdc per battery (1.75 Vdc per cell).
6. Monitor the elapsed time. At the same time, monitor the battery’s temperature.
7. Record the temperature at the end of the test. Use the equation below to adjust the results for temperature.
Mc= Mr(1 – 0.009 [T – 26.7])
where Mr= actual elapsed minutes
T= temperature at end of run time
Mc= minutes corrected for temperature with a baseline of 80°F (26.7°C).
8. Compare Mcwith the appropriate value in Table 1. The batteries should deliver greater than 90% of their
rated run time.
Table 1 Rated Values for M
c
EnergyCell
model
Expected Mc
EnergyCell
model
Expected Mc
Minutes Hours
Minutes Hours
34RE
50.1 < 1
170RE 300 5
52RE
78.3 1 hr 18 min
200RE 347 5 hr 47 min
78RE
123.8 2 hr 4 min
200GH 348 5 hr 48 min
95RE
139.8 2 hr 20 min
220GH 460 7 hr 40 min
106RE
153.2
2 hr 33 min
Charging (EnergyCell GH)
EnergyCell GH batteries are usually charged using a constant-voltage or float charger. OutBack
inverter/chargers and charge controllers do not have this function as their default setting. They can be made to
perform a constant float charge by skipping the absorption stage or setting the absorption voltage equal to the
float voltage.Other adjustments may be necessary.
Float Charge
A float charger gradually charges the batteries by maintaining them at a fixed voltage. In backup applications,
it is common for this voltage to be maintained continuously by the charger until the batteries are needed.
However, if the charger is not in regular operation, the batteries should be given an occasional freshening

Installation and Operation
14 900-0127-01-00 Rev C
charge for a minimum of 24 hours. After discharge, the float charge should be applied as soon as possible.
It must not be delayed more than 7 days in any case.
The charger should be sized so that the full charge rate is at least 17 Adc per battery string.
The float charger should be set to maintain the batteries at 13.62 Vdc per battery in a string (2.27 volts per cell) at
77°F (25°C). Other temperatures require voltage compensation within a range of 2.21 to 2.29 volts per cell. See
Temperature Compensation on page 15.
Freshening Charge
A maintenance or “freshening” charge is given to batteries that have been in storage. The freshening charge
must be appropriate to the battery model. All charging should be temperature-compensated (see page 15).
The charge should proceed as described above using a float charger. The voltage should be 13.62 Vdc per
battery in a string (2.27 volts per cell).
Charging (EnergyCell RE)
EnergyCell RE batteries are usually charged using a “three-stage” charging cycle: bulk stage, absorption stage,
and float stage. Most OutBack chargers follow this algorithm. However, not all chargers are designed or
programmed the same way. The settings should be checked and changed to match the recommendations
below if necessary. Contact OutBack Technical Support before using other charger types.
Bulk Stage
The bulk stage is a constant-current stage. The
charger’s current is maintained at a constant
high level. The battery voltage will rise as long as
the current continues to flow. Each battery
model has a recommended maximum current
limit (see Table 6 on page 19) which should not
be exceeded. At excessive current rates, the
battery’s efficiency of conversion becomes less
and it may not become completely charged.
The battery may permanently lose capacity over
the long term.
The purpose of the bulk stage is to raise the
battery to a high voltage (usually referred to as
either bulk voltage or absorption voltage). The
acceptable voltage range is 14.4 to 14.8 Vdc per
battery in a string (2.40 to 2.47 volts per cell). If
batteries are in series, this number is multiplied
by the number of batteries in the string. This
stage typically restores the battery to 85% to
90% SoC, if the charge rate does not exceed the
maximum shown on page 19.
Absorption Stage
The absorption stage is a constant-voltage stage. It is established upon reaching the desired voltage in the bulk
stage. This causes the charger to begin limiting the current flow to only what is necessary to maintain this
voltage. A large amount of current is required to raise the voltage to the absorption level, but less current is
required to maintain it there. This requirement will tend to decrease as long as the absorption level is
maintained, resulting in a tapering current flow. The amount of absorption current will vary with conditions, but
will typically decrease to a very low number. This “tops off the tank”, leaving the battery at 100% SoC.
The battery is considered to be completely full when the following conditions are met: The charge current must
taper down to a level of current equal to between 1% and 2% of the total battery amp-hours (while
Hours (typical)
Amperes (typical)
Hours (typical)
Bulk
Absorption
Float
Absorption
Bulk
Float
DC Volts
Figure 12 Three-Stage Charging

EnergyCell Batteries
900-0127-01-00 Rev C 15
maintaining the absorption voltage). At this point the charger is allowed to exit absorption to the next stage.
Not all chargers measure their absorption stage in amperes. Many chargers maintain absorption for a timed
period (often two hours), under the assumption that the current will taper to the desired level during this time.
However, if the charger exits absorption and ends the charge before the current has tapered down to the
desired level, the battery may not reach 100% SoC. Repeated failure to perform a complete charge will result in
decreased battery life. If possible, it is recommended to use a DC ammeter to observe and time the current as it
tapers to the proper amperage. The user can then manually set the charger’s absorption timer accordingly.
Float Stage
The float stage is a maintenance stage which ensures the battery remains fully charged. Left with no
maintenance, the battery will tend to slowly lose its charge. The float stage provides current to counter this
self-discharge. As with the absorption stage, float is a constant-voltage stage which supplies only enough
current to maintain the designated voltage.
The voltage requirements for float stage are much lower than for bulk and absorption. The voltages per
model of EnergyCell RE are listed in Table 6 on page 19.The float stage should provide enough current to
maintain the appropriate voltage. If batteries are in series, this number should be multiplied by the number of
batteries in the string.
Freshening Charge
A maintenance or “freshening” charge is given to batteries that have been in storage. The freshening charge
must be appropriate to the battery model. All charging should be temperature-compensated (see below).
With a three-stage charger, voltages are set as noted in Table 6 on page 19.
If a specialized VRLA charger is available, it should charge EnergyCell RE batteries at 14.4 to 14.8 Vdc
continuously for 16 hours before use.
Notes on EnergyCell RE Charging
The current requirements for the absorption and float stages are usually minimal; however, this will vary with
conditions, with battery age, and with battery bank size. (Larger banks tend to have higher exit current values
for the absorption stage, but they also have higher float current.) Any loads operated by the battery while
charging will also impact the requirements for the charger, as the charger must sustain everything.
Not all chargers exit directly to the float stage. Many will enter a quiescent or “silent” period during which the
charger is inactive. These chargers will turn on and off to provide periodic maintenance at the float level, rather
than continuous maintenance.
Constant-Float Charging
“Constant-float” charging may be used with the EnergyCell RE in backup power applications where the battery
bank is rarely discharged. When a discharge occurs, it is critical to recharge the bank as soon as possible
afterward. When charged with a constant-float charger, the charger should be set to maintain the batteries at
13.65 Vdc per battery in a string (2.30 volts per cell) at room temperature. The batteries are considered to be
fully charged when the cell voltage is maintained at this level and the charge current has dropped to a low level
over a long period of time. In constant-float charging, it is critical to compensate the settings for temperature.
The EnergyCell RE is not optimized for constant-float. OutBack recommends using the EnergyCell GH instead.
Temperature Compensation
Battery performance will change when the temperature varies above or below room temperature (77°F or 25°C).
Temperature compensation adjusts battery charging to correct for these changes.
When a battery is cooler, its internal resistance goes up and the voltage changes more quickly. This makes it
easier for the charger to reach its voltage set points. However, while accomplishing this process, it will not
deliver enough current to restore the battery to 100% SoC. As a result, the battery will tend to be undercharged.
Conversely, when a battery is warmer, its internal resistance goes down and the voltage changes more slowly.

Installation and Operation
16 900-0127-01-00 Rev C
This makes it harder for the charger to reach its voltage set points. It will continue to deliver energy over time
until the charging set points are reached. However, this tends to be far more than the battery requires, meaning
it will tend to be overcharged. (See Improper Use.)
To compensate for these changes, a charger used with the EnergyCell battery must have its voltages raised by a
specified amount for every degree below room temperature. They must be similarly lowered for every degree
above room temperature. This factor is multiplied if additional batteries are in series. Failure to compensate for
significant temperature changes will result in undercharging or overcharging which will shorten battery life.
EnergyCell GH Required Compensation
The factor is 4 mV per cell (0.024 Vdc or24 mV per battery) per degree C above or below room temperature
(77°F or 25°C).
EnergyCell RE Required Compensation
The factor is 5 mV per cell (0.03 Vdc or 30 mV per battery) per degree C above or below room temperature
(77°F or 25°C).
Remote Temperature Sensor
OutBack inverter/chargers and charge controllers are equipped with the Remote Temperature Sensor (RTS)
which attaches to the battery and automatically adjusts the charger settings. When the RTS is used, it should be
placed on the battery sidewall, as close to the center of the battery (or to the center of the bank) as possible.
The charger determines the RTS compensation factor. Most OutBack chargers are preset to a compensation of
5 mV per cell. If an RTS is not present, if a different charger is in use, or if a different compensation factor is
required, it may be necessary to adjust the charger settings manually. The RTS should be checked periodically.
Failure to compensate correctly may result in wrong voltages.
Improper Use
CAUTION: Equipment Damage
Read all items below. Maintenance should be performed as noted on page 18.
Failure to follow these instructions can result in battery damage which is not
covered under the EnergyCell warranty.
CAUTION: Equipment Damage
Do not exceed the specified absorption voltage when charging any EnergyCell
battery. Excessive voltage could result in battery damage which is not covered
under the EnergyCell warranty.
For any EnergyCell battery, if the charger settings are too high, this will cause premature aging of the battery,
including loss of electrolyte due to gassing. The result will be permanent loss of some battery capacity and
decreased battery life. This is also true for battery charging that is not compensated for high temperatures.
“Thermal runaway” can result from high ambient temperatures, charging at higher voltages over extended time,
incorrect temperature compensation, or shorted cells. When the buildup of internal heat exceeds the rate of
cooling, the battery’s chemical reaction accelerates. The reaction releases even more heat, which in turn
continues to speed up the reaction. Thermal runaway causes severe heat, gassing, lost electrolyte, and cell
damage. It usually requires battery replacement. The process can be halted by turning off the charger.
However, if cell damage has occurred, shorted cells may continue to generate heat and gas for some time.
If an EnergyCell battery is not charged completely (or if the settings are too low), it will not reach 100% SoC.
Its total capacity will not be available during the next discharge cycle. This capacity will become progressively
less and less over subsequent cycles. Long-term undercharging will result in decreased battery life. This is also
true for battery charging that is not compensated for low temperatures.

900-0127-01-00 Rev C 17
Troubleshooting and Maintenance
Table 2 Troubleshooting
Category
Symptom
Possible Cause
Remedy
Performance
Reduced operating time
Normal life cycle
Replace battery bank when (or before) capacity
drops to unacceptable levels.
Defective cells
Test and replace battery as necessary.
Excessive voltage drop upon
applying load
Excessively cold battery
Carefully warm up the battery.
Undersized cabling
Increase cable ampacity to match loads.
Loose or dirty cable
connections
Check and clean all connections. Physical
damage on terminals may require the battery
to be replaced. Replace hardware as necessary.
Undersized battery bank
Add additional batteries to match loads.
Defective cells
Test and replace battery as necessary.
External
Inspection
Swollen or deformed battery
casing; “rotten-egg” or
sulfurous odor; battery is hot
Thermal runaway
NOTE: A modest amount of
swelling (or concavity) on
the battery case is normal.
NOTE: Thermal runaway is a hazardous
condition. Treat the battery with caution.
Allow the battery to cool before approaching.
Disconnect and replace battery as necessary.
Address the conditions that may have led to
thermal runaway (see page 16).
Damaged battery casing
Physical abuse
Replace battery as necessary.
Heat damage or melted
grease at terminals
Loose or dirty cable
connections
Check and clean all connections. Physical
damage on terminals may require the battery
to be replaced. Replace hardware as necessary.
Voltage
testing
Fully-charged battery
displays low voltage
High temperature
Carefully cool the battery. An overheated
battery may contribute to thermal runaway.
Fully-charged battery
displays high voltage
Low temperature
Carefully warm up the battery.
Individual battery charging
voltage will not exceed
13.3 Vdc; high float current;
failure to support load
Shorted cell
Test and replace battery as necessary.
A shorted cell may contribute to thermal
runaway.
Individual battery float
voltage exceeds 14.5 Vdc;
failure to support load
Open cell
Test and replace battery as necessary.

Maintenance
18 900-0127-01-00 Rev C
Table 2 Troubleshooting
Category
Symptom
Possible Cause
Remedy
Current
testing
Charging current to series
string is zero; failure to
support load
Open connection or open
battery cell in string
Check and clean all connections. If battery
appears to have an open cell, test and replace
as needed.Replace hardware as necessary.
Charging current to series
string remains high over time
Batteries require additional
time to charge
Normal behavior; no action necessary.
Charging current to series
string remains high with no
corresponding rise in voltage
Shorted cell
Test and replace battery as necessary.
A shorted cell may contribute to thermal
runaway.
Periodic Evaluation
Upon replacement of a battery (or string), all interconnect hardware should be replaced at the same time.
To keep track of performance and identify batteries that may be approaching the end of their life, perform the
following tests during on a quarterly basis following commissioning (see page 13). Tests must be made with a
high-quality digital meter. Voltages must be measured directly on battery terminals, not on other conductors.
All connections must be cleaned, re-tightened, and re-torqued before testing. If a battery fails any test, it may be
defective. If this occurs under the conditions of the warranty, the battery will be replaced according to the terms
of the warranty.
Bring the batteries to a full state of charge before performing either of the following tests.
24-Hour Open-Circuit Test
Remove all battery connections, then allow the battery to rest in this state for 24 hours. Test the battery voltage,
compensating for temperature. The EnergyCell RE battery should measure 12.84 Vdc. The EnergyCell GH
battery should measure 12.95 Vdc. A battery below 12.6 Vdc has lost capacity and may need to be replaced.
25-Amp Capacity Test
1. Install a DC load which draws a continuous 25 Adc. This allows the results to be correlated to the specified
capacity. The load may be used on either a single battery or a full string.
2. The load test unit wires must be sized correctly. For load testing all wiring should have a minimum ampacity
of 150% of the load current.
3. With this load, discharge the batteries until they have reached 10.5 Vdc per battery (1.75 Vdc per cell).
4. Monitor the elapsed time. At the same time, monitor the battery’s temperature.
5. Record the temperature at the end of the test. Use the equation below to adjust the results for temperature.
Mc= Mr(1 – 0.009 [T – 26.7])
where Mr= actual elapsed minutes
T= temperature at end of run time
Mc= minutes corrected for temperature with a baseline of 80°F (26.7°C).
6. Compare Mcwith the appropriate value in Table 1 on page 13. If the result is less than 80% of this number,
the battery (or string) may need to be replaced.

900-0127-01-00 Rev C 19
Specifications
Table 3 EnergyCell Battery Electrical Specifications
EnergyCell RE (all models)
EnergyCell GH (all models)
Battery Category
Valve-regulated, lead-acid (VRLA)
Valve-regulated, lead-acid (VRLA)
Battery Technology
Absorbed glass-mat (AGM)
Absorbed glass-mat (AGM)
Cells Per Unit
6
6
Voltage Per Unit (nominal)
12 Vdc
12 Vdc
Operating Temperature Range
(with temperature compensation)
Discharge: -40°F (-40°C) to 160°F (71°C)
Charge: -10°F (-23°C) to 140°F (60°C)
-40°F (-40°C) to 122°F (50°C)
Optimal Operating
Temperature Range
74°F (23°C) to 80°F (27°C) 50°F (10°C) to 104°F (40°C)
Self-Discharge Store up to 6 months at 77°F (25°C)
before a freshening charge is required.
Store up to 18 months at 77°F (25°C)
before a freshening charge is required.
Table 4 EnergyCell Front Terminal Mechanical Specifications
170RE
200RE
200GH
220GH
Terminal
Threaded insert terminal to accept
¼”-20 UNC bolt
Threaded stud to accept M6 nut
Terminal Hardware Initial Torque
110 in-lb (12.4 Nm)
80 in-lb (9.0 Nm)
Weight
115.0 lb (52.2 kg)
131.0 lb (59.4 kg)
115.7 lb (52.5 kg)
132.3 lb (52.5 kg)
Dimensions (H x L x W)
11.1 x 22.1 x 4.9”
(28.3 x 56.1 x
12.5 cm)
12.6 x 22.0 x 4.9”
(32.0 x 55.9 x
12.5 cm)
11.1 x 22.1 x 4.9”
(28.3 x 56.1 x
12.5 cm)
12.4 x 22.1 x 4.9”
(31.6 x 56.1 x
12.5 cm)
Table 5 EnergyCell Top Terminal Mechanical Specifications
34RE
52RE
78RE
95RE
106RE
Terminal
Threaded insert terminal to
accept 10”-32 UNC bolt
Threaded insert terminal to accept ¼”-20 UNC bolt
Terminal Hardware Initial Torque
30 in-lb (3.4 Nm)
110 in-lb (12.4 Nm)
Weight
27 lb (12.2 kg)
40 lb (18.1 kg)
54 lb (24.5 kg)
64 lb (29.0 kg)
69 lb (31.3 kg)
Dimensions (H x L x W)
6.8 x 7.8 x 5.2”
(17.3 x 19.7 x
13.2 cm)
8.1 x 9.0 x 5.5”
(20.5 x 22.9 x
13.9 cm)
8.0 x 10.8 x 6.8”
(20.3 x 27.3 x
17.3 cm)
8.1 x 12.5 x 6.8”
(20.5 x 31.8 x
17.3 cm)
8.5 x 13.4 x 6.8”
(21.6 x 34.1 x
17.3 cm)
Table 6 EnergyCell Charging Requirements at 77°F (25°C)
34RE
52RE
78RE
95RE
106RE
170RE
200RE
200GH
220GH
Recommended Maximum
Current Limit Per String
7 Adc 10 Adc 15 Adc 18 Adc 20 Adc 25 Adc 30 Adc 32 Adc 36 Adc
Float Charging Voltage
13.5 to 13.8 Vdc
13.62 to 13.8 vdc
13.62 Vdc
Absorb Charging Voltage
14.4 to 14.8 Vdc
14.4 Vdc
Temperature
Compensation Factor 0.03 Vdc per battery in series (5 mV per cell) per degree C
0.024 Vdc per battery
in series (4 mV per
cell) per degree C

Specifications
20 900-0127-01-00 Rev C
Ampere-Hour Capacity Based On Discharge Rate
The EnergyCell battery capacity is measured in amp-hours. The battery capacity is not a fixed number, but will
vary with conditions. (See page 8.) The figures in the tables below are used to measure the capacity of the
EnergyCell battery based on load size.
Battery capacity is judged by the number of amp-hours measured when a battery is discharged to a standard
voltage under load. This is known in the industry as “terminal voltage”. A commonly cited terminal voltage is
10.5 volts per 12-volt battery, or 1.75 volts per cell (Vpc).Another common value is 1.85 volts per cell; this value
is used when sizing batteries conservatively to avoid severely discharging them.
The amp-hours measured upon reaching terminal voltage also depend on the size of the load. A load capable of
discharging the battery in 1 hour is far larger than a load which takes 3, 4, or 5 hours. (8-hour loads, 12-hour
loads, etc. are progressively smaller in size.) As described on page 8, the battery has less capacity under larger
loads and more capacity under smaller loads.
Table 7 shows EnergyCell capacity at a terminal of voltage 1.75 Vpc. Table 8 shows EnergyCell capacity at a
terminal voltage of 1.85 Vpc.
Example: Under a 1-hour load, the EnergyCell 170RE has a capacity of only 89.1 amp-hours when measured to
1.75 Vpc in Table 7. Under a much lighter 100-hour load, the same battery has 170 amp-hours in Table 7, almost
twice that amount.
Other EnergyCell batteries are measured similarly.
Table 7 Amp-Hour Capacity to 1.75 Vpc @ 77°F (25°C)
Discharge in Hours
Model 1 2 3 4 5 6 7 8 10 12 20 24 48 72 100
34RE 19.7 23.6 26.1 28.0 29.0 29.6 30.1 30.1 31.1 31.7 33.0 33.1 - 33.8 34.0
52RE 29.6 35.1 38.9 41.4 43.3 44.6 45.4 46.0 47.2 48.0 50.0 50.4 - 51.8 52.0
78RE 43.5 53.2 58.5 62.0 64.5 66.6 68.6 69.6 71.0 72.0 75.0 75.6 - 77.6 78.0
95RE 47.0 58.0 66.0 70.8 74.0 76.2 78.0 79.2 81.7 83.6 88.0 88.8 - 93.0 95.0
106RE 49.2 61.5 70.0 76.0 80.6 84.0 86.8 89.0 92.0 94.2 100.0 101.0 - 104.0 106.0
170RE 89.1 - 114.2 120.6 125.9 - - 137.0 - 145.3 153.8 157.0 163.9 - 170.0
200RE 103.0 - 132.0 139.6 145.5 - - 158.4 - 168.0 178.0 181.4 189.6 - 200.0
200GH 120.0 - 148.5 154.8 159.0 - - 168.8 - 176.4 191.0 189.6 192.0 - 200.0
220GH 133.5 - 166.2 173.2 178.0 - - 188.8 - 198.0 214.0 216.0 - - 220.0
Table 8 Amp-Hour Capacity to 1.85 Vpc @ 77°F (25°C)
Discharge in Hours
Model 1 2 3 4 5 6 7 8 10 12 20 24 48 72 100
34RE 22.3 25.8 28.1 29.9 30.8 31.4 31.8 31.8 32.7 33.4 34.7 35.1 - 36.4 36.7
52RE 33.5 38.4 41.9 44.3 46.0 47.3 47.9 48.7 49.7 50.5 52.6 53.4 - 55.7 56.1
78RE 49.3 58.2 63.1 66.3 68.6 70.7 72.4 73.6 74.7 75.8 78.8 80.1 - 83.5 84.2
95RE 53.3 63.5 71.1 75.7 78.7 80.8 82.4 83.8 85.9 88.0 92.5 94.1 - 100.1 102.5
106RE 55.7 67.3 75.5 81.2 85.7 89.1 91.7 94.2 96.8 99.2 105.1 107.1 - 111.9 114.4
170RE 100.9 - 123.1 128.9 133.8 - - 144.9 - 153.0 161.6 166.4 176.8 - 183.4
200RE 116.7 - 142.3 149.2 154.7 - - 167.6 - 176.9 187.1 192.3 204.6 - 215.8
200GH 136.0 - 160.1 165.5 169.0 - - 178.6 - 185.7 200.7 200.9 207.2 - 215.8
220GH 151.3 - 179.2 185.2 189.2 - - 199.8 - 208.5 224.9 228.9 - - 237.4
This manual suits for next models
9
Table of contents
Other Outback Camera Accessories manuals