Pacific Ventilation BEC 150HP User manual

www.pacicventilation.com
User’s Manual
BEC 150HP – Centrifugal ceiling extract fan

2 Pacic Ventilation
Contents
Safety requirements ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 3
Purpose . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 5
Delivery set... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 5
Designation key ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 5
Technical data ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 6
Design and functioning ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 7
Mounting and set-up... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 8
Connection to power mains ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 10
Electronics operation algorithm ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 10
Technical maintenance ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 11
Manufacturer’s warranty ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 12
This user’s manual is a main operating document intended for technical, maintenance, and operating staff.
The manual contains information about purpose, technical details, operating principle, design, and installation of the
BEC 150HP unit and all its modications.
Technical and maintenance staff must have theoretical and practical training in the eld of ventilation systems and
should be able to work in accordance with workplace safety rules as well as construction norms and standards
applicable in the territory of the country.

Pacic Ventilation 3
Safety requirements
All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical,
and technical norms and standards must be observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations.
Only qualied electricians with a work permit for electrical units up to 1000V are allowed for installation and
maintenance. The present user’s manual should be carefully read before beginning works.
Check the unit for any visible damage of the impeller, the casing, and the grille before starting installation. The
casing internals must be free of any foreign objects that can damage the impeller blades.
While mounting the unit, avoid compression of the casing! Deformation of the casing may result in motor jam and
excessive noise.
Misuse of the unit and any unauthorised modications are not allowed.
Do not expose the device to adverse atmospheric agents (rain, sun, etc.).
Transported air must not contain any dust or other solid impurities, sticky substances, or brous materials.
Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc.
Do not close or block the intake or extract vents in order to ensure the efcient air ow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the document’s preparation.
The Company reserves the right to modify the technical characteristics, design, or conguration of its products at
any time in order to incorporate the latest technological developments.
WARNING! Similar to the use of any other household electrical appliances when operating this fan, the following
basic rules must be followed:
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.

4 Pacic Ventilation
The connection to the supply mains must be made through a means of disconnection, which is incorporated in the
xed wiring in accordance with the wiring rules, and has a contact separation in all poles that allows for full
disconnection under over voltage category III conditions.
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualied persons
in order to avoid a safety hazard.
CAUTION: In order to avoid a safety hazard due to inadvertent resetting of the thermal cut-out, this appliance must
not be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly
switched on and off by the utility.
Ensure that the appliance is switched off from the supply mains before removing the guard.
WARNING: If unusual oscillating movements is observed, immediately stop using the appliance and contact the
manufacturer, its service agent or suitably qualied persons.
The replacement of parts of the safety suspension system device shall be performed by the manufacturer, its service
agent or suitably qualied persons.
Fixing means for attachment to the ceiling such as hooks or other devices shall be xed with a sufcient strength to
withstand 4 times the weight of the appliance.
The mounting of the suspension system shall be performed by the manufacturer, its service agent or suitably
qualied persons.
The appliance is to be installed so that the blades are more than 2.3m above the oor.
Precautions must be taken to avoid the back-ow of gases into the room from the open ue of gas or
other fuel-burning appliances.
The product must be disposed separately at the end of its service life.
Do not dispose the unit as unsorted domestic waste.

Pacic Ventilation 5
Purpose
The centrifugal ceiling extract fan BEC 150HP is designed for extract ventilation of small to medium-sized premises.
The unit is rated for continuous operation.
The unit should not be operated by children or persons with reduced Physical, mental, or sensory
capacities, or those without the appropriate Training.
The unit must be installed and connected only by properly qualied Personnel after the
appropriate brieng.
The choice of unit installation location must prevent unauthorised Access by unattended children.
The unit must not be operated in kitchen premises.
Transported air must not contain any ammable or explosive mixtures, evaporation of chemicals, sticky substances,
brous materials, coarse dust, soot and oil particles or environments favourable for the formation of hazardous
substances (toxic substances, dust, pathogenic germs).
Delivery set
Name BEC 150HP Round
Centrifugal ceiling extract fan 1 pc.
Decorative grille 1 pc.
User’s manual 1 pc.
Packing box 1 pc.

6 Pacic Ventilation
Technical data
The centrifugal ceiling extract fan is designed for indoor application with the ambient temperature ranging
from +1 °C up to +45 °C.
The unit is rated as a Class I electrical appliance.
The unit design is constantly being improved, thus some models may be slightly different from those described
in this manual.
Overall and connecting dimensions
BEC 150HP BEC 150HP Round
370
300
198
38
330
316
148
198
36
330
148
198
321
148
370
300
198
38
330
316
148
198
36
330
148
198
321
148
Template for marking the fan installation location
370
300
198
38
330
316
148
198
36
330
148
198
321
148

Pacic Ventilation 7
Technical data
Parameter BEC 150HP
Frequency [Hz] 50
Voltage [V] 1 ~ 220-240
Rated fan power [W] 57
RPM [min-1] 1085
Current [A] 0.25
Max. air ow [m3/h] 482
Max. air ow [l/s] 134
Specic fan power (SFP) [W/l/s] 0.43
Sound pressure level at 3m distance [dBA] 39
Weight [kg] 4.13
IP X4
SEC class C
Design and functioning
Exhaust air du
ct with a non-
return valve
Terminal box Decorative panel
Casing
The fan casing is made of plastic.
The extract spigot with a non-return valve is attached to the fan to prevent back air ow.
In the upper part of the casing there is a terminal box, which contains terminals for connecting the fan to power mains
and to electronics board, if available.
A single-phase electric motor with a centrifugal impeller with forward curved blades is fastened inside of the casing.
Depending on the model, the fan is equipped with a timer and a humidity sensor.

8 Pacic Ventilation
Mounting and set-up
Read the user’s manual before installing the unit.
The fan is a component part and is not designed for stand-alone operation.
The fan is designed for ceiling mounting and installation in the oor slab with fastening to the ceiling surface using
removable rotary clamping brackets on the fan casing.
The fan installation location must comply with local building codes for this type of product.
Check the fan for mechanical damages prior to mounting.
Before mounting make sure the casing does not contain any foreign objects (e.g. foil, paper).
While installing the unit ensure convenient access for subsequent maintenance and repair.
The minimum distance between the fan and the ceiling should be at least 5 mm.
L = 5mm (min)

Pacic Ventilation 9
Mounting sequence
1. Use the template to mark the
mounting location for the fan and
make a hole in the ceiling Ø 300 mm.
2. The exible air duct is pushed
through the hole from behind the
ceiling, from above. The air duct is
installed on a spigot with a non-
return valve.
3. Before installation, it is required to
loosen the self-tapping screws on
the rocking levers, thereby increasing
the gap between the casing and the
lever.
Ø
300
Ø
300
Ø
300
4. The spigot and the air duct are
installed on the fan.
5. The fan assembly is inserted into the
ceiling opening from the room side.
6. Secure the fan by turning the levers.
Ø
300
Ø
300
Ø
300
7. After installing the fan, it is necessary
to clamp the self-tapping screws on
the rocking levers to press the fan
casing against the ceiling.
8. Install the decorative panel (purchased separately for the BEC 150HP model)
on the fan casing. The panel is mounted in accordance with the User’s manual
for the decorative panel.
Ø
300
Ø
300

10 Pacic Ventilation
Connection to power mains
Power off the power supply prior to any operations with the unit.
The unit must be connected to power supply by a qualied electrician.
The rated electrical parameters of the unit are given on the Manufacturer’s label.
Any tampering with the internal connections is prohibited and will void the warranty
The fan is rated for connection to single-phase AC 220-240 V/50 (60) Hz.
The fan is connected to power mains with an electric plug through a QF circuit breaker with a magnetic trip integrated
into the xed wiring system.
The position of the automatic circuit breaker must ensure free access for quick power-off of the unit.
Wiring diagram of the fan
8 mm
max.
L
QF
L
N
N
S
N
QF
L
N
L
S1
S
N
QF
L
N
L
S1
8 mm
max.
L
QF
L
N
N
S
N
QF
L
N
L
S1
S
N
QF
L
N
L
S1
8 mm
max.
L
QF
L
N
N
S
N
QF
L
N
L
S1
S
N
QF
L
N
L
S1
Terminal designations on the wiring diagram: L – phase; N – neutral; S1 — switch; QF – automatic circuit breaker.
Electronics operation algorithm
Timer (T)
After turning on an external switch, such as a light switch, the fan turns on.
After the switch is turned off the fan keeps operating for a set turn-off delay time period, adjustable
from 0 to 30 minutes.
Humidity sensor (TH)
If the set humidity level in the room is exceeded from 60 % to 90 %, the fan turns on.
As the indoor humidity level drops down the fan keeps operating for a set turn-off delay time period, adjustable
from 0 to 30 minutes, and then turns off.
The fan delivery set includes a specially designed
plastic screwdriver for fan settings adjustments.
Use it to change the turn-on and turn-off delay time
and the humidity set point. H
60% 90%
T
2 min 30 min
— To adjust the fan turn-on delay time, turn the control knob Ton clockwise to increase and counter-clockwise
to decrease the turn-on delay time respectively, adjustable from 0 up to 2 minutes.
— To adjust the humidity set point, turn the control knob H clockwise to increase and counter-clockwise to decrease
the humidity sensor set point, adjustable from 60% up to 90%.
Do not use a metal screwdriver, knife, etc.
For adjustment operations not to damage the circuit board.

Pacic Ventilation 11
Technical maintenance
Disconnect the unit from power supply before any maintenance operations!
Ensure that the unit is switched off from the supply mains before removing the guard.
The fan maintenance includes regular cleaning of the surfaces of dust and dirt. Replace the lter as required, but at least
every 6 months.
The impeller cleaning is shown below. Clean the impeller blades thoroughly every 6 months.
Troubles and troubleshooting
Trouble Possible reasons Troubleshooting
The fan does not get started.
No power supply. Check the electric connections and the
operation status of the circuit breaker.
Motor jam. Turn the fan off. Troubleshoot clogging
of the impeller. Restart the fan.
Automatic circuit breaker tripping
during the unit turning on.
Over current as a result of short circuit
in the electric circuit leads to tripping
of the circuit breaker.
Disconnect the fan from power supply
and contact the product Seller. Do not
turn the fan on again!
Low air ow.
Air ducts or other components of the
ventilation system are clogged. The
impeller is clogged. The air ducts are
damaged. The air dampers are closed.
Clean the air ducts, the impeller and
other components of the ventilation
system. Make sure that the air ducts
are not damaged. Make sure that the
air dampers and louvre shutters are
open.
Storage and transportation regulations
Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range
from +5 ˚C to +40 ˚C and relative humidity up to 70 %.
Storage environment must not contain aggressive vapours and chemical mixtures provoking corrosion, insulation, and
sealing deformation.
Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
Follow the handling requirements applicable for the particular type of cargo.
The unit can be carried in the original packaging by any mode of transport provided proper protection against
precipitation and mechanical damage. The unit must be transported only in the working position.
Avoid sharp blows, scratches, or rough handling during loading and unloading.
Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating
temperature for at least 3-4 hours.

12 Pacic Ventilation
Manufacturer’s warranty
Pacic Ventilation warrants that all goods manufactured or supplied will be free of defects in workmanship and materials
for a period of 12 months from the date of invoice to the customer, provided that the goods are installed according to the
requirements of AS/NZS3000:2007 Australian / New Zealand wiring rules and the installation instructions described herein.
Pacic Ventilation accepts no responsibility for costs involved in the removal or replacement of defective parts.
Pacic Ventilation may require the return of goods at the claimants expense to establish the validity of the claim.
A full copy of our conditions of sale including warranty provisions is available at www.pacicventilation.com.
Note: with the purpose of performing warranty servicing you please produce User Manual or other relevant substituting
document and the payment document as an evidence of the purchase with indication of the sale date.
The product model shall comply with that one specied in the User Manual or other relevant substituting document.
The warranty repair does not include:
routine technical maintenance
unit installation/dismantling
unit setup
To benet from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and
the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual.
Contact the Seller for warranty service.

Pacic Ventilation 13
The manufacturer’s warranty does not apply to the following cases:
User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission
with missing component parts previously dismounted by the user.
Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s
manual.
User’s failure to ensure timely technical maintenance of the unit.
External damage to the unit casing (excluding external modications as required for installation) and internal
components caused by the user.
Redesign or engineering changes to the unit.
Replacement and use of any assemblies, parts and components not approved by the manufacturer.
Unit misuse.
Violation of the unit installation regulations by the user.
Violation of the unit control regulations by the user.
Unit connection to power mains with a voltage different from the one stated in the user’s manual.
Unit breakdown due to voltage surges in power mains.
Discretionary repair of the unit by the user.
Unit repair by any persons without the manufacturer’s authorization.
Expiration of the unit warranty period.
Violation of the unit transportation regulations by the user.
Violation of the unit storage regulations by the user.
Wrongful actions against the unit committed by third parties.
Unit breakdown due to circumstances of insuperable force (re, ood, earthquake, war, hostilities of any kind,
blockades).
Missing seals if provided by the user’s manual.
Failure to submit the user’s manual with the unit purchase date stamp.
Missing payment paperwork certifying the unit purchase.
Following the regulations stipulated herein will ensure a long and trouble-free operation of the
unit.
User’s warranty claims shall be subject to review only upon presentation of the unit, the
payment document and the user’s manual with the purchase date stamp.

14 Pacic Ventilation
Notes

Pacic Ventilation 15
Notes

Pacic Ventilation Pty Ltd
AU 1300 733 833
NZ 0800 100 326
www.pacicventilation.com
PV00186_OCT_2021_V0.0.1
We are the safe choice.
Table of contents
Other Pacific Ventilation Fan manuals