4
2.5 ALARM ACKNOWLEDGE
If the space pressure has fallen outside the operating range and is in alarm mode, the audible alarm
can be silenced by pressing the ALARM ACKNOWLEDGE switch.
2.6 REMOTE ALARM RELAY
A SPDT relay is de-energized when space pressure is within the operating range and energized
when the space pressure has fallen outside the operating range.
2.7 DISPLAY SELECT
Pressing the ALARM SP. or CONT. SP. switch once will change from process monitoring to
displaying the alarm or controller setpoint value.
1) PROCESS - Displays the measured pressure differential.
2) ALARM SP - Displays field adjustable positive or negative setpoint value.
To return to displaying process, press the ALARM SP. switch once. If the ALARM SP. switch is not
pressed, the display will automatically return to process in approx. 60 seconds.
3) CONT. SP. - Displays field adjustable positive or negative setpoint value.To return to displaying
process, press the CONT. SP. switch once. If the CONT. SP. switch is not pressed, the display will
automatically return to process in approx. 60 seconds.
2.8 DISPLAY
The 3-1/2 digit LED is factory calibrated for either Inches of Water or Pascals.
2.9 ACCESS DOOR OPTIONS & ADJUSTMENTS
1) SPAN - Used for span calibration of the transducer.
2) ZERO - Used for zero calibration of the transducer.
3) ALARM SETPOINT - By pressing the ALARM SP. Switch once and displaying the alarm
setpoint, the user can adjust the positive or negative alarm setpoint value.
4) ALARM DELAY -Alarm time delay adjustable from 0 to 30 seconds.
5) AUDIBLE ALARM SELECT - The audible alarm is ON/OFF jumper selectable.
6) CONTROLLER SELECTIONS & ADJUSTMENTS:
a) CONTROLLER SETPOINT - By pressing the CONT.SP. switch once and displaying the
controller setpoint, the user can adjust the positive or negative controller setpoint value.
b) INTERLOCK(H12) - Provides an unloaded system start-up output value. Shorting of
SYSTEM START terminals is required and will illuminate a green LED indicating system
start is activated. Either minimum or maximum controller output condition can be achieved
by jumper selection.
c) ACTION(H13) - Selects either inverse or direct control action.
d) RESET(H15) - Selects controller reset rate (1=fast / 3=slow).
e) 1/D(H16) - Selects controller inverse derivative rate (1=fast / 4=slow).
f) AUTO/MANUAL MODE(H17) - Selects if controller output is controlled manually or in
the auto mode.
g) MANUAL/SAMPLE HOLD(H14) - In manual mode or door interrupt mode of operation,
the output can be manually controlled by R9 potentiometer adjustment (MAN) or the output
will lock at the same value it was when the manual mode of operation was selected (SH).
h) INTERNAL SETPOINT - R49 (INT SP) adjusts the internal controller setpoint.
i) EXTERNAL SETPOINT - R68 (EXT. SP ZERO) and R64 (EXT SP SPAN) adjust
external setpoint signal.