Paragon GUARDIAN PLUS Manual

OPERATION & MAINTENANCE MANUAL
GUARDIAN PLUS
SPACE PRESSURE MONITOR
AND CONTROLLER
PARAGON CONTROLS INCORPORATED
P.O. BOX 99
FORESTVILLE, CALIFORNIA 95436-0099
(707) 579-1424
/SPMPLUS
REV. 4 07/02/02

TABLE OF CONTENTS
SECTION PAGE
1.0 BASIC OPERATION 3
2.0 GUARDIAN FEATURES 3
2.1 Power Supply
2.2 Alarm Status
2.3 Controller Status
2.4 Audible Alarm On/Off
2.5 Alarm Acknowledge
2.6 Remote Alarm Relay
2.7 Display Select
2.8 Display
2.9 Access Door Options & Adjustments
2.10 Door Interlock
2.11 System Start
3.0 PRE-STARTUP CHECK 5
3.1 Equipment Needed
3.2 Pre-Startup Check
4.0 CALIBRATION PROCEDURES 6
4.1 Power Supply
4.2 Input/Output & Display Scaling
4.3 Controller Output Scaling
5.0 CONTROLLER TUNING AND INPUT/OUTPUT SELECTIONS 8
5.1 Action
5.2 Reset
5.3 Inverse Derivative
5.4 Process Output
5.5 External Controller Setpoint
5.6 Controller Output

3
1.0 BASIC OPERATION
The Guardian Plus is a complete system package consisting of space and reference pressure sensors and the central
control processing module. The central module measures and displays the pressure differential with a resolution of
up to one ten thousandth of an inch water column. The LED display can be calibrated to read in either inches of
water column or pascals. The 3-mode (P, I, 1/D) controller circuitry compares the space pressure to a space pressure
setpoint signal and outputs a 0-10vdc or 4-20ma signal to maintain the desired differential pressure. Controller status
LED•s indicate controller output level and status of control interrupt input signal. An auxiliary 0-10vdc or 4-20ma
analog output signal linear to the pressure differential is provided for remote monitoring, control and data logging.
An alarm condition will occur when the space pressure falls outside the preset operating range. During an alarm
condition, a local LED will illuminate, the audible alarm will enable if turned on and an auxillary dry contact for
remote alarming will close. An alarm acknowledge button located on the front panel will turn only the audible alarm
off. A key locked front panel allows for controlled access to the field configurable functions of the Guardian Plus.
These functions include:
1.1 Transducer calibration zero and span adjustments.
1.2 Alarm setpoint adjustment.
1.3 Controller setpoint adjustment.
1.4 Alarm time delay to prevent nuisance alarms which would occur due to normal foot traffic.
1.5 Audible alarm On/Off selection.
1.6 Alarm and Controller setpoint display selection switches.
1.7 Controller (P, I, 1/D) tuning adjustments.
1.8 Controller output selection (Auto/Manual) and adjustment.
2.0 GUARDIAN PLUS FEATURES
(Note: Refer to figures 1, 3 & 4 for component and test point locations)
2.1 POWER SUPPLY
The Guardian Plus utilizes an isolated linear type power supply generating +15 vdc and ∀5vdc to
power the transducer sensor, scaling and digital circuitry. Input power to the Guardian is 24VAC.
The power supply is fused with an 3/8 Amp Slo Blow fuse.
2.2 ALARM STATUS
1) NORMAL (Green LED) - Indicates space pressure is within the operating range.
2) ALARM (Red LED) - Indicates space pressure has fallen outside the operating range.
2.3 CONTROLLER STATUS
1) MIN OUTPUT (Red LED) - Indicates that controller output is at a minimum value (0vdc or
4ma).
2) NORMAL (Green LED) - Indicates that controller output is controlling between minimum and
maximum output.
3) MAX OUTPUT (Red LED) - Indicates that controller output is at a maximum value (10vdc or
20ma).
4) CONTROL INTERRUPT (Red LED) - Indicates that the controller is in a control interrupt
mode of operation. Depending upon controller setup, the output will drive to a pre-determined
output value or lock the output at the same value it was when the control interrupt was activated.
2.4 AUDIBLE ALARM ON/OFF
1) ON - Indicates audible alarm is activated when in alarm condition.
2) OFF - Indicates audible alarm is de-activated when in the alarm condition.

4
2.5 ALARM ACKNOWLEDGE
If the space pressure has fallen outside the operating range and is in alarm mode, the audible alarm
can be silenced by pressing the ALARM ACKNOWLEDGE switch.
2.6 REMOTE ALARM RELAY
A SPDT relay is de-energized when space pressure is within the operating range and energized
when the space pressure has fallen outside the operating range.
2.7 DISPLAY SELECT
Pressing the ALARM SP. or CONT. SP. switch once will change from process monitoring to
displaying the alarm or controller setpoint value.
1) PROCESS - Displays the measured pressure differential.
2) ALARM SP - Displays field adjustable positive or negative setpoint value.
To return to displaying process, press the ALARM SP. switch once. If the ALARM SP. switch is not
pressed, the display will automatically return to process in approx. 60 seconds.
3) CONT. SP. - Displays field adjustable positive or negative setpoint value.To return to displaying
process, press the CONT. SP. switch once. If the CONT. SP. switch is not pressed, the display will
automatically return to process in approx. 60 seconds.
2.8 DISPLAY
The 3-1/2 digit LED is factory calibrated for either Inches of Water or Pascals.
2.9 ACCESS DOOR OPTIONS & ADJUSTMENTS
1) SPAN - Used for span calibration of the transducer.
2) ZERO - Used for zero calibration of the transducer.
3) ALARM SETPOINT - By pressing the ALARM SP. Switch once and displaying the alarm
setpoint, the user can adjust the positive or negative alarm setpoint value.
4) ALARM DELAY -Alarm time delay adjustable from 0 to 30 seconds.
5) AUDIBLE ALARM SELECT - The audible alarm is ON/OFF jumper selectable.
6) CONTROLLER SELECTIONS & ADJUSTMENTS:
a) CONTROLLER SETPOINT - By pressing the CONT.SP. switch once and displaying the
controller setpoint, the user can adjust the positive or negative controller setpoint value.
b) INTERLOCK(H12) - Provides an unloaded system start-up output value. Shorting of
SYSTEM START terminals is required and will illuminate a green LED indicating system
start is activated. Either minimum or maximum controller output condition can be achieved
by jumper selection.
c) ACTION(H13) - Selects either inverse or direct control action.
d) RESET(H15) - Selects controller reset rate (1=fast / 3=slow).
e) 1/D(H16) - Selects controller inverse derivative rate (1=fast / 4=slow).
f) AUTO/MANUAL MODE(H17) - Selects if controller output is controlled manually or in
the auto mode.
g) MANUAL/SAMPLE HOLD(H14) - In manual mode or door interrupt mode of operation,
the output can be manually controlled by R9 potentiometer adjustment (MAN) or the output
will lock at the same value it was when the manual mode of operation was selected (SH).
h) INTERNAL SETPOINT - R49 (INT SP) adjusts the internal controller setpoint.
i) EXTERNAL SETPOINT - R68 (EXT. SP ZERO) and R64 (EXT SP SPAN) adjust
external setpoint signal.

5
j) CONTROLLER OUTPUT - R51 (10V), R79 (I ZERO) and R77 (I SPAN) adjust voltage
and current output levels.
2.10 DOOR INTERLOCK
The Door Interlock option allows a user to disable the PI1/D control algorithm in the case of room
pressure loss due to a door opening and either forces the controller output to a pre-determined value
or lock the output at the same value it was when the door interlock option was activated. The
following jumper positions determine how door interlock is activated and how the controller output
will react to option activation.
1) Door Interlock Activation (H10): CL Position = Contact closure activates door interlock.
OP Position = Open contact activates door interlock.
2) Controller Output (H14): Man Position = Controller output will ramp to a pre-
determined value determined by potentiometer R9.
S/H Position = Controller output will lock at the value it
was when the option was activated.
2.11 SYSTEM START
Closure of the System Start contact enables the control algorithm and guarantees the output starts
from a known value (0vdc, 4-ma, etc). If System Start is not activated, the control algorithm is
disabled and the controller output will remain at the minimum value.
(NOTE: If not interlocked with fan start command, jumper terminals to enable controller)
3.0 PRE-STARTUP CHECK
3.1 Equipment Needed
1) 4-1/2 Digit Digital Volt Meter (DMM)
3.2 Pre-Startup Check
(Refer to Figure 1.0 for test point and adjustment locations)
1) With 24VAC power applied to the Guardian Plus, Verify Display is illuminated.
2) Open access door and connect + probe of DMM to TP7 (PROCESS) and the - probe to TP1
(GND). Disconnect one side of ROOM and REFERENCE tubing from fittings. Verify a reading of
0∀.005vdc. If out of specification, adjust ZERO potentiometer (R4) for 0.000vdc.
3) Verify system start LED (LED2) is off and MIN OUTPUT controller status LED is illuminated.

6
Space Pressure Monitor MIN OUTPUT
NORMAL
CONTROLLER STATUS
NORMAL
ALARM
PCIPARAGON
CONTROLS
INCORPORATED
PRESSURE STATUS
AUDIBLE ALARM
GUARDIAN
Inches of Water Gauge
ALARM ACKNOWLEDGE
MAX OUTPUT
CONTROL INTERRUPT
ALARM
ALARM
DELAY
ADJUST
ZERO SPAN SETPOINT
INTER
IMAN
VS/H
ALARM SP
C SP
PLUS
AUDIBLE
ALARM
SPANZEROINT.SP EXT.SP EXT.SP
10V I ZERO I SPAN
MANUALERROR
OUTPUT MANUAL
ROOM
REFERENCE
MODEL ATE-100
LOW PRESSURE
MODEL PS-100
PRECISION
MODEL AP-100
AIR PUMP
AIR SOURCE MANOMETER
-
+
GND
FIGURE 1.0 GUARDIAN PLUS PRE-STARTUP CHECK
4.0 CALIBRATION PROCEDURES
(NOTE):
1) Removal of Guardian Plus from the wall will be required to perform the following calibration
procedure.
2) All voltage measurements will be performed with DMM (-) Probe attached to TP1.
3) Refer to Figure 1.0 for test set-up and Figure 2.0, 3.0 & 4.0 for test point and potentiometer
locations.
4) Equipment needed: 1) 4-1/2 Digit Multi Meter
2) Precision Manometer
3) Low Pressure Air Source
4.1 Power Supply
1) Turn system power (24 VAC) ON
2) Monitor TP2 and verify a reading of +5.0 + .6 vdc.
3) Monitor TP3 and verify a reading of -4.5 + .6 vdc
4) Monitor TP4 and verify a reading of +15 ∀.6 vdc.
5) Monitor TP5 and verify a reading of +2.5 ∀.1vdc.
6) Monitor TP6 and verify a reading of -2.5 ∀.1vdc.
4.2 Input / Process Output & Display Scaling

7
(Note: To determine the output configuration (CURRENT or VOLTAGE), refer to the label on
the back side of the access door)
1) With zero input pressure to the transducer -
a. Adjust R4 (ZERO) for a reading of 0.0 + .001 VDC at TP7.
b. PROCESS OUTPUT ZERO:
CURRENT (Uni-Polar Range)- Adjust R89 (ZERO) for a reading of 4.0∀.01MA
between J2 PROCESS (OUT+) and (GND) terminals.
CURRENT (Bi-Polar Range)- Adjust R89 (ZERO) for a reading of 12.0∀.01MA
between J2 PROCESS (OUT+) and (GND) terminals.
VOLTAGE (Uni-polar Range)- Adjust R75 (ZERO) for a reading of 0.00
∀.01 vdc between J2 PROCESS (OUT+) and (GND) terminals.
VOLTAGE (Bi-polar Range)- Adjust R75 (ZERO) for a reading of 5.00
∀.01 vdc between J2 PROCESS (OUT+) and (GND) terminals.
2) With full scale pressure applied to the ROOM port (See label on back of access door) -
a. Adjust R10 (SPAN) for a reading of 1.00 + .001 VDC at TP7.
b. OUTPUT SPAN:
CURRENT - Adjust R87 (SPAN) for a reading of 20.0ma between J2 PROCESS (OUT+)
and (GND) terminals.
VOLTAGE - Adjust R84 (SPAN) for a reading of 10.00vdc between J2
PROCESS(OUT+)and (GND) terminals.
c. Adjust R38 (DISPLAY) for full scale value on the LED display.
3) Repeat steps 1 and 2 to verify that they meet specification tolerances. Large
adjustments to either zero or span may result in a slight shift in the other adjustment.
4.3 Controller Output Scaling
(Note: All adjustments are made on the control board located under the access door.)
1) CURRENT OUTPUT ZERO:
a. Set H12 jumper to -5vdc if H13 is in the INV position or +5vdc if H13 is in the DIR position
and verify controller status MIN OUTPUT LED is illuminated.
b. Adjust R79 (I ZERO) for a reading of 4.0ma between J2 CONT (OUT+) and (GND) terminals.
2) OUTPUT SPAN:
a. Set H12 jumper to +5vdc if H13 is in the INV position or -5vdc if H13 is in the DIR position
and verify controller status MAX OUTPUT LED is illuminated.
b. CURRENT - Adjust R77 (I SPAN) for a reading of 20.0ma between J2 CONT (OUT+) and
(GND) terminals.
VOLTAGE - Adjust R51 (10V) for a reading of 10.0vdc between J2 CONT (OUT+) and
(GND) terminals.
c. Return H12 jumper to the original position.
5.0 CONTROLLER JUMPER SELECTIONS
5.1 Controller Action

8
(Note: All adjustments are made on the control board located under the access door.)
1) The controller action is determined by the jumper position of H13.
SELECTED ROOM
PRESSURE
ACTION H13 JUMPER
SELECTION
Positive
Positive
Negative
Negative
Direct
Reverse
Direct
Reverse
DIR
INV
INV
DIR
TABLE 5.1 CONTROLLER ACTION MODIFICATIONS
5.2 Reset
1) Based on a field survey performed, the three (3) most commonly used reset rates have been
selected by the factory. These rates are user selectable by positioning H15 jumper to the respective
resistance on the controller board. The following table gives the jumper position, resistance value
and time rate.
H15 JUMPER
SELECTION
TIME RATE
1
2
3
40 Secs.
1.66 Min.
2.5 Min.
TABLE 5.2 RESET JUMPER SETTINGS
5.3 Inverse Derivative (1/D)
1) Inverse Derivative (1/D): All inverse derivative time rates have been computed for a 10%
proportional band (factory set standard). These rates are user selectable by positioning H16 jumper
to the respective resistance on the controller board. The following table gives the jumper position,
resistance value and time rate.
H16 JUMPER
SELECTION
TIME RATE
1
2
3
32 Sec.
1.1 Min.
1.9 Min.
TABLE 5.3 INVERSE DERIVATIVE JUMPER SETTINGS
5.4 Process Output

9
1) Process Output signal can be changed between voltage or current by positioning H5 jumper to I or
V. The following table gives the jumper position and corresponding output selection.
H5 JUMPER
SELECTION
OUTPUT
SELECTION
I
V
4-20 MA
0-10VDC
TABLE 5.4 OUTPUT SELECTION
5.5 External Controller Setpoint
1) The Guardian Plus can be set up for an External Controller Setpoint signal by positioning H20
jumper located under the access door to EXT. The factory default setup is for 4-20ma input but can
be configured for 0-10vdc.
H20 JUMPER
SELECTION
SETPOINT
SELECTION
EXT
INT
EXT. Setpoint
INT. Setpoint
TABLE 5.3 SETPOINT CONFIGURATION
5.6 Controller Output
1) Controller Output signal can be changed between voltage or current by positioning H21 jumper to
I or V. The following table gives the jumper position and corresponding output selection.
H21 JUMPER
SELECTION
CONTROLLER OUTPUT
SELECTION
I
V
4-20 MA
0-10VDC
TABLE 5.6 CONTROLLER OUTPUT SELECTION

10
DETAIL A
ELECTRICAL CONNECTIONS
REFERENCE PRESSURE CONNECTION
ROOM PRESSURE CONNECTION
PROCESS
24VAC
IN+
GND
POWER SP.
EXT.
OUT+
OUT+
GND
GND
ROOM
CONT REFERENCE
COM
NC
NO
ALARM
DOOR INTERRUPT(DRY CONTACT)
SYSTEM START(DRY CONTACT)
PROCESS OUTPUT(0-10VDC/4-20MA)
CONT. OUTPUT(0-10VDC/4-20MA)
EXT. INPUT(0-10VDC/4-20MA)
EARTH GROUND
24VAC POWER
J1
J2
J4
REMOTE ALARM
NC
COM
NO
SENSOR
PRESSURE
REFERENCE
PRESSURE
SENSOR
ROOM
MONITOR
PANEL
(CONDUIT BETWEEN SENSORS AND
1/4"X.170 TUBE BARB
MONITOR PANEL MAY BE REQUIRED).
DETAIL A
SEE
H3BD-3/4-1 OR EQUAL)
ELECTRICAL BOX (T&B PART NUMBER:
TRIPLE GANG DOUBLE DEEP
FIGURE 2.0 FIELD CONNECTION LAYOUT

11
COMPONENT SIDE
REFERENCE
ROOM
24VAC
CONT. S.P. INPUT
F1
IN+
J1
REFERENCE PRESSURE CONNECTION
ROOM PRESSURE CONNECTION
GND
GND
OUT+
OUT+
GND
J2 H10 CL
OP
H2
R106
-2.5V ADJ.
TRANSFORMER
T1
CONT.
ALARM
ALARM SP
-
+
SP.
AUTO
H3
DISPLAY SPAN
SPAN
ZERO & SPAN
-2.5V
-5V
TP2
TP3
+5V
TP1
GND
GNDTP1
+2.5V
+15V
TP5
TP6
TP4
TP7DPT
ALARM
R84
NC
COM
NO
J4 INV
NON-
INV H1
RELAY
ZERO & SPAN
PROCESS CURRENT OUTPUT
PROCESS VOLTAGE OUTPUT
R38
R89
CURRENT
ZERO
R75
H5
R87
ZERO
VOLTAGE SPAN
CURRENT
SPACE
POS
NEG
AUTO
H4
FIGURE 3 COMPONENT AND ADJUSTMENT LOCATIONS
MANUAL
R10
SPAN
TP3TP6
-2.5V -5V
+2.5V
DPT
+15V
GND
+5V
GND
TP5
TP4
TP2
TP1
TP7 TP1
ZERO
R4
REFERENCE CONT SP V
ACTION(H13)
OFF
ON
ROOM ALARM SP
ALARM
SETPOINT
ADJUST
DELAY
ALARM
R20
-
GND
+
H12
INTER
LED
DIR
I(H15)
PID(H16)
INV
OUTPUT
I
ERROR
EXT +
H20 INT H19 -
10V I ZERO
INT.SP EXT.SP
ZERO
S/H
MAN
MANUAL
I SPAN
EXT.SP
SPAN
FIGURE 4 CONTROLLER COMPONENT AND ADJUSTMENT LOCATIONS
Table of contents