5
3. Installation
3.1. Connecting The Cooling Water Unit
The cooling water unit should be connected in accordance
with local regulations. As far as possible, make the
connections so that the flow of the water is visible (with the
flowmeter).
Before installing the unit, check for cleanliness.
Foreign bodies on the valve seat can prevent
full closing.
The temperature of the cooling water at the
cooling water inlet port must be at least 10°C
and must not exceed 30°C (maximum). The
pressure of the cooling water at the inlet port
must be at least 0.3 bar higher than at the outlet
port. The maximum cooling water pressure of
10 bar must not be exceeded. If higher pressures are involved
a pressure reducing valve must be fitted.
Fitting Cooling Water Units
The customer must fit any cooling water unit which is contai-
ned in the delivery:
➡Remove the stopper from the 1/2“ inner thread on the
underside of the pump.
➡Screw the 90° angle piece 76 of the cooling water piping
into the 1/2” inner thread on the underside of the pump
adjacent to the exhaust flange.
– Seal the thread with a liquid sealing agent.
➡Make further pipe connections as shown in the illustration
(screw joint 85 is metallically sealed).
– Seal all other threads with a liquid sealing agent.
➡Place cooling water regulator sensor 88 in protective slee-
ve 83 and position in the boring provided in the pump
casing.
➡Secure sensor 88 in protective sleeve 83 with slotted secu-
ring nut 84 but only lightly tighten.
Position capilliary pipe 88.1 so that it does not
vibrate (danger of breakage from too much
vibration) and so that it cannot be damaged nor
squashed. The smallest sweep is 10mm. Do not
feed the capilliary pipe through areas where
temperatures higher than those at the sensor
are involved.
➡Screw hose nozzle 75 into the 1/2” inner thread for the
cooling water outlet in the pump casing.
➡
Secure the hoses for the cooling water in and outlets with
circlips and ensure firm seating.
➡
Fit the dirt trap in the inlet line.
➡
Use a screwdriver on the cooling water regulator adjusting
disk (position a) to set the required operating temperature.
The setting range is 40-85 °C (preset at works).
Water or some other appropriate medium can be used as the
coolant. The pump can be connected to the cold water mains
or to a cooling aggregate (please see ”Accessories”).
The minimum requirements for the cooling water where
connection to the water mains is involved is that it must be
mechanically clean, optically clear, no turbidity, no sediment,
chemically neutral.
Oxygen content: max. 4 mg/kg
Chloride content: max. 100 mg/kg
Carbonate hardness: max. 10 ° dH
Consumption of potassium
permanganate: max. 10 mg/kg
Carbon dioxide: Undetectable
Ammonia: Undetectable
pH-value: 7 - 9
Max. fore-line over pressure: max. 10 bar
Minimum flow rate: 25 l/h at 15 °C
81/ 83/
75 84/
88 88.1 86 80/75 76 85 77 76
Installation, Cooling Water Regulator
75 Hose nozzle
76 90° angle piece
77 Extension
80 Cooling water connection, inlet
81 Cooling water connection, outlet
83 Protective sleeve
84 Securing nut
85 Screw joint 1/2”
86 Cooling water regulator
88 Sensor
88.1 Capilliary pipe