Page 13
2-pipe Control Logic -With 6-way Modulating Valve
COOL MODE
When unit is turned on in cooling mode:
a) If Tr ≥ Ts + 1ºC (Modbus 300033 setting), MTV1 is turned on. AUX1 is closed. Fan is turned on at setting speed. DA1 is
turned on at 0VDC for 2 minutes, then check Ti1:
When Ti1≤8ºC, DA1 output is based on water temperature difference (Ti1/Ti2) and Modbus parameter 300027 setting PID
calculation. The output is 4~0VDC.
When 8<Ti1≤10ºC, DA1 output is based on water temperature difference (Ti1/Ti2) and Modbus parameter 300027 setting
minus 1 PID calculation. The output is 4~0VDC.
When 10<Ti1≤12ºC, DA1 output is based on water temperature difference (Ti1/Ti2) and Modbus parameter 300027 setting
minus 2 PID calculation. The output is 4~0VDC.
When 12<Ti1≤15ºC, DA1 output is based on water temperature difference (Ti1/Ti2) and Modbus parameter 300027 setting
minus 3 PID calculation. The output is 4~0VDC.
When 15<Ti1≤28ºC (Modbus 300017 setting), DA1 output is kept at 0VDC.
When Ti1>28ºC (Modbus 300017 setting), DA1 output is 4VDC. and report pre-heat alarm.
b) If Tr < Ts-1ºC (Modbus 300033 setting), then cool operation is terminated and MTV1 and AUX1 are turned off. Indoor fan
runs at set speed. DA1 output is 5VDC.
When unit is turned off, MTV1 and AUX1 are off. DA1 is 5VDC. Fan is turned off after 30s.
The range of Ts is 16 - 30ºC
Indoor fan speed can be adjusted to low, medium, high and auto.
LOW TEMPERATURE PROTECTION OF INDOOR COIL IN COOLING MODE
If Ti1 ≦2 ºC for 2 minutes, MTV1 is turned OFF. DA1 is set to 5Vdc. Indoor fan is turned on at Medium speed if fan runs at low
speed. If Ti1 ≧5ºC for 2 minutes, MTV1 is turned ON. DA1 is set to original status. Indoor fan is changed to set speed.
FAN MODE
Indoor fan speed can be adjusted for low, medium and high. If fan speed is set auto by Modbus, fan runs at low speed.
HEAT MODE
Without Electrical Heater(Modbus300043=0)
When unit is turned on in heating mode:
a) When Tr ≤ Ts - 1 ºC(Modbus 300033 setting) , MTV2 and AUX2 are turned on. DA1 is at 10VDC for 2 minutes, then check
Ti1:
If Ti1 < 28ºC (Modbus 300017 setting), fan is turned on at low speed. DA1 is at 10VDC.
If 28ºC<Ti1< 28(Modbus 3000017 setting)+4ºC, fan is on at original state. DA1 is at original state.
If Ti1 ≥ 28(Modbus 3000017 setting)+4ºC , fan is on at setting speed. DA1 output is based on water temperature difference
(Ti1/Ti2) and Modbus parameter 300027 setting PID calculation. The output is 6~10VDC.
If Ti1 sensor is damaged, fan is worked at setting speed.
b) When Tr > Ts- 1ºC (Modbus 300033 setting) , MTV1 and AUX2 are turned off. DA1 is at 5VDC. fan is turned on at lowest
speed.
When unit is turned off, MTV1 and AUX2 are turned off. DA1 is at 5VDC. Fan is turned off after 2 minutes.
With Electrical Heater as booster (Modbus300043=1)
When unit is turned on in heating mode:
a) When Tr ≤ Ts - 1 ºC(Modbus 300033 setting) , MTV2 and AUX2 are turned on. Fan is turned on at setting speed. DA1 is
at 10VDC for 2 minutes, then check Ti1:
If Ti1 < 28ºC (Modbus 300017 setting), EH is turned on. DA1 is at 10VDC.
If 28ºC<Ti1< 28(Modbus 3000017 setting)+4ºC, EH is kept at original state. DA1 is at original state.
If Ti1 ≥ 28(Modbus 3000017 setting)+4ºC , EH is turned off. DA1 output is based on water temperature difference (Ti1/Ti2)
and Modbus parameter 300027 setting PID calculation. The output is 6~10VDC.
If Ti1 sensor is damaged, fan is worked at setting speed.
b) When Tr > Ts -1ºC (Modbus 300033 setting) , MTV2 and AUX2 are turned off. EH is turned off. DA1 is at 5VDC. fan is
turned on at low speed.
When unit is turned off, MTV2 and AUX2 are turned off. DA1 is at 5VDC. Fan is turned off after 2 minutes.
OVER-HEAT PROTECTION OF INDOOR COIL
If Ti1 ≥ 75ºC, then MTV1, AUX2, DA1 and EH are turned off. Indoor fan remains on and runs at high speed.
If Ti1 < 70ºC, then unit keep original state.
If the indoor coil temperature sensor is damaged or not connected, then the protection mode will be overridden and the
unit will work according to the pre-heat and post-heat program.