General Precautions
1. Before using Invisimo, read all instructions and cautionary markings on : (1) Invisimo (2)
the batteries (3) this manual
2. CAUTION --To reduce risk of injury, charge only lead-acid type rechargeable batteries.
Other types of batteries may cause damage and injury.
3. Do not expose Invisimo to rain, snow or liquids of any type. Invisimo is designed for
indoor.
4. Do not disassemble Invisimo. Take it to a qualified service center when service or repair is
required.
5. WARNING: Provide ventilation to outdoors from the battery compartment. The battery
enclosure should be designed to prevent accumulation and concentration of hydrogen gas
at the top of the compartment.
6. NEVER charge a frozen battery.
7. Be extra cautious when working with metal tools around batteries. Short-circuiting the
batteries could cause an explosion.
8. For battery installation and maintenance: read the battery manufacturer’s installation and
maintenance instructions prior to operating.
Personnel Precautions
1. Have plenty of fresh water and soap nearby in case battery acid contacts skin, clothing, or
eyes.
2. Avoid touching eyes while working near batteries.
3. Never smoke or allow a spark or flame in vicinity of a battery.
4. Remove personal metal items such as rings, bracelets, necklaces, and watches when
working with batteries. Batteries can produce a short-circuit current high enough to make
metal melt, and could cause severe burns.
5. If a remote or automatic generator start system is used, disable the automatic starting
circuit or disconnect the generator to prevent accident during servicing.
Specification
MODEL Invisimo 700 1000 1500
2000 3200
CAPACITY VA / Watts 700VA /
450W 1000VA /
600W 1500VA /
900W
2000VA /
1200W 3200VA /
2000W
AC Voltage 115VAC / 230VAC, 1 Phase + Neutral
Voltage Tolerance (AC) 90~135VAC / 187~264VAC ±4%
DC Voltage 12VDC 24VDC
Voltage Tolerance (DC) 10VDC ~ 14VDC 20VDC ~ 28VDC
INPUT
Frequency 47Hz ~ 53Hz / 57Hz ~ 63Hz
Voltage 115VAC / 230VAC
Voltage Tolerance ±7%
Frequency 50Hz or 60Hz
Frequency Tolerance ±3Hz in Battery Mode
Transfer Time Maximum 10 milliseconds
OUTPUT
Voltage Waveform Modified Sinewave
Type Maintenance free dry type (suggested)
Capacity Up to 1000Ah
Battery Low Level 10.8V ±0.2V 21V ±0.5V
Battery Cut-off Level 10V ±0.2V 20V ±0.5V
BATTERY
Battery house External; Rack or Cabinet (Optional)
Battery Charge Voltage 13.6VDC ±0.2VDC 27.5V ±0.3V
Charge Capacity 40A max. (Adjustable)
CHARGER
Over Charge Protection 14.5VDC ±0.5VDC 29V ±0.5V
Control Panel On/Off button, Battery charge current adjustment
Line Mode Line-On LCD lighting
Battery Mode Back-Up LCD lighting
Over Load O-Load LCD lighting
Over Temp. O-Temp LCD lighting
UPS Off Cut-Off LCD lighting
Load Level 5-Step LCD lighting
INDICATORS
& CONTROL
PANEL Indicators
Battery Level 5-Step LCD lighting
Full Protection Over load, Short circuit, Over charge, Over temperature, Input
& Output fuse
Noise Level Less than 45 dBA (at 1 meter)
Operating Temperature 0℃~ 40℃
Storage Temperature -20℃~ +70℃
Relative Humidity Maximum 0-90% (non-condensing)
Type of Cooling Forced with fan
PROTECTION
Installation Height <3000 meters, elevation
Dimension, D*H*W 420*160*218mm
PHYSICAL
Weight, w/o Battery 9kgs 11kgs 14kgs 16kgs 20kgs
DESIGN, MANUFACTURE, SERVICES ISO 9001