18
The H/E, blending valve, flow-switch tee and the strainer fitting
can be removed from the boiler as a sub-assembly for ease of
working.
1 Refer to General above.
2 Turn off mains water supply (remove strainer cap to drain
if necessary).
3 Isolate primary side of H/E by closing the gate valve near
the top of the H/E, and closing isolation valve below
pump. Drain via pump bleed screw if necessary.
4 Disengage flow-switch from the tee fitting by loosening
union nut.
5 Loosen the compression nuts below the strainer and
blending valve and above the gate valve and pump.
6 Lift H/E sub-assembly away from the boiler.
7 Separate the pipework from the H/E by removing the M5
nuts and the retaining plates. NB Top and bottom plates
differ slightly.
8 The H/E and/or blending valve can now be replaced.
NB Ensure that the O-ring joints on the H/E connections
are kept clean. Do not allow oil to come into contact with
the O-rings.
9 Check and adjust mini-expansion pre-charge pressure to
4.0 to 5.0 bar and clean strainer element before
reassembling in reverse order. NB Ensure that the flow
switch is replaced and the arrow pointing upwards and
the ‘flats’ in line with the pipework.
10 When replacing expanion vessel, ensure it seals on
washer within socket. Any sealant must be approved for
use with potable water.
Thermostats – Control & Cold Start Fig.12.1
a Refer to General above.
b Disconnect the two thermostat leads.
c Remove the clip and phial from the pocket.
d Remove the two retaining screws holding the
thermostat housing, note the routeing of the capillary
tubing and remove.
e Carefully replace the new capillary tubing and phial
ensuring that the phial is secured with the spring clip.
Note: Do not bend capillary tubing to a radius of less than
20mm.
f Hold thermostat housing in position and replace
retaining screws. Turn spindle fully clockwise (Control
‘stat only)
g Reconnect electrical leads.
Overheat and Limit Thermostat Fig.12.2
a Refer to General above.
b Disconnect the two leads.
c Remove clip and phial from the pocket.
d Remove the retaining nut holding thermostat housing,
note the routeing of the capillary tubing and remove.
DHW heat exchanger (H/E) e Carefully replace the new capillary tubing and phial,
ensuring the latter is retained with the spring clip.
f Hold thermostat in position and replace retaining nut.
Reconnect leads.
Programmer Fig.12.2
a Refer to General. Remove switch panel.
b Disconnect leads from programmer noting relative
position of colour coded wires.
c Working from rear of switch panel, remove two 4BA
screws and washers and remove programmer.
d Replace in reverse order ensuring the leads are
correctly connected – see wiring diagram Fig 10.2 – and
re-fit switch panel.
e Before restarting the appliance, switch on the
programmer battery by moving the slider switch on rear
of programmer body to the right (when facing
appliance).
Note: The programmer is fitted with a long-life lithium
battery, which should only be replaced by suitably
qualified personnel. A discharged battery should be
disposed of through a registered professional agency for
waste material.
f Set new programmer to customer’s requirements.
Relay Fig.12.2
a Refer to General above
b Remove one M4 screw and loosen the other. Relay can now
be removed and leads transferred.
EMC Filter Fig.12.1
a Refer to General above
b Remove both fixing screws. Release wiring between filter
and both terminal blocks.
c Replace filter. Reconnect wiring (including earth lead) and
MAINTAIN CORRECT LINE/NEUTRAL POLARITY
See Fig. 10.1
Safety Relief Valve Fig.12.1
a Refer to General above
b Loosen cap on automatic air vent and drain
approx. 0.5 litre out of thermal store. Unscrew nut on
discharge pipe and nut on pressure gauge fitting.
c Loosen both M4 grub screw (2mm Hex-Key) in socket
and pull valve clear of socket.
d Refill system – see Section 12.
Automatic Air Vent Fig.12.1
a Refer to General above
b Release pressure within primary system and drain
approx. 0.5 litre out of thermal store. Body of vent can
now be unscrewed.
c Replace and refill system – see Section 12.
Low Water Switch Fig.12.1
a Refer to General Above
b Release wires at RH terminal block
c Reduce pressure and drain approx 0.5 litre out of
thermal store and remove outer flange (6 screws).
d Unscrew large plastic nut and remove switch.
e IMPORTANT – When fitting new switch it is essential to
keep ‘crocodile’ float hinge horizontal so that float can
drop. Use a small adjustable spanner to hold flats on
body in a vertical plane whilst nut and grommet are being
re-tightened. DO NOT OVER-TIGHTEN LARGE NUT –
HAND TIGHT + 1 FLAT IS RECOMMENDED.
f Re-connect wires, refill system – see Section 12 – and
test for operation and leak tightness.
Pressure Gauge
a Refer to General above
b Release pressure within primary system.
c Unscrew nut retaining capillary tube to safety relief valve.
d Remove gauge from panel by squeezing lugs on gauge
body
e Fit new gauge ensuring that capillary tube is routed well
away from electrical connections.
f Refill system – see Section 12.
Sealed system models only