Power Sentry EAC ISSM 375 SM User manual

IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. DO NOT USE OUTDOORS.
2. Do not mount near gas or electric heaters.
3. Do not use this equipment for other than its intended use.
4. The EAC ISSM 375 SM should be mounted securely and in locations and at heights where it will not readily
be subjected to tampering by unauthorized personnel.
5. The use of accessory equipment and replacement parts not recommended by the original manufacturer
may cause an unsafe condition and void the warranty.
6. The AC voltage rating of this equipment is specified on the product label. Do not connect the
EAC ISSM 375 SM equipment to any other voltage.
7. Use only the battery part number specified for use with the EAC ISSM 375 SM. Failure to do so may cause
an unsafe condition, will void warranty, and result in non-compliance with UL specifications.
8. The EAC ISSM 375 SM uses a sealed valve regulated lead acid battery. Batteries can be punctured if not
handled properly, therefore use caution when servicing batteries. In the event battery acid comes in contact
with eyes or skin, flush with fresh water and consult a physician immediately.
9. Install in accordance with the National Electrical Code and local regulations.
10. Installation and servicing should be performed by qualified personnel.
11. Electricians and end-users need to ensure product system compatibility before final installation.
SAVE THESE INSTRUCTIONS
THIS UNIT CONTAINS A
RECHARGEABLE VALVE-REGULATED
LEAD ACID BATTERY. PLEASE
RECYCLE OR DISPOSE OF
PROPERLY.
INSTRUCTION MANUAL
INTERRUPTIBLE AC INVERTER SYSTEM
MODEL EAC ISSM 375 SM
FOR EMERGENCY LIGHTING POWER

Page 2
Wiring
1. CONNECTING THE INVERTER AC INPUT (FIGURE 1)
The Inverter AC Input leads (designated “Input Leads”) serve as your normal power sense and charging input for the
internal battery, therefore the EAC ISSM 375 SM requires an unswitched AC input of either 120 or 277 VAC. If a local
switch is present on the designated emergency circuit, the EAC ISSM 375 SM input must be wired ahead of the switch.
A. For 120V supply, connect the AC line wire to the BLACK lead coming from the inverter housing labeled INPUT
WIRES. For 277V supply, connect the AC line wire to the ORANGE lead coming from the inverter housing
labeled INPUT WIRES. CAUTION: Cap the unused BLACK or ORANGE input wire. Failure to do
so may result in equipment failure and void the warranty.
B. Connect the Neutral wire to the WHITE lead labeled INPUT.
C. Connect the ground wire in accordance with local and national codes. A GREEN wire is provided for this purpose.
DO NOT ENERGIZE THE CIRCUIT AT THIS TIME.
2. CONNECTING THE NORMAL AC INPUT (FIGURE 1)
The Normal AC input leads (designated “Flying Leads”) provide normal power to the designated emergency circuit. If
the designated circuit is for Normally-Off fixtures (ie. emergency operation only - come on only during power failure), the
Normal AC input leads are not required and should be capped separately.
A. NORMALLY-ON FIXTURES - Select the proper voltage “flying lead” (BLACK for 120V, ORANGE for 277V)
and connect to the unswitched AC input. Cap the unused lead. Connect the Neutral (WHITE) “flying lead” to the
unswitched AC input neutral of the supply line feeding the input wires. Refer to Figure 1.
B. FIXTURES ON LOCAL SWITCH (fixtures may be turned on and off locally, but will come on during power
failure regardless of switch position) - Connect the load side of the switch to the proper voltage “flying lead” from
(BLACK for 120V, ORANGE for 277V). Cap the unused lead. Ensure the the Inverter AC Input (“Input Leads” are
connected ahead of the local switch. Refer to Figure 1.
INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off.
NOTE: The battery is shipped in separate packaging for ease of handling. Store the battery in a cool, dry and safe
location until ready for installation. The battery may be kept in storage for up to 3 months without recharging.
CAUTION: This is a dual input and output voltage unit. It can be connected to either a 120 or 277 volt supply.
The input and output voltages must match.
NOT FOR USE WITH HID LIGHTING
Mounting the EAC ISSM 375 SM
1) Remove the front cover of the EAC ISSM 375 SM by removing the two (2) screws located at the top of cover.
2) Knock out the keyhole slots at the rear of the unit and use for mounting the EAC ISSM 375 SM securely to the wall. There
is an additional round hole for a #10 screw in the cabinet. Code requires that an additional screw be used through this
hole to prevent the unit from being inadvertently lifted up off the keyhole slots. Do not drill any holes in this unit.If a
recessed junction box is to be mounted in the wall behind the unit, make sure an unswitched AC supply of proper rated
voltage is extended to the box, and that the remote wiring to the emergency fixtures is also extended to the box prior to
mounting the unit. A 1/2″conduit knockout is provided in the back of the unit for wires to pass through. Sixteen inches of
wire should be routed into the unit from the recessed junction box. NOTE: Input and output wires must be run in separate
conduits. CAUTION: Do not drill holes into the cabinet; drill filings may damage the unit and keep it from operating. If larger
knockouts are required, use a chassis-punch through the appropriate knockout to punch out a larger knockout.
3) If the wiring is to be external to the wall, extend both the unswitched supply, the normally-on lamp supply (if used),
and the load wires to the unit at this time.
CAUTION: The EAC ISSM 375 SM must be mounted securely. Do not rely on the junction box for supporting the
weight of the unit. Mount the EAC ISSM 375 SM securely to the wall using the keyhole slots provided.
ALWAYS CONSULT LOCAL CODES FOR STRUCTURAL REQUIREMENTS WHEN MOUNTING THE UNIT.

Page 3
FIGURE 1 - EAC ISSM 375 SM WIRING CONNECTIONS
IIS_375_550_WITH CIRCUIT BREAKER.EPS
INVERTER - INTERRUPTIBLE WITH CIRCUIT BREAKER
NORMAL
CIRCUIT
NORMAL
LIGHTING LOAD
DESIGNATED
EMERGENCY LOAD
BRANCH
CIRCUIT
OPERATES IN BOTH
NORMAL AND EMERGENCY
MODES. CIRCUIT MUST BE
ISOLATED FROM
NORMAL CIRCUITS.
BATTERY
INVERSION
CIRCUIT
BREAKER
WALL
SWITCH
(IF PRESENT)
NORMAL
AC INPUT
(FLYING LEADS)
INVERTER
INPUT LEADS
CONVERSION
AC INPUT FOR THE INVERTER - MUST BE
UNSWITCHED. SELECT PROPER VOLTAGE
LEAD AND CAP UNUSED LEAD.
GROUND WIRE - CONNECT FIXTURE SUPPLY
GROUND AND UNIT GROUND IN ACCORDANCE
WITH LOCAL AND NATIONAL CODES.
IF USING A SECONDARY AC INPUT, SELECT
PROPER VOLTAGE LEAD AND CAP UNUSED
LEAD.
USE A 277V RATED SWITCH IF CONNECTING
TO 277V INPUT.
FLYING LEADS ARE FOR THE NORMAL AC INPUT
(SWITCHED OR UNSWITCHED) - SELECT PROPER
VOLTAGE LEAD AND CAP UNUSED LEAD. CIRCUIT BREAKER CONNECTIONS - CONNECT
PROPER LOAD VOLTAGE TO CIRCUIT BREAKER
AND CAP UNUSED LEAD.
GROUND
WIRE
WHT (NEU)
ORG (277V)
BLK (120V)
GREEN
ORG (277V)
BLK (120V) (120V)
(277V)
VIOLET (120V)
YELLOW (277V)
(120V)
(277V)
ALTERNATE
AC INPUT
(120V OR 277V)
GRAY (NEUTRAL)
YEL/VIO (120/277V)
EMERGENCY
CIRCUIT
WHT (NEU)
3. CONNECTING EMERGENCY FIXTURES (FIGURE 1)
A. Connect emergency fixtures to the correct output leads. The color code is as follows: YELLOW/VIOLET for
120/277V and GRAY for NEUTRAL. All remote circuitry is to be wired in accordance with Article 700 of the National
Electric Code. Do not exceed the total rating of the EAC ISSM 375 SM. When making connections to the EAC
ISSM 375 SM, DO NOT connect the Input Neutral (WHITE) to the Output Neutral (GRAY).
B Connect the Fixture Supply Ground to the EAC ISSM 375 SM Ground.
DO NOT ENERGIZE THE CIRCUIT AT THIS TIME.
Consult the EAC ISSM 375 SM Application Notes for connecting the unit to specific lighting loads. Application Notes are
available on the internet or through Customer Service.
4. CONNECTING THE INTERNAL CIRCUIT BREAKER
A. Two leads are provided for connection to the internal circuit breaker. Select the proper voltage lead (VIOLET
for 120VAC or YELLOW for 277VAC) and connect it to the circuit breaker. Cap the unused lead. Push the circuit
breaker switch to the ‘closed’ position so that the indicator on the circuit breaker shows RED.
CAUTION: Before proceeding to Wiring Step 4, make sure that all unused wires are properly capped.
Failure to do so may result in an unsafe condition and equipment failure.
DO NOT ENERGIZE THE CIRCUIT AT THIS TIME.
5. INSTALLING THE BATTERY
ATTENTION: Use only battery part number ELB AC04 with the unit. See Page 1 of this instruction manual.
A. Before installing the battery, check the torque on the hardware that connects the polarized connector to the
terminals as these connections may have loosened in transit and storage. The proper torques should be
70 in/lbs for a Screw Stud terminal, and 65 in/lbs for an L Flag terminal.
B. Install the battery into the EAC ISSM 375 SM with the terminal posts facing toward the front of the unit. NOTE:
The EAC ISSM 375 SM battery is heavy. To avoid injury, exercise caution when handling the battery.
C. Plug the battery connector together.
Note: Neither the indicator lights nor the emergency fixtures will illuminate at this time. Also, please note that
there are 2 battery tie down lugs in the event that it is required that the battery be held in place. Please contact
Customer Service to purchase this accessory if needed.
For Screw Stud batteries, initial torque is 70 in/lbs, annual is 65 in/lbs.
For L-Flag batteries, initial torque is 65 in/lbs, annual is 52 in/lbs.
NOTE: The emergency indicator lights will not illuminate at this time.
6. COMPLETING INSTALLATION
A. Energize the AC supply. The Ready (Yellow) Indicator and the Charging (Red) Indicator will illuminate.
The Inverter On (Green) Indicator will not illuminate at this time.

Page 4
Rev. 1500
68375-420
ONE LITHONIA WAY, CONYERS, GEORGIA 30012, TELEPHONE 800-334-8694
EMCSA00799-REV B 101917
B. Operate the Test Switch for approximately 10 seconds. Observe that any emergency fixtures do not go out, that
the Inverter On (Green) Indicator comes on, and that any normally off fixtures come on.
C. Release the Test Switch. Normally Off fixtures and the Inverter On (Green) Indicator will extinguish. Normally
On, emergency, and any switched fixtures will return to their normal operating mode.
D. Reinstall the front cover using all the original hardware.
E. Affix red “EMERGENCY CIRCUIT” label (provided) to the panelboard dead front cover near the circuit breaker
feeding the EAC ISSM 375 SM.
Operation
Normal Mode - AC power is present and operates the fixtures as intended. The EAC ISSM 375 SM is in the standby
charging mode. The Ready (Yellow) Indicator will be lit providing a visual indication that the unit is in Standby Mode.
Emergency Mode - The AC power fails. The EAC ISSM 375 SM senses the AC power failure and automatically
switches to the Emergency Mode. All fixtures, including Normally Off or switched off fixtures, connected to the EAC
ISSM 375 SM will be illuminated for a minimum of 90 minutes. When the AC power is restored, the EAC ISSM 375
SM switches the system back to the Normal Mode and resumes battery charging. See page 1 of the instruction
manual for important operational safeguards and requirements.
Resetting the Circuit Breaker - Should the unit experience an overload situation or a short circuit the breaker will
trip. Before resetting the breaker insure that all wiring is correct, the load side of the inverter must be isolated from all
other power sources. Verify that the load does not exceed the rated capacity of the inverter.
Testing
1) To test the equipment, depress the test switch.The Ready (Yellow) Indicator will go off.The designated fixtures will
either illuminate if they were off or will stay on if they were normally illuminated. The Inverter On (Green) Indicator
will come on.
2)
Release the Test Switch. The Ready (Yellow) Indicator will come on. Normally Off emergency fixtures will extinguish.
The equipment is supplied with an automatic solid state charger designed to fully recharge the battery within 72
hours after AC power is restored, and then maintain the battery in a fully charged state. Allow the battery to charge
for a minimum of 72 hours after installation or power failure before conducting a 90 minute discharge test. The Life
Safety Code and the Authorities Having Jurisdiction require that this test be performed on an annual basis.
Maintenance
1. CAUTION: Always follow proper shutdown procedure before servicing by 1) turning off the AC supply to the equip-
ment, and 2) disconnecting the battery by unplugging the battery connector. Only qualified service technicians
should service this equipment. The use of parts supplied by other than manufacturer may result in an unsafe con-
dition, equipment failure will void the warranty, and result in non-compliance with UL specifications.
2. BATTERY - The manufacturer recommends that the battery terminations be re-torqued on an annual basis.
Re-torque specifications are as follows: Screw Stud terminals 65 in/lbs; L Flag terminals 52 in/lbs. The battery
supplied in this equipment is a high quality maintenance-free Valve Regulated Lead Acid design. It requires no
maintenance and when installed in an ambient temperature of 20° to 30° C (68° to 86° F) its life expectancy is 8
to 10 years. However, as stated above, the equipment must be tested for 90 minutes a minimum of once per year.
When the battery will no longer operate the load for 90 minutes it must be replaced. Use only manufacturer sup-
plied parts. Dispose or recycle the lead-acid battery properly.
Shutdown Procedure
If a shutdown of the IIS unit becomes necessary for routine maintenance or other purposes, always follow proper
shutdown procedure:
1) De-energize the AC supply by locking off the circuit breaker feeding the unit.
2) Disconnect the battery by uncoupling the battery connector between the battery and converter.
When restoring power to the IIS unit, refer to instructions beginning on Page 3, Step 3 for start-up procedures.
CONTACT CUSTOMER SERVICE FOR REPLACEMENT PARTS.
“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”
SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.
Table of contents
Popular Inverter manuals by other brands

ProVista Technology
ProVista Technology GTW1500HF Operation manual

Mitsubishi Electric
Mitsubishi Electric FR-A800 instruction manual

World Video Sales
World Video Sales MicroImage Video Systems PG314N manual

Sungrow
Sungrow SG60KU-M Quick installation guide

Sima
Sima SPV-8 User instructions

SMA
SMA SBS3.7-10 operating manual