Powerbank GO-1000 User manual

GO-1000/GO-2000/GO-3000
ERTN-1000/ERTN-2000/ERTN-3000
Online UPS
Uninterruptible Power Supply System
Version:1.2
User Manual

Table of Contents
1. Important Safety Warning ............................................................................................... 1
1-1. Transportation ......................................................................................................... 1
1-2. Preparation ............................................................................................................. 1
1-3. Installation .............................................................................................................. 1
1-4. Operation................................................................................................................ 1
1-5. Maintenance, service and faults ................................................................................ 2
2. Installation and setup ..................................................................................................... 3
2-1. Rear panel view....................................................................................................... 3
2-2. UPS Rack Installation (Only available for Rack UPS) ................................................... 5
2-3. Setup the UPS ......................................................................................................... 6
2-4 Battery replacement (Only for Rack UPS) ................................................................... 8
2-5 Battery kit assembly (Option for Rack UPS) ................................................................ 9
3. Operations ................................................................................................................... 11
3-1. Button operation.................................................................................................... 11
3-2. LCD Panel ............................................................................................................. 11
3-3. Audible Alarm........................................................................................................ 13
3-4. LCD display wordings index .................................................................................... 13
3-5. UPS Setting ........................................................................................................... 13
3-6. Operating Mode Description ................................................................................... 16
3-7. Faults Reference Code............................................................................................ 17
3-8. Warning indicator .................................................................................................. 18
4. Troubleshooting............................................................................................................ 19
5. Storage and Maintenance.............................................................................................. 20
6. Specifications ............................................................................................................... 21

1
1. Important Safety Warning
Please comply with all warnings and operating instructions in this manual strictly. Save this
manual properly and read carefully the following instructions before installing the unit. Do not
operate this unit before reading through all safety information and operating instructions
carefully
1-1. Transportation
Please transport the UPS system only in the original package to protect against shock
and impact.
1-2. Preparation
Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed. Please
allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or near
heater.
Do not block ventilation holes in the UPS housing.
1-3. Installation
Do not connect appliances or devices which would overload the UPS system (e.g. laser
printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them.
Do not connect domestic appliances such as hair dryers to UPS output sockets.
The UPS can be operated by any individuals with no previous experience.
Connect the UPS system only to an earthed shockproof outlet which must be easily
accessible and close to the UPS system.
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS
system.
When installing the equipment, it should ensure that the sum of the leakage current of
the UPS and the connected devices does not exceed 3.5mA.
1-4. Operation
Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective
earthing of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output
sockets or output terminals block may be electrically live even if the UPS system is not
connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
Prevent no fluids or other foreign objects from inside of the UPS system.

2
1-5. Maintenance, service and faults
The UPS system operates with hazardous voltages. Repairs may be carried out only by
qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains
(building wiring outlet), components inside the UPS system are still connected to the
battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries
and verify that no current is present and no hazardous voltage exists in the terminals of
high capability capacitor such as BUS-capacitors.
Only persons are adequately familiar with batteries and with the required precautionary
measures may replace batteries and supervise operations. Unauthorized persons must
be kept well away from the batteries.
Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the ground.
Before touching, please verify that no voltage is present!
Batteries may cause electric shock and have a high short-circuit current. Please take
the precautionary measures specified below and any other measures necessary when
working with batteries:
-remove wristwatches, rings and other metal objects
-use only tools with insulated grips and handles.
When changing batteries, install the same number and same type of batteries.
Do not attempt to dispose of batteries by burning them. This could cause battery
explosion.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and
eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire
hazards.
Do not dismantle the UPS system.

3
2. Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is
damaged. Please keep the original package in a safe place for future use.
2-1. Rear panel view
GO-1000 GO-1000L
IEC Type NEMA Type IEC Type
GO-2000 GO-2000L
IEC Type NEMA Type IEC Type
GO-3000 GO-3000L
IEC Type NEMA Type IEC Type

4
ERTN-1000
IEC Type For 110/120V
For 220/230/240V
ERTN-1000L
ERTN-2000
IEC Type For 110/120V
For 220/230/240V
ERTN-2000L
IEC Type

5
ERTN-3000
IEC Type For 110/120V
For 220/230/240V
ERTN-3000L
IEC Type
1. AC input
2. Input circuit breaker
3. USB communication port
4. RS-232 communication port
5. SNMP intelligent slot (option)
6. External battery connection (only available for long-run model)
7. Output receptacles
8. Output circuit breaker
9. Output terminal
2-2. UPS Rack Installation (Only available for Rack UPS)
This UPS can be mounted in the 19” rack chassis. Please follow below steps to position this UPS.
Step 1 Step 2

6
2-3. Setup the UPS
Step 1: External battery connection (Only for long-run
model)
This UPS is not including batteries. Please connect external
batteries as chart.
Step 2: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle
only. Avoid using extension cords.
For 200/208/220/230/240VAC models:
The power cord is
supplied in the UPS package.
For 100/110/115/120/127VAC models: The power cord is
attached to the UPS. The input plug is a NEMA 5-15P for 1K model and NEMA 5-20P for 2K
model.
Step 3: UPS output connection
For socket-type outputs, simply connect devices to the outlets.
For terminal-type input or outputs, please follow below steps for the wiring configuration:
a) Remove the small cover of the terminal block
b) Suggest using AWG14 or 2.1mm2power cords for 3KVA (200/208/220/230/240VAC
models). Suggest using AWG12-10 or 3.3mm2-5.3mm2power cords for 3KVA
(100/110/115/120/127VAC models). Please also install a circuit breaker (40A) between
the mains and AC input of UPS in 3KVA (100/110/115/120127VAC models) for safety
operation.
c) Upon completion of the wiring configuration, please check whether the wires are
securely affixed.
d) Put the small cover back to the rear panel.
Step 4: Communication connection
Communication port:
USB port RS-232 port Intelligent slot
To allow for unattended UPS shutdown/start-up and status monitoring, connect the
communication cable one end to the USB/RS-232 port and the other to the communication port
of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and
monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing
either SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring
options.
PS. USB port and RS-232 port can’t work at the same time.
Step 5: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not expect
full battery run capability during this initial charge period.

7
Step 6: Install software
For optimal computer system protection, install UPS monitoring software to fully configure UPS
shutdown. You may insert provided CD into CD-ROM to install the monitoring software. If not,
please follow steps below to download and install monitoring software from the internet:
1. Go to the website http://www.power-software-download.com
2. Click ViewPower software icon and then choose your required OS to download the software.
3. Follow the on-screen instructions to install the software.
4. When your computer restarts, the monitoring software will appear as an orange plug icon
located in the system tray, near the clock.

8
2-4 Battery replacement (Only for Rack UPS)
NOTICE: This rack UPS is equipped with internal batteries and user can replace the batteries
without shutting down the UPS or connected loads (hot-swappable battery design).
Replacement is a safe procedure, isolated from electrical hazards.
CAUTION!! Consider all warnings, cautions, and notes before replacing batteries.
Note: Upon battery disconnection, equipment is not protected from power outages.
Step 1
Step 2
Step 3
Remove front panel.
Disconnect battery wires.
Pull out the battery box by
removing two screws on the
front panel.
Step 4
Step 5
Step 6
Remove the top cover of battery
box and replace the inside
batteries.
After replacing the batteries,
put the battery box back to
original location and screw it
tightly.
Re-connect the battery wires.
Step 7
Put the front panel back to the unit.

9
2-5 Battery kit assembly (Option for Rack UPS)
NOTICE: Please assemble battery kit first before installing it inside of UPS. Please select correct
battery kit procedure below to assemble it.
2-battery kit
Step 1: Remove adhesive tapes.
Step 2: Connect all battery terminals by
following below chart.
Step 3: Put assembled battery packs on
one side of plastic shells.
Step 4: Cover the other side of plastic shell as
below chart. Then, battery kit is assembly well.
3-battery kit
Step 1: Remove adhesive tapes.
Step 2: Connect all battery terminals by
following below chart.
Step 3: Put assembled battery packs on
one side of plastic shells and insert one
more dummy battery on the space.
Step 4: Cover the other side of plastic shell as
below chart. Then, battery kit is assembly well.
Tapes
Tapes
Tapes
Dummy
battery

10
4-battery kit
Step 1: Remove adhesive tapes.
Step 2: Connect all battery terminals by
following below chart.
Step 3: Put assembled battery packs on
one side of plastic shells.
Step 4: Cover the other side of plastic shell as
below chart. Then, battery kit is assembly well.
6-battery kit
Step 1: Remove adhesive tapes.
Step 2: Connect all battery terminals by
following below chart.
Step 3: Put assembled battery packs on
one side of plastic shells.
Step 4: Cover the other side of plastic shell as
below chart. Then, battery kit is assembly well.
Tapes
Tapes
Tapes
Tapes

11
3. Operations
3-1. Button operation
Button
Function
ON/Mute Button
Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds
to turn on the UPS.
Mute the alarm: When the UPS is on battery mode, press and hold this
button for at least 5 seconds to disable or enable the alarm system. But
it’s not applied to the situations when warnings or errors occur.
Up key: Press this button to display previous selection in UPS setting
mode.
Switch to UPS self-test mode: Press and hold ON/Mute button for 5
seconds to enter UPS self-testing while in AC mode, ECO mode, or
converter mode.
OFF/Enter Button
Turn off the UPS: Press and hold this button at least 2 seconds to turn
off the UPS. UPS will be in standby mode under power normal or
transfer to Bypass mode if the Bypass enable setting by pressing this
button.
Confirm selection key: Press this button to confirm selection in UPS
setting mode.
Select Button
Switch LCD message: Press this button to change the LCD message for
output voltage, output frequency, input voltage, input frequency,
battery voltage, load percent, load VA, load W and load current,
ambient temperature. It will return back to default display when
pausing for 60 seconds.
Setting mode: Press and hold this button for 5 seconds to enter UPS
setting mode when UPS is in standby mode or bypass mode.
Down key: Press this button to display next selection in UPS setting
mode.
ON/Mute + Select
Button
Switch to bypass mode: When the main power is normal, press
ON/Mute and Select buttons simultaneously for 5 seconds. Then UPS
will enter to bypass mode. This action will be ineffective when the
input voltage is out of acceptable range.
3-2. LCD Panel

12
Display
Function
Remaining backup time and running time information
Indicates the remaining backup time.
Indicates the running time.
Indicates the remaining backup /running time in numbers.
H: hour, M: minute, S: Second
Warning and Fault information
Indicates that the warning occurs.
Indicates that the fault occurs.
Indicates the warning and fault codes.
Setting operation
Indicates that the setting occurs.
Mute operation
Indicates that the UPS alarm is disabled.
Select information
Select displayed information such as output voltage (Default), output
frequency, input voltage, input frequency, battery voltage, load
percent, load in VA, load in watts, load current and ambient
temperature.
K: kilo, W: Watt, V: Volt, A: Amp, VA: Volt*Amp, %: percent, ℃: Degree, Hz: Hertz
Mode operation information
Indicates the UPS works in line mode.
Indicates the UPS works in battery mode.
Indicates the UPS works in converter mode.
Indicates the UPS works in bypass mode.
Indicates the UPS works in ECO mode.
Load information
Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates overload.
Indicates that outlets have output voltage.
Indicates the load or the UPS output is short circuit.
Battery information
Indicates the Battery level by 0-25%, 26-50%, 51-75%, and
76-100%.
Indicates the charger is working.
Indicates battery.
Indicates the battery is needed to replace.
Indicates low battery voltage.

13
3-3. Audible Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
Bypass Mode
Sounding every 10 seconds
3-4. LCD display wordings index
Abbreviation
Display content
Meaning
ENA
Enable
DIS
Disable
ESC
Escape
LLS
Low loss
HLS
High loss
TP
Temperature
CH
Charger
BF
Battery fault
FU
Bypass frequency unstable
EE
EEPROM error
3-5. UPS Setting
There are two parameters to set up the UPS.
Parameter 1: It’s for program alternatives.
Parameter 2: It’s the setting options or values
for each program.
01: Output voltage setting
Interface
Setting
For 200/208/220/230/240 VAC models, you may choose
the following output voltage:
200: presents output voltage is 200Vac
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac(Default)
240: presents output voltage is 240Vac
For 100/110/115/120/127 VAC models, you may choose
the following output voltage:
100: presents output voltage is 100Vac
110: presents output voltage is 110Vac
115: presents output voltage is 115Vac
120: presents output voltage is 120Vac(Default)
127: presents output voltage is 127Vac
Parameter 2
Parameter 1

14
02: Converter mode enable/disable
Interface
Setting
ENA: converter mode enable
DIS: converter mode disable (Default)
03: Output frequency setting
Interface
Setting
You may choose the following output frequency:
50: presents output frequency is 50Hz
60: presents output frequency is 60Hz
04: Acceptable low voltage setting in Bypass mode
Interface
Setting
Press the Down key or Up key to set the acceptable bypass
low voltage point(LLS):
For 200/208/220/230/240 VAC models:
170-220: setting the low voltage point from 170Vac to
220Vac (Default: 170Vac)
For 100/110/115/120/127 VAC models:
85-115: setting the low voltage point from 85Vac to
115Vac (Default: 85Vac)
05: Acceptable high voltage setting in Bypass mode
Interface
Setting
Press the “Down” key or “Up” key to set the acceptable
high voltage point (HLS) in bypass mode:
For 200/208/220/230/240 VAC models:
230-264: Setting high voltage point from 230Vac to 264Vac
(Default: 264Vac)
For 100/110/115/120/127 VAC models:
120-140: Setting high voltage point from 120Vac to 140Vac
(Default: 132Vac)
06: Acceptable low frequency setting in Bypass/ECO mode
Interface
Setting
Press the “Down” key or “Up” key to set the acceptable low
frequency point (LLS) in bypass/ECO mode:
For 50Hz output frequency models:
45-49Hz: Setting low frequency point from 45Hz to 49HZ
(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz: Setting low frequency low point from 55Hz to

15
59Hz(Default: 57.0Hz)
07: Acceptable high frequency setting in Bypass/ECO mode
Interface
Setting
Press the “Down” key or “Up” key to set acceptable high
frequency point (HLS) in bypass/ECO mode:
For 50Hz output frequency models:
51-55Hz: Setting the frequency low loss point from 51Hz to
55HZ(Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz: Setting the frequency low loss point from 61Hz to
65Hz(Default: 63.0Hz)
08: ECO mode enable/disable
Interface
Setting
ENA: ECO mode enable
DIS: ECO mode disable (Default)
09: Acceptable low voltage setting in ECO mode
Interface
Setting
Press the “Down” key or “Up” key to set acceptable low
voltage point (LLS) in ECO mode:
For 200/208/220/230/240 VAC models, the setting range
is from -7V to -24V of the nominal voltage. (Default:
-12V)
For 100/110/115/120/127 VAC models, the setting range
is from -3V to -12V of the nominal voltage. (Default: -6V)
10: Acceptable high voltage setting in ECO mode
Interface
Setting
Press the “Down” key or “Up” key to set acceptable high
voltage point (HLS) in ECO mode:
For 200/208/220/230/240 VAC models, the setting range is
from +7V to +24V of the nominal voltage. (Default: +12V)
For 100/110/115/120/127 VAC models, the setting range is
from +3V to +12V of the nominal voltage. (Default: +6V)

16
11: Bypass enable/disable when UPS is off
Interface
Setting
ENA: Bypass mode is enabled when UPS is off
DIS: Bypass mode is disabled when UPS is off (Default)
12: Autonomy limitation setting
Interface
Setting
1-999: setting the backup time in minutes from 1-999 for
output outlets on battery mode.
DIS: The backup time setting will be disabled. (Default)
00: Exit setting
3-6. Operating Mode Description
Operating mode
Description
LCD display
Standby mode
UPS is powered off and no output supply
power, but still can charge batteries.
Online mode
When the input voltage is within
acceptable range, UPS will provide pure
and stable AC power to output. The UPS
will also charge the battery at online
mode.
ECO mode
Energy saving mode:
When the input voltage is within voltage
regulation range, UPS will bypass
voltage to output for energy saving.
Converter mode
When input frequency is within 40 Hz to
70 Hz, the UPS can be set at a constant
output frequency, 50 Hz or 60 Hz. The
UPS will still charge battery under this
mode.

17
Battery mode
When the input voltage is beyond the
acceptable range or power failure and
alarm is sounding every 4 second, UPS
will backup power from battery.
Battery test
mode
UPS will turn off charger and check if
battery and DC/DC are normal.
Bypass mode
When input voltage is within acceptable
range but UPS is overload, UPS will enter
bypass mode or bypass mode can be set
by front panel. Alarm is sounding every
10 second.
Fault mode
When a fault has occurred, the ERROR
icon and the fault code will be displayed.
3-7. Faults Reference Code
Fault event
Fault code
Icon
Fault event
Fault code
Icon
Bus start fails
01
x
Inverter output
short-circuited
14
Bus over
02
x
Battery voltage is too high
27
x
Bus under
03
x
Battery voltage is too low
28
x
Bus unbalance
04
x
Over temperature
41
x
Inverter soft start fails
11
x
Over load
43
Inverter voltage is high
12
x
Charger fault
45
x
Inverter voltage is low
13
x

18
3-8. Warning indicator
Warning
Icon (flashing)
Alarm
Low Battery
Sounding every second
Overload
Sounding twice every second
Battery is not connected or
Battery Replace
Sounding every second
Over Charge
Sounding every second
Over temperature
Sounding every second
Charger failure
Sounding every second
Battery fault
Sounding every second
Out of bypass voltage range
Sounding every second
Bypass frequency unstable
Sounding every second
EEPROM error
Sounding every second
This manual suits for next models
5
Table of contents
Other Powerbank UPS manuals