PTX2-A3 Service Manual Rev.2
Page 3 of total 19 August 2007
3. Troubleshooting
3.1 Quick Start
Before any check of UPS, please check the components as listed in the following table. This action could help you find
problem quickly and make sure these components good or not first.
Possible Circuit Block Coded Components Description Failure Mode
BAT FUSE F303/F304 Fuse Open
I/P FUSE (on PSDR) F301/F302 Fuse Open
PFC Correction Q301, Q302 MOSFET A-K Short or open
Q306, Q307,Q308, Q309,
Q310, Q311
IGBT D-S short or open
D302, D304, D306, D303,
D305, D307
Push-Pull Boost
D309, D311, D308, D310
Power Diode Short or open
Q201, Q202, Q203, Q204 IGBT C-E short or open
D201, D202, D203, D204,
D205
Inverter
D210, D211, D212, D213
Power Diode Short or open
Charger module(standard) Q907, Q908 IGBT D-S short or open
D901,D902,D903 Power Diode Short or open
Q909 MOSFET A-K Short or open
IP SCR module Q3, Q4, Q5, Q6 MOSFET A-K short or open
For the 6 and 10kVA, both of the boards are the same size, only the some power components of
10kVA should be more than 6kVA.
If the fuse is open, replacing fuse only, DO NOT mean you have solved the problem. General
speaking, fuse open was caused by other failure of components; therefore, you must find the
real defective components and replace them, before restart the UPS.