FUNCTION
The reverse power relay measures the phase voltage (L –N operation) and the current of that
phase through the current transducer. It calculates I Cos ө representing the active power. If the
active power becomes negative and exceeds the preset level (4 –20 %) the pickup, RED LED
will blink and the delay timer will start. After the preset time (0 –20 sec) the relay will trip and
the RED LED will glow. The reverse power (-I * Cos ө) is displayed on the LCD. During the
healthy condition the GREEN LED glows,
SETTING PROCEDURE
Connect the auxiliary supply, sensing voltage and current to the reverse power relay.
The display shows
After few seconds, the display shows the sensing voltage, current, frequency and power factor
(only if both voltage & load current above 100ma available at the sensing input).
To enter the setting mode, press the mode/set key . At first display comes for setting
of reverse current. The display shows
Range is from 4% to 20% at steps of 1%
Press the increment and decrement key to make the desired setting.
Press the set key to store the value. The display changes as shown
Range is from 0 sec to 20 sec at steps of 0.1 sec