protech 84-HRV100 User guide

04188-15/09/03
Installer Manual
HRV / ERV
Ventilation Systems
PROTECH™ MODELS
84-HRV100
84-HRV200
84-ERV100
84-ERV200
VB0038

2
Table of Contents
1.0 SERVICE..............................................................................................................4
1.1 3-D Drawing................................................................................................4
1.2 Parts Ordering Chart....................................................................................5
2.0 SIZING ................................................................................................................6
3.0 UNIT TYPE & DEFROST SETTING VS GEOGRAPHICAL LOCATION ........................7
4.0 TECHNICAL DATA ................................................................................................8
4.1 Air Distribution (Normal Operation) ............................................................8
4.2 Air Distribution (Defrost Mode) ..................................................................8
4.3 Performance Charts ..............................................................................9-10
4.4 Dimensions................................................................................................11
4.5 Controls and Furnace Link Option ............................................................11
4.6 Specifications............................................................................................11
5.0 TYPICAL INSTALLATIONS....................................................................................12
5.1 Fully Ducted System..................................................................................12
5.2 Exhaust Ducted System
(Source Point Ventilation)
..................................12
5.3 Simplified
(Volume Ventilation)
................................................................13
6.0 INSTALLATION....................................................................................................13
6.1 Adjusting the Damper Rod (For ERVs Installed in Warm Regions)......................13
6.2 Locating and Mounting the Unit................................................................14
6.3 Planning of the Ductwork..........................................................................14
6.4 Calculating the Duct Size......................................................................14-15
6.4.1 Example Calculation........................................................................15
6.4.2 Example of a Design for a Fully Ducted System..............................15
6.5 Installing the Ductwork and Registers ......................................................16
6.5.1 Fully Ducted System........................................................................16
6.5.2 Exhaust Ducted System (Source Point Ventilation) ........................16
6.5.3 Simplified Installation (Volume Ventilation) ....................................17
6.6 Connecting Duct to the Unit......................................................................18
6.7 Installing the Exterior Hoods ....................................................................19
6.8 Connecting the Drain ................................................................................19
7.0 CONTROL DEVICES............................................................................................20
7.1 Main Controls............................................................................................20
7.2 Optional Control ........................................................................................21
7.3 Other Features ..........................................................................................21
7.4 Special Cold Weather TBI Mode for ERVs ................................................21

3
Table of Contents (cont’d)
About this Manual
8.0 INSTALLATION OF THE CONTROLS......................................................................22
8.1 Dimensions and Specifications................................................................22
8.2 Installation of the Main Control..........................................................22-23
8.3 Electrical Connection to Optional Controls..............................................24
8.4 Electrical Connection to the Furnace ......................................................24
9.0 WIRING DIAGRAM ............................................................................................25
10.0 AIR FLOW BALANCING ................................................................................26-27
11.0 OVERALL VERIFICATION ....................................................................................28
11.1 Main Controls..........................................................................................28
11.2 Optional Control ......................................................................................28
12.0 MAINTENANCE / INSTRUCTIONS FOR USER........................................................29
13.0 TROUBLESHOOTING......................................................................................30-31
14.0 REFERENCES ....................................................................................................32
This manual uses the following symbols to emphasize particular information:
NOTE: Indicates supplementary information needed to fully complete an instruction.
WARNING
Identifies an instruction which, if not followed, might cause serious personal injuries
including possibility of death.
CAUTION
Denotes an instruction which, if not followed, may severely damage the unit and/or
its components.
!

4
1.1 3-D DRAWING
1.0 Service
6
1
2
3
4
5
7
8
910
11
12
13
14
15
16
17
18
19
20
21
22 3
23
23 24
25
26
VL0016
DAMPER ASSEMBLY (REAR VIEW)

5
1.2 PARTS ORDERING CHART
1.0 Service (cont’d)
TO ORDER PARTS: Contact your local distributor.
No Description HRV100 HRV200 ERV100 ERV200
1 Double Collar Port #2 00866 00866 00866 00866
2 Wing Nut #10-32 00874 00874 00874 00874
3 Balancing Double Collar Port 02256 02256 02256 02256
4 Inlet Ring 12913 12913 12913 12913
5 Top Wheel 14307 03093 03093 03093
6 Electronic Board V99 13507 13507 13507 13507
7 Motor Assembly 13504 13556 13555 13506
8 Bottom Wheel 02015 03093 02015 03093
9 Square Damper 12645 12645 12645 12645
10 Door Latches 00886 00886 00886 00886
11 Drain Connector 02418 02418 02418 02418
12 Drain Washer 0.625 Dia. 02419 02419 02419 02419
13 Washer 5/8’’ ID x 1’’ OD 03117 03117 03117 03117
14 Nut 5/8-18 02420 02420 02420 02420
15 Recovery Core 03134 03135 03136 03137
16 Door Ass’y 13772 13772 13772 13772
17 Door Keeper 00887 00887 00887 00887
18 Hinge Ass’y (kit) 00672 00672 00672 00672
19 Filter 03096 03097 03096 03097
20 Door Switch (SPST), E69 10A 01825 01825 01825 01825
21 Damper #2 12643 12643 12643 12643
22 Balancing Damper 02253 02253 02253 02253
23 Damper Rod 12620 12620 12620 12620
24 Port #5 02021 02021 02021 02021
25 Damper #1 12459 12459 12459 12459
26 Actuator Ass’y 03124 03124 03124 03124
Please take note that parts not listed are not available; those parts require assembly knowledge that only
manufacturer can guarantee.

These are the two most common methods used to evaluate the ventilation needs of a house:
CSA F326 and Canadian Building Code:
• High speed:10 cfm per room
20 cfm for the master bedroom and the basement
• Low speed: 40-60% of high speed
ASHRAE Standard 62-2001:
• 0.35 air change per hour
Refer to ventilation code of your area to determine which method to use.
Example:
6
Master
Bedroom
Bedroom #1
Kitchen
Basement
Bedroom
#2
Bedroom
#3
Living room
Bathroom
#3
Dining room
VH0021A
Family room
Bathroom
#1
Bathroom
#2
Laundry
room
1320 ft2
1320 ft2
Method 1
CSA F326
Kitchen (10 cfm)
Dining room (10 cfm)
Living room (10 cfm)
Family room (10 cfm)
Master bedroom (20 cfm)
Bedroom #1 (10 cfm)
Bedroom #2 (10 cfm)
Bedroom #3 (10 cfm)
Bathroom #1 (10 cfm)
Bathroom #2 (10 cfm)
Bathroom #3 (10 cfm)
Laundry room (10 cfm)
Basement (20 cfm)
Total 150
cfm
Method 2
ASHRAE Standard 62-2001
Volume of basement 10560 ft3
Volume of main floor 10560 ft3
Volume of second floor 10560 ft3
Total volume 31680 ft3
x .35/h
11090 ft3/h
÷ 60 (min/h)
Total 185 cfm (high speed)
1320 ft2
Second floor Main floor
Basement
2.0 Sizing

7
3.0
Unit Type & Defrost Setting vs Geographical Location
ANCHORAGE
WHITEHORSE
JUNEAU
HAY RIVER
YELLOWKNIFE
Prince Rupert GRANDE PRAIRIE
FORT MCMURRAY
ZONE A
FORT SMITH
EDMONTON
PRINCE ALBERT
SASKATOON
JASPER
KAMLOOPS
CALGARY
PENTICTON REGINA
LETHBRIDGE
HELENA
VICTORIA
OLYMPIA
WINNIPEG
SALEM
BOISE
BISMARCK
SALT LAKE CITY
SAULT STE MARIE
ST. PAUL
DES MOINES
MADISON
TIMMINS
HARRISBURG
SACRAMENTO
DENVER
TOPEKA
SUDBURY
TORONTO
DETROIT
INDIANAPOLIS
SANTA FE
SPRINGFIELD
OKLAHOMA CITY
PHOENIX
COLUMBUS
NASHVILLE
ATLANTA
BATON ROUGE
AUSTIN
COLUMBIA
RALEIGH
WASHINGTON
OTTAWA
NORTH BAY
VAL-DOR
CHICOUTIMI
HARTFORD
CHIBOUGAMAU
MONTRÉAL
QUEBEC
BOSTON
GOOSE BAY
LABRADOR CITY
SEPT-ILES
MATANE
GASPÉ
BATHURST
ST-JOHN HALIFAX
CHARLOTTETOWN
ST JOHN'S
ZONE B
ZONE C
RENO
VN0003
ZONE A (HRVs only) ZONE C (ERVsrecommended)
- Set Extended Defrost according to section 8.2, point 10 - ERV’s: Set Defrost mode #1
- MODELS: HRV100, HRV200 according to Section 6.1
- ERVMODELS:ERV100,ERV200
ZONE B (HRV or ERV according to your client’s particular problems)
See ZONE B SELECTION CHART beside
HRV MODELS: HRV100, HRV200
ERV MODELS: ERV100, ERV200
SYMPTON SOLUTION
(condensation)
Indoor air quality problem ERV
and/or
Excess moisture problem ERV
and/or
Important excess moisture problem HRV
ZONE B SELECTION CHART

VF0020
VF0013
8
4.1 A
IR
D
ISTRIBUTION
(N
ORMAL
O
PERATION
)
4.2 A
IR
D
ISTRIBUTION
(D
EFROST
M
ODE
)
4.0 Technical Data
FRESH AIR
TO BUILDING
For defrost cycles table, refer to Section 9.0, Wiring Diagram.
Applicable to all model numbers
FRESH AIR
TO BUILDING STALE AIR
FROM BUILDING
STALE AIR
TO OUTSIDE
FRESH AIR
FROM OUTSIDE
Defrost Mode 1
Applicable to model numbers:
- 84-HRV100
- 84-HRV200
STALE AIR
FROM BUILDING
VF0012
FRESH AIR
TO BUILDING
STALE AIR
TO OUTSIDE
Defrost Mode 2
Applicable to model numbers:
- 84-ERV100
- 84-ERV200
STALE AIR
FROM BUILDING

9
MODEL NUMBER: 84-HRV100
Electrical requirements: 120 volts, 1.3 amps.
Exhaust air transfer ratio: 0.05
4.3 P
ERFORMANCE
C
HARTS
4.0 Technical Data (cont’d)
External Static Pressure - Pascals
(250 Pascals = 1” of water)
Gross Air Flow -L/s (0.47L/s = 1cfm)
225
175
200
150
125
100
75
50
25
005025 100 12575 150
VG0039
External Static Pressure - Pascals
(250 Pascals = 1” of water)
225
175
200
150
125
100
75
50
25
005025 100 12575 150
VG0040
MODEL NUMBER: 84-HRV200
Electrical requirements: 120 volts, 1.9 amps.
Exhaust air transfer ratio: 0.042
ENERGY PERFORMANCE
Supply Net Average Sensible Recovery Apparent Sensible Latent Recovery
Temperature Air Flow Power Efficiency Effectiveness Moisture Transfer
°C °F L/s cfm watts % %
0 32 30 64 54 75 83 -0.03
0 32 46 97 78 67 74 -0.01
0 32 65 138 124 64 72 -0.02
-25 -13 26 55 62 67 89 0.05
Total Recovery Efficiency
35 95 Not tested
COOLING
HEATING
VENTILATION PERFORMANCE
External Static Net Supply Gross Air Flow
Pressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
25 0.1 84 177 88 186 90 190
50 0.2 80 169 84 178 86 182
75 0.3 77 163 81 171 81 171
100 0.4 69 146 72 153 76 161
125 0.5 61 130 65 137 66 139
150 0.6 46 98 49 103 52 110
175 0.7 38 81 40 85 31 67
NOTE: Unit operating at maximum speed.
VENTILATION PERFORMANCE
External Static Net Supply Gross Air Flow
Pressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
50 0.2 120 253 124 264 126 268
75 0.3 118 250 123 262 119 251
100 0.4 111 235 116 245 114 241
125 0.5 102 216 106 224 107 226
150 0.6 87 185 91 193 96 204
175 0.7 75 160 78 167 81 172
200 0.8 57 120 59 124 57 121
NOTE: Unit operating at maximum speed.
ENERGY PERFORMANCE
Supply Net Average Sensible Recovery Apparent Sensible Latent Recovery
Temperature Air Flow Power Efficiency Effectiveness Moisture Transfer
°C °F L/s cfm watts % %
0 32 51 109 92 70 77 -0.01
0 32 73 155 128 65 72 -0.02
0 32 102 215 191 62 70 -0.01
-25 -13 52 110 104 60 94 0.05
Total Recovery Efficiency
35 95 Not tested
COOLING
HEATING
Supply
(l/s)
Exhaust
(l/s)
Supply
(l/s)
Exhaust
(l/s)
Gross Air Flow -L/s (0.47L/s = 1cfm)

10
4.3 P
ERFORMANCE
C
HARTS
(
CONT
’
D
)
4.0 Technical Data (cont’d)
External Static Pressure - Pascals
(250 Pascals = 1” of water)
225
175
200
150
125
100
75
50
25
005025 100 12575 150
VG0041
External Static Pressure - Pascals
(250 Pascals = 1” of water)
225
175
200
150
125
100
75
50
25
005025 100 12575 150
VG0042
MODEL NUMBER: 84-ERV100
Electrical requirements: 120 volts, 1.3 amps.
Exhaust air transfer ratio: 0.06
MODEL NUMBER: 84-ERV200
Electrical requirements: 120 volts, 1.9 amps.
Exhaust air transfer ratio: 0.06
VENTILATION PERFORMANCE
External Static Net Supply Gross Air Flow
Pressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
25 0.1 81 173 87 184 93 197
50 0.2 78 165 83 175 86 182
75 0.3 72 152 76 162 80 169
100 0.4 67 142 71 151 77 163
125 0.5 55 117 59 124 67 143
150 0.6 46 98 49 104 56 118
175 0.7 36 77 39 82 41 87
200 0.8 30 63 32 67 24 51
NOTE: Unit operating at maximum speed.
ENERGY PERFORMANCE
Supply Net Average Sensible Recovery Apparent Sensible Latent Recovery
Temperature Air Flow Power Efficiency Effectiveness Moisture Transfer
°C °F L/s cfm watts % %
0 32 29 60 56 71 79 0.52
0 32 47 100 80 64 73 0.41
0 32 65 137 126 60 68 0.36
-15 5 31 65 64 56 81 0.41
Total Recovery Efficiency
35 95 28 59 52 45
COOLING
HEATING
VENTILATION PERFORMANCE
External Static Net Supply Gross Air Flow
Pressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
25 0.1 109 231 116 245 128 271
50 0.2 107 228 114 241 123 260
75 0.3 101 214 107 227 118 249
100 0.4 95 201 101 213 110 233
125 0.5 86 182 91 193 103 217
150 0.6 79 167 83 177 92 195
175 0.7 62 132 66 140 81 172
200 0.8 40 85 43 90 55 116
NOTE: Unit operating at maximum speed.
ENERGY PERFORMANCE
Supply Net Average Sensible Recovery Apparent Sensible Latent Recovery
Temperature Air Flow Power Efficiency Effectiveness Moisture Transfer
°C °F L/s cfm watts % %
0 32 52 110 93 69 76 0.45
0 32 74 157 130 64 71 0.38
0 32 96 203 193 60 68 0.30
-15 5 52 110 122 55 76 0.26
Total Recovery Efficiency
35 95 50 106 89 41
COOLING
HEATING
Gross Air Flow -L/s (0.47L/s = 1cfm)
Supply
(l/s)
Exhaust
(l/s)
Supply
(l/s)
Exhaust
(l/s)
Gross Air Flow -L/s (0.47L/s = 1cfm)

11
4.4 D
IMENSIONS
4.0 Technical Data (cont’d)
13-3/4"
(
349mm
)
20" (508mm)
50
0
"
(
6"
(
152mm
)
2.5"
(
63mm
)
30-1/4"
(
768mm
)
VK
00
4
0
Model numbers:
- 84-HRV100
- 84-ERV100
19"
(
483mm
)
20" (508mm)
8m
5
0
6"
(
152mm
)
30-1/4"
(
768mm
)
2.5"
(
63mm
)
VK
0039
Model numbers:
- 84-HRV200
- 84-ERV200
Main controls:
• Economy
• Value
Optional controls:
• 20/40/60-minute push-button Link option (standard):
• Furnace interlock
(use with forced air systems)
4.5 C
ONTROLS AND
F
URNACE
L
INK
O
PTION
4.6 S
PECIFICATIONS
Model 84-
Weight
Port Diameter
Drain Diameter
HRV/ERV 100
65 lbs (30 kg)
6” (152 mm)
1/2” (12 mm)
HRV/ERV 200
73 lbs (33 kg)
6” (152 mm)
1/2” (12 mm)
Installation Chains, springs and hooks (provided with the unit).
Motor Speed High and low speeds factory set (optional increased low speed - BLUE wire).
Electrical supply 120 V, 60 Hz 120 V, 60 Hz
Power Consumption 150 Watts 225 Watts

12
5.0 Typical Installations
(Primarily for homes with radiant hot water or
electric baseboard heating. See figure 1.)
Moist, stale air is exhausted from the high
humidity areas in the home, such as
bathrooms, kitchen and laundry room.
Fresh air is supplied to bedrooms and
principal living areas.
The use of bathroom fans and a range hood
is suggested to better exhaust stale air.
Homes with more than one level require at
least one exhaust register at the highest
level.
5.1 F
ULLY
D
UCTED
S
YSTEM
There are three (3) common installation methods.
VH
00
24
figure 1
See 6.5.1
for details
5.2 E
XHAUST
D
UCTED
S
YSTEM
(S
OURCE
P
OINT
V
ENTILATION
)
(For homes with forced air heating.
See figure 2.)
Moist, stale air is exhausted from the high
humidity areas in the home, such as
bathrooms, kitchen and laundry room.
Fresh air is supplied to the cold air return or
the supply duct of the furnace.
The use of bathroom fans and a range hood
is suggested to better exhaust stale air.
Homes with more than one level require at
least one exhaust register at the highest
level.
NOTE: For this type of installation, it is not
essential that the furnace blower
runs when the unit is in operation,
but we recommend it.
VH
00
2
5
See 6.5.2
for details
figure 2

13
5.0 Typical Installations (cont’d)
5.3 S
IMPLIFIED
(V
OLUME
V
ENTILATION
)
(For homes with forced air heating. See figure 3 or 4.)
Fresh air and exhaust air flow through the furnace ducts wich simplifies the installation.
The use of bathroom fans and a range hood is suggested to better exhaust stale air.
NOTE: For the installation type shown in figure 4, furnace blower must be running when the unit is in operation.
VH
00
2
7
figure 3
OR
VH
00
2
6
figure 4
See 6.5.3
for details
6.0 Installation
See 6.5.3
for details
I
NSPECT THE
C
ONTENTS OF THE
B
OX
• Inspect the exterior of the unit for shipping damage. Ensure that there is no damage to the door, door
latches, door hinges, dampers, duct collars, cabinet, etc.
• Inspect the interior of the unit for damage. Ensure that the fan motor assembly, recovery core,
insulation, dampers, damper actuator and drain pan are all intact.
• If the unit was damaged during shipping, contact your local distributor. (Claim must be made within
24 hours after delivery.)
• Use checklist included with the unit to ensure that no parts are missing.
6.1 A
DJUSTING THE
D
AMPER
R
OD
(F
OR
ERV
S
I
NSTALLED IN
W
ARM
R
EGIONS
)
Refer to Section 4.2 and observe the difference in the damper position
at the right in diagrams Defrost Mode 1 and Defrost Mode 2:
for Defrost Mode 1 the damper is completely closed, whereas for
Defrost Mode 2 the damper is half closed. At the factory, all ERVs are
assembled for defrost Mode 2. Therefore, if your installation is for an
ERV in a warm region (zone D as defined in Section 3), the rod must
be moved to position 1 (see figure 5).
NOTE: Before attempting to change the position of the damper rod,place
the unit on a table for easy access and remove the recovery core.
V
O00
1
5
O00 5
1
2
figure 5
CAUTION
This is a delicate operation: to avoid injury proceed carefully and use the appropriate tools.

14
6.0 Installation (cont’d)
6.2 L
OCATING AND
M
OUNTING THE
U
NIT
Choose an appropriate location for the unit:
• Within an area of the house where the temperature is above 10°C /
50°F (basement, attic, furnace room, laundry room, etc.).
• Away from living areas (dining room, living room, bedroom), if possible.
• So as to provide easy access to the interior cabinet and to the
control panel on the right hand side of the unit.
• Close to an exterior wall, so as to limit the length of the insulated
flexible duct to and from the unit.
• Close to a drain. If no drain is close by, use a pail to collect run-off.
• Away from hot chimneys, electrical panel and other fire hazards.
• Allow for a power source (110 V standard outlet).
Hang the unit to ceiling joists with the 4 chains and springs
provided (see figures 6 and 7).
VD0064
VD0038
figure 6
figure 7
CAUTION
Make sure the unit is level.
6.3 P
LANNING OF THE
D
UCTWORK
a) Follow the instructions in Section 6.4 below to determine the appropriate duct diameters for your system.
b) Keep it simple. Plan for a minimum number of bends and joints. Keep the length of insulated duct to a
minimum.
c) Do not use wall cavities as ducts. Do not use branch lines smaller than 4” (102 mm) Ø.
d) Do not ventilate crawl spaces or cold rooms. Do not attempt to recover the exhaust air from a dryer or
a range hood. This would cause clogging of the recovery module. Use sheet metal for the kitchen
exhaust duct.
e) Be sure to plan for at least one exhaust register on the highest lived-in level of the house if it has 2 floors
or more.
6.4 C
ALCULATING THE
D
UCT
S
IZE
Use the table below to ensure that the ducts you intend to install will be carrying air flows at or
under the recommended values. Avoid installing ducts that will have to carry air flows near the
maximum values and never install a duct if its air flow exceeds the maximum value.
VI0003
end
branches
main branch
6”ø 140 cfm
5”ø
70 cfm
4”(102 mm) 40 cfm 19 l/s 68 m3/h 60 cfm 28 l/s 102 m3/h
5”(127 mm) 75 cfm 35 l/s 127 m3/h 110 cfm 52 l/s 187 m3/h
6”(152 mm) 120 cfm 57 l/s 204 m3/h 180 cfm 85 l/s 306 m3/h
7”(178 mm) 185 cfm 87 l/s 314 m3/h 270 cfm 127 l/s 459 m3/h
8”(203 mm) 260 cfm 123 l/s 442 m3/h 380 cfm 179 l/s 645 m3/h
Duct Recommended Maximum
Diameter Air Flow Air Flow
figure 8
140 cfm

15
6.0 Installation (cont’d)
NOTE: Examples 6.4.1 and 6.4.2 use imperial measures.
The same calculation applies to metric measures.
6.4.1 Example of calculation:
Problem: My installation requires two exhaust registers (one for the kitchen, one for the bathroom).
I will connect these registers to a main duct which will connect to the unit (high speed performance
value of 140 cfm). What size of duct should I use for the main exhaust duct and for the two end
branches leading to the registers? (See figure 8.)
Solution: Simplified method. (For a more detailed method of calculating duct size refer to the
ASHRAE or HRAI HANDBOOK).
Main duct: Table above indicates a 6” Ø duct: recommended air flow: 120 cfm; maximum air flow:
180 cfm. The high speed air flow of 140 cfm is close enough to the recommended value (120) and
far enough away fromthe maximum value (180). Therefore a 6ӯ duct or larger is an appropriate choice
for the main exhaust duct.
End branches: Each end branch will have to transport an air flow of 70 cfm (140 divided by 2). Table
on page 14 indicates a 5ӯ duct: recommended air flow: 75 cfm; maximum air flow: 110 cfm. The
high speed air flow of 70 cfm is close enough to the recommended value (75) and far enough away
from the maximum value (110). Therefore a 5ӯ duct or larger is an appropriate choice for the 2 end
branches.
NOTE: A 4ӯ duct would have been too small because the maximum acceptable value for a 4ӯ duct
is 60 cfm.
6.4 C
ALCULATING THE
D
UCT
S
IZE
(CONT’D)
6.4.2 Example of a design for a fully ducted system for a unit having a high speed
performance of 222 cfm (See figure 9).
VI0004
4” Ø
42 cfm
6” Ø
129 cfm
5” Ø
65 cfm
5” Ø
64 cfm
6” Ø
93 cfm
5”
6”
7” 7” 6”
6”
6”
4”
4”
4”
4”
7” Ø 222 cfm
7” Ø 222 cfm
4” Ø 42 cfm
6” Ø 84 cfm 6” Ø 96 cfm
6” Ø 138 cfm
figure 9
0
!

6.0 Installation
(cont’d)
6.5.1 Fully Ducted System (as illustrated in Section 5.1)
Stale air exhaust ductwork:
• Install registers in areas where contaminants are produced: kitchen, bathrooms, laundry
room, etc.
• Install registers 6 to 12 inches (152 to 305 mm) from the ceiling on an interior wall OR install
them in the ceiling.
• Install the kitchen register at least 4 feet (1.2 m) from the range top.
• If possible, measure the velocity of the air flowing through the registers. If the velocity is higher
than 400 ft/min. (122 m/min), then the register type is too small. Replace with a larger one.
Fresh air distribution ductwork:
• Install registers in bedrooms, dining room, living room and basement.
• Install registers either in the ceiling or high on the walls with air flow directed towards the ceiling.
(The cooler air will then cross the upper part of the room, and mix with room air before descending
to occupant level.)
• If a register must be floor installed, direct the air flow up the wall.
6.5.2 Exhaust Ducted System (Source Point Ventilation) (as illustrated in Section 5.2)
Stale air exhaust ductwork:(same as for Fully Ducted System, described in point 6.5.1)
Fresh air distribution:
There are two methods for connecting the unit to the furnace:
Method 1: supply side connection
• Cut an opening into the furnace supply duct at least
18 inches (0.5 m) from the furnace.
• Connect this opening to the fresh air distribution port
of the HRV/ERV (use steel duct, see figure 10).
• Make sure that the HRV/ERV duct forms an elbow
inside the furnace ductwork.
• If desired, interlock (synchronize) the furnace blower
operation with the HRV/ERV operation.
(See Section 8.4).
Method 2: return side connection
• Cut an opening into the furnace return duct not less than
10 feet (3.1 m) from the furnace (A+B).
• Connect this opening to the fresh air distribution port of
the HRV/ERV (see figure 11).
NOTE: For Method 2, it is not essential that the furnace
blower runs when the HRV/ERV is in operation, but
we recommend it. If desired, synchronize the furnace
blower operation (see Section 8.4).
6.5 I
NSTALLING THE
D
UCTWORK AND
R
EGISTERS
WARNING
Never install a stale air exhaust register in a room where a combustion device is, such as a gas
furnace, a gas water heater or a fireplace.
0
!
WARNING
When performing duct connection to the furnace, installation must be done in accordance with all
applicable code sand standards. Please refer to your local building code.
CAUTION
When performing connection to the furnace supply duct, this duct must be sized to support the
additional airflow produced by the HRV/ERV. Also, use a steel duct with a backdraft damper to
prevent the risk of overheating the HRV/ERV.
!
VD0040
B
A
VD0041
minimum
18” (0.5 m)
Steel duct with
backdraft damper
A+B= not less
than 10’ (3.1 m)
figure 10
figure 11
16

17
6.5 Installing the Ductwork and Registers (cont’d)
6.0 Ductwork Installation (cont’d)
6.5.3 Simplified installation (Volume Ventilation) (as illustrated in Section 5.3)
There are two methods (figures 12 and 13) for connecting the unit to the furnace:
Method 1: return-supply Method 2: return-return
Stale air intake:
• Cut an opening into the furnace return duct (at least 6 feet (1.8 m) from the furnace).
• Connect this opening to the stale air intake port on the HRV/ERV as shown .
Fresh air distribution: (same instructions as for Method 1 or Method 2, Section 6.5.2).
For Method 2 (return-return) make sure there is a distance of at least 3 feet (0.9 m) between
the 2 connections to the furnace.
NOTE: For Method 1, it is not essential to synchronize the furnace blower operation with the
HRV/ERV operation, but we recommend it.
VD0042
A
BVD0043
A
B
minimum 3’
(0.9 m)
A+B= not less
than 10’ (3.1 m)
minimum
18” (0.5 m)
figure 12
figure 13
A+B= not less
than 10’ (3.1 m)
CAUTION
If using Method 2, make sure the furnace blower operation is synchronized with the
HRV/ERV operation! See Section 8.4.
WARNING
When performing duct connection to the furnace, installation must be done in accordance with all
applicable code sand standards. Please refer to your local building code.
CAUTION
When performing connection to the furnace ducts (Method 1), these ducts must be sized to support
the additional airflow produced by the HRV/ERV. Also, the supply duct must be a steel duct with a
backdraft damper to prevent the risk of overheating the HRV/ERV.
0
!
Steel duct with
backdraft damper

18
Rigid duct:
Use duct tape to connect the rigid ducts to the ports.
Make sure that the 2 balancing dampers are left in a fully open position beforeconnecting the ducts to these
ports (fresh air distribution port and stale air exhaust port as shown on figure 14).
6.0 Installation (cont’d)
figure 14
CAUTION
Do not use screws to connect rigid ducts to the ports.
6.6 C
ONNECTING
D
UCT TO THE
U
NIT
Insulated flexible duct
Use the following procedure for connecting the insulated flexible duct to the ports on the unit (exhaust to
outside and fresh air from outside).
a) Pull back the insulation to expose the flexible duct.
b) Connect the interior flexible duct to the port using a duct tie.
c) Carefully seal the connection with duct tape.
d) Pull the insulation over the joint and tuck it between the inner and outer rings of the double collar.
e) Pull the vapor barrier over the insulation and over the outer ring of the double collar.
f) Apply duct tape to the joint making an airtight seal. Avoid compressing the insulation when you pull the
tape tightly around the joint. Compressed insulation loses its R value and causes waterdripping due to
condensation on the exterior surface of the duct.
a) b) c) d), e) f)
CAUTION
Make sure that the vapor barrier on the insulated ducts does not tear during installation
to avoid condensation within the duct.
VJ0001
VJ0002
VJ0003
VJ0004
VJ0005

19
6.0 Installation (cont’d)
6.7 I
NSTALLING THE
E
XTERIOR
H
OODS
Choose an appropriate location for installing
the exterior hoods:
• a minimum distance of 6 feet (1.8 m)
between the hoods to avoid
cross-contamination
• a minimum distance of 18 inches
(457 mm) from the ground
Make sure the intake hood is at least 6 feet
(1.8 m) away from any of the following:
• dryer exhaust, high efficiency furnace
vent, central vacuum vent
• gas meter exhaust, gas barbecue-grill
• any exhaust from a combustion source
• garbage bin and any other source of
contamination
Refer to figure 15 for connecting the
insulated duct to the hoods. Place the
“FRESH AIR INTAKE” sticker, provided in the
installation kit, on corresponding hood. An
“Anti-Gust Intake Hood” should be installed
in regions where a lot of snow is expected to
fall.
CAUTION
All models require an exhaust hood with a backdraft damper.This damper closes when the unit is off
and prevents unwanted cold air from entering the house.
VD0028
Exhaust
hood
Optional duct
location
Tape and duct tie
Caulking
Intake
hood
6ӯ
(152 mm)
18”
(457 mm)
18”
(457 mm)
6’
(1.8 m) 6’
(1.8 m)
18”
(457 mm)
figure 15
6.8 C
ONNECTING THE
D
RAIN
12"(305 mm)
VO0004
VO0003
Attach the 2 plastic drain fittings
to the unit using the gaskets,
washers and nuts as shown.
Cut 2 sections of plastic tubing,
about 12” (305 mm) long and
attach them to each drain fitting.
12VO0005
Join the 2 short sections to the
“T” junction and main tube as
shown.
3
VO0011
To drain
Tie-wrap
4
Make a water trap loop in the tube to prevent the unit from drawing
unpleasant odors from the drain source. Make sure this loop is
situated BELOW the “T” as shown. This will prevent water from
being drawn back up into the unit in case of negative pressure. Run
the tube to the floor drain or to an alternative drain pipe or pail. Be
sure there is a slight slope for the run-off.

20
ECONOMY model
7.1 M
AIN
C
ONTROLS
7.0
Control Devices
CO
NDEN
S
AT
I
0
N
CO
NTR
O
L
AIR SUPPL
Y CONTRO
L
Y CONTRO
L
L
MIN.
MAX.
O
F
F
A
AI
R
R
I
R
I
EXCHANGE
CH
HA
-2
0
C
-
4
°
41
°
F
C
O
F
Z
N
E
S
U
M
M
E
R
VC0027
VALUE model
°
C
-
4
°
F
-
5
C
41
°
F
CO
NDEN
S
AT
I
0
N
CO
NTR
O
L
AIR SUPPL
Y CONTRO
L
Y CONTRO
L
L
CO
NDEN
SA
T
I
O
N
CO
NTR
OL
MAXIM
U
M
S
PEE
D
AIR EX
C
HAN
G
E IN PR
OG
RE
SS
MIN.
MAX.
CONTINUOUS
CONTINUOUS
INTERMITTENT
T
INTERMITTENT
20 MI
M
N
.
N
ON
ON
40 MIN.
M
OFF
OF
C
O
M
Z
O
E
S
U
M
M
E
R
VC0028
Models Economy Value
Off Position X X
Intermittent Exchange (TBI)
(20 min./ON -40 min./OFF) X
Low Speed Continuous Exchange X X
High Speed Continuous Exchange X X
Condensation Control
(Temperature scale) XX
Mode Indicator X
Air Exchange Indicator X
Condensation Control
Max. Speed Indicator X
Maintenance Indicator with
Intermittent Flashing X
Sliding Button X
Push Button X
Switches Indicators Detector Modes
Types
CAUTION
All models require a main control.
This manual suits for next models
3
Table of contents
Other protech Fan manuals
Popular Fan manuals by other brands

Ebmpapst
Ebmpapst W4D710-GF01-01 operating instructions

Broan
Broan ZB110HL installation guide

Vents-us
Vents-us VK user manual

Craftmade
Craftmade Theo installation guide

Home Decorators Collection
Home Decorators Collection TOLEDO 52-PLM Use and care guide

Kichler Lighting
Kichler Lighting 52 inch Colerne LED instruction manual