protech 84-HRV200 User manual

User Manual
Address of your installer
04187-03/11/15
HRV / ERV Ventilation Systems
PROTECH™ MODELS
84-HRV100
84-HRV200
84-ERV100
84-ERV200
VB0038

The purpose of this manual is to help you with the use of your unit. Section 2
(How to Operate the Unit Using Controls) shows you how you can operate the
unit in no time. Section 3 deals with maintenance and explains how to maintain
the unit to ensure maximum operation and performance. In the other sections,
for example Troubleshooting, you will learn how to solve minor problems
(Section 4); plus other important information which we urge you to read.
Several models are described in this publication. Some details of your unit may
be slightly different than the ones shown, as the illustrations are typical ones.
We welcome any suggestions you may have concerning this manual and/or the
unit, and we would appreciate hearing your comments on ways to better serve
you. Please forward all correspondence to us at the address indicated on the
product registration card included with this manual.
This manual uses the following symbols to emphasize particular information:
NOTE: Indicates supplementary information needed to fully complete an
instruction.
Finally, we want to congratulate you on your purchase of this excellent unit which
will allow you and your family to enjoy fresh air throughout your home for years
to come!
2
ABOUT THIS MANUAL/PRODUCT
CAUTION
Some activities create dust or vapors which may damage your unit. You
must therefore turn off and unplug your unit in the following situations:
• major renovation work
• housing construction
• sanding (e.g. gypsum joints, etc.)
• varnishing
During very heavy snowstorms, the unit should also be turned off to avoid
problems caused by snow entering the unit, even if it is equipped with an
anti-gust intake hood.
WARNING
Identifies an instruction which, if not followed, might cause serious
personal injuries including possibility of death.
0
!
CAUTION
Denotes an instruction which, if not followed, may severely damage the
unit and/or its components.

1.0 YOUR UNIT AND ITS PURPOSE . . . . . . . . . . . . . . . . .4
1.1 Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.2 Purpose of the Ventilation System . . . . . . . . . . . . . . . . . .4
1.3 Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
1.4 Defrosting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
1.5 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.0 HOW TO OPERATE THE UNIT USING CONTROLS . . . . . .7
2.1 Instructions Regarding your Control Devices . . . . . . . . . .7
2.2 Using the ECONOMY Main Control . . . . . . . . . . . . . . . . .8
2.3 Using the VALUE Main Control . . . . . . . . . . . . . . . . . .9-10
2.4 Using the Optional Wall Control . . . . . . . . . . . . . . . . . . .11
3.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . .12
3.1 Every Three Months . . . . . . . . . . . . . . . . . . . . . . . . .12-13
3.2 Annual Maintenance (Fall) . . . . . . . . . . . . . . . . . . . . .14-15
4.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . .16
3
TABLE OF CONTENTS

1.1 UNIT DESCRIPTION
4
1.0 YOUR UNIT AND ITS PURPOSE
Your ventilation system is designed to provide fresh air, warmed outdoor air to
your home while exhausting stale, humid air from your home. By eliminating
accumulated pollutants and humidity, it maintains an optimum air quality and an
ideal relative humidity.
1.2 PURPOSE OF THE VENTILATION SYSTEM
VH
00
2
5
NOTES: 1. Shown with a forced air system. Can also operate on its own.
2. Installation may vary.
1
2
3
4
5
VL0017
1. Power supply cord
2. Filters
3. Recovery core
4. Condensation tray
5. Fan

ERV: Units equipped with a heat and humidity recovery core (enthalpic core)
can reduce ventilation costs in winter as well as in summer.
1. During the heating season, the unit draws the humidity and heat from the
stale air and transfers them, in part, to the cold air entering the house, thus
avoiding dryness problems and providing maximum comfort.
In order to preserve the structure of the enthalpic core, the unit will only
exchange 20 minutes per hour when the temperature drops under -15°C
(5°F).
Example
(in winter)
:
1.3 RECOVERY
5
HRV: Units equipped with a heat recovery core (polypropylene core) are
specifically designed to control excess humidity and reduce ventilation costs by
recovering the heat energy from the exhausted air, and using that same heat
energy to warm the fresh air being supplied. This heat recovery process is
accomplished in such a way that the stale air is never mixed with the fresh air.
Example
(in winter)
:
OUTSIDEINSIDE
STALE AIR TO OUTSIDE 4°C/40°F
FRESH AIR TO BUILDING 18°C/64°F
FRESH AIR FROM OUTSIDE 0°C/32°F
STALE AIR FROM BUILDING 22°C/72°F
VF0011
2. During the cooling season, the unit reverses the process, preventing the
humidity from the outside air from entering into the house.
Example
(in summer with air conditioning)
:
OUTSIDEINSIDE
VF
00
2
7
STALE AIR TO OUTSIDE 4°C/40°F
FRESH AIR TO BUILDING 18°C/64°F
FRESH AIR FROM OUTSIDE 0°C/32°F
STALE AIR FROM BUILDING 22°C/72°F
OUTSIDEINSIDE
VF
00
2
8
STALE AIR TO OUTSIDE 30°C/86°F
FRESH AIR TO BUILDING 27°C/80°F
FRESH AIR FROM OUTSIDE 32°C/90°F
STALE AIR FROM BUILDING 25°C/77°F

6
When the outside temperature is below 0°C (32°F), recovery (of heat or energy)
creates frost in the core.To maintain its proper operation, the unit is programmed
to defrost the recovery core. The defrost frequency varies according to the
outside temperature. Defrosting lasts 6 minutes. During the defrost cycle, the
unit shifts to maximum speed and the dampers close.
After defrosting, the unit returns to the operating mode selected by the user.
1.4 DEFROSTING
1.5 SPECIFICATIONS
Model 84 HRV100 / ERV100
Width 30 1/4“ (768 mm)
Height 20“ (508 mm)
Depth 13 3/4“ (349 mm)
Weight 65 lbs (30 kg)
Electrical Supply 120 V, 60 Hz
Power Consumption 150 Watts
Model 84 HRV200 / ERV200
Width 30 1/4“ (768 mm)
Height 20“ (508 mm)
Depth 19“ (483 mm)
Weight 73 lbs (33 kg)
Electrical Supply 120 V, 60 Hz
Power Consumption 225 Watts

7
2.1 INSTRUCTIONS REGARDING YOUR CONTROL DEVICES
Determine which controls are installed in your house and identify them in the
following table on this page. Then, you can proceed to the pages indicated to
learn how to CONTROL your unit.
CO
NDEN
S
AT
I
0
N
CO
NTR
O
L
AIR SUPPL
Y CONTRO
L
Y CONTRO
L
L
MIN.
MAX.
O
F
F
A
AI
R
R
I
R
I
EXCHANGE
CH
HA
-2
0
C
-
4
°
41
°
F
C
O
F
Z
N
E
S
U
M
M
E
R
VC0027
°
C
-
4
°
F
-
5
C
41
°
F
CO
NDEN
S
AT
I
0
N
CO
NTR
O
L
AIR SUPPL
Y CONTRO
L
Y CONTRO
L
L
CO
NDEN
SA
T
I
O
N
CO
NTR
OL
MAXIM
U
M
S
PEE
D
AIR EX
C
HAN
G
E IN PR
OG
RE
SS
MIN.
MAX.
CONTINUOUS
CONTINUOUS
INTERMITTENT
T
INTERMITTENT
20 MI
M
N
.
N
.
N
ON
ON
40 MIN.
M
OFF
OF
C
O
M
Z
O
E
S
U
M
M
E
R
VC0028
2.0 HOW TO OPERATE THE UNIT USING CONTROLS
MAIN CONTROLS
ECONOMY main control . . . . . . . . . . . . . .Page 8
VALUE main control . . . . . . . . . . . . . . . . .Page 9
OPTIONAL WALL CONTROL
20/40/60-min. push-button timer . . . . . . . . .Page 11
VC0046
20 min.
40 min.
60 min.

8
Location: Located in the busiest area of the house.
Purpose: To adjust air supply and reduce condensation on windows.
ADJUSTING THE AIR SUPPLYCONTROL
a) Select speed “MIN.” or “MAX.” using
switch A(as shown on diagram).
• When “MIN.” (minimum speed) is
selected, if the knob Bis set above
the click, the unit will exchange in
low speed with the outside and if it
is set below the click, the unit will
exchange on high speed with the
outside until the desired humidity
level has been reached.
• When “MAX.” (maximum speed) is
selected, the unit will exchange on
high speed with the outside either
if he knob Bis set below of above the click.
b) To turn the unit off, place selector Aat the “OFF” position.
Optional controls, however, may still be active.
ADJUSTING THE CONDENSATION CONTROL
Setting during the summer months:
Normally there is no condensation on your windows during this period which
therefore eliminates the need of the condensation control for a few months. Set
knob Bat the “SUMMER’’ positon during this period.
Setting during the fall, winter and spring months:
1) Determine the humidity level in your house (bring the knob Bcounterclockwise
to -20°C, then bring it back clockwise slowly until you hear a “click”).
2) Set knob Ba notch under this temperature level or “click”.
NOTES: 1. Do not select a temperature below -20°C. This could lead to excessive
dryness in the air causing discomfort for the occupants.
2. When the humidity level is high, the unit automatically operates at
maximum speed. If you change the setting of your “AIR SUPPLY”
knob (B) at that time, it will remain at maximum speed until the
humidity level is reduced, and then switch to the desired setting.
It is possible (and normal) to experience condensation on your windows
when drastic changes in temperature happen (for example: -5°C (23°F) to
-20°C (-4°F) within few hours). In that case, we suggest waiting a few days
to allow the situation to stabilize.
2.2 USING THE ECONOMY MAIN CONTROL
CO
NDEN
S
AT
I
0
N
CO
NTR
O
L
AIR SUPPL
Y CONTRO
L
Y CONTRO
L
L
MIN.
MAX.
O
F
F
A
AI
R
R
I
R
I
EXCHANGE
CH
HA
-2
0
C
-
4
°
41
°
F
C
O
F
Z
N
E
S
U
M
M
E
R
VC0027
B
A

9
2.3 USING THE VALUE MAIN CONTROL
Location:Located in the busiest area of the house.
Purpose: To adjust air supply and reduce condensation on windows.
ADJUSTING AIR SUPPLYCONTROL
a) Press “PUSH” (A) until the “MIN.”, “MAX.” or “INTERMITTENT” light
indicator appears.
• When “MIN.” (minimum speed) is
selected, if the knob Bis set
above the click, the unit will
exchange in low speed with the
outside and if it is set below the
click, the unit will exchange on
high speed with the outside until
the desired humidity level has
been reached.
• When “MAX”. (maximum speed)
is selected, the unit will
exchange on high speed with
the outside either if he knob Bis
set below of above the click.
• Select “INTERMITTENT” (20 minutes minimum speed exchange every
hour) when you are away from the house for a few days or when you
deem the inside air too dry.
b) To turn the unit off , press “PUSH” (A) until the “MIN.”, “MAX.” and
“INTERMITENT” light indicators are all turned off.
NOTE: Optional controls will still be active. (Indicator (C) will be the only one to
light up if an optional control is active).
ADJUSTING CONDENSATION CONTROL
Setting during the summer months:
Normally there is no condensation on your windows during this period which
therefore eliminates the need of the condensation control for a few months. Set
knob Bat the “SUMMER’’ positon during this period.
Setting during the fall, winter and spring months:
Ideally, maintain humidity level within the “Comfort Zone” (between 5°C and
-20°C), which is the dark area around knob B.
To reduce humidity level, turn knob B clockwise a notch below the click. The unit
will then switch to high speed, lighting up the humidity light (Dindicator).When
this light goes "OFF" (after a few hours or a few days), repeat the same procedure
if excess humidity persists.
NOTE: If the air is too dry, set your knob B back to the “Comfort Zone” and use
INTERMITTENT or turn off the unit.
When the humidity light (Dindicator) goes "ON", you can still change the
mode of operation but your change will take place only when the light goes OFF.
°
C
-
4
°
F
-
5
C
41
°
F
CO
NDEN
S
AT
I
0
N
CO
NTR
O
L
AIR SUPPL
Y CONTRO
L
Y CONTRO
L
L
CO
NDEN
SA
T
I
O
N
CO
NTR
OL
MAXIM
U
M
S
PEE
D
AIR EX
C
HAN
G
E IN PR
OG
RE
SS
MIN.
MAX.
CONTINUOUS
CONTINUOUS
INTERMITTENT
T
INTERMITTENT
20 MI
M
N
.
N
.
N
ON
ON
40 MIN.
M
OFF
OF
C
O
M
Z
O
E
S
U
M
M
E
R
VC0028
A
B
C
D

10
2.3 USING THE VALUE MAIN CONTROL (CONT’D)
UNDERSTANDING THE LIGHT INDICATORS
AIR SUPPL
Y CONTRO
L
Y CONTRO
L
L
CO
NDEN
SA
T
I
O
N
CO
NTR
OL
MAXIM
U
M
S
PEE
D
AIR EX
C
HAN
G
E IN PR
OG
RE
SS
MIN.
MAX.
CONTINUOUS
CONTINUOUS
INTERMITTENT
T
INTERMITTENT
20 MI
M
N
.
N
ON
ON
40 MIN.
M
OFF
OF
VC0028
LIGHTS UP when you have
selected the intermittent mode.
FLASHES when maintenance is
required (see Section 3).
LIGHTS UP when the
system is operating
(exhausting stale
air from the house
and drawing in
fresh air).
FLASHES when
the defrosting cycle
is malfunctioning
(see Section 3).
LIGHTS UP when
the control has
detected excess
humidity. This forces
the motor to operate
at high speed. The
light indicator turns
off when the
humidity drops to
the level associated
with the temperature
selected on knob B.

11
Location: Located in the bathroom or in other locations where there is
temporary excess humidity or pollutants.
Purpose: To eliminate excess humidity produced by showers or other
periodic activities producing pollutants.
20/40/60-MINUTE PUSH-BUTTON TIMER:
Activate the push button. Within 2 seconds, push
one time for 20 minutes, two times for 40 minutes
or three times for a 60-minute activation.
Results expected:
1. Motor speed: high for 20, 40 or 60 minutes.
2. Indicator light goes “ON” and flashes every
5 seconds (one time to indicate a 20-minute
operation, two times for a 40-minute, and three
times for a 60-minute operation).
3. Air exchange indicator light goes “ON” (VALUE
wall control only).
NOTE: To stop activation, push one more time.
2.4 USING THE OPTIONAL CONTROL
VC0046
20 min.
40 min.
60 min.

12
1. Disconnect the power supply.
2. Unlatch the door. Lift the pannel
towards you. Hold it firmly and hit
on the right side of the pannel.
The door should slide to the left.
3. Clean the inside of the door with a
damp cloth.
4. A) Clean filters
• Remove filters.
• Vacuum to remove most
of the dust.
• Wash with a mixture of
warm water and mild
soap. You may add bleach
if you wish to disinfect
(one tablespoon per gal-
lon). Rinse thoroughly.
Shake filters to remove
excess water and let dry.
NOTE: Washing the filters in the top
tray of the dishwasher is
possible, but the aluminum
frame might tarnish.
MAINTENANCE PROCEDURE:
3.1 EVERY THREE MONTHS
Regular maintenance should be performed every 3 months. Annual maintenance
should also take place every fall season.
3.0 MAINTENANCE
VD0005
VD0007
WARNING
Dangerous voltage may be present. During maintenance and repairs, the
unit must always be turned off, then unplugged.
We take great care to minimize sharp edges; however, please proceed
with caution when handling all components.
0
!
VD
0
1
00

13
3.1 EVERY THREE MONTHS (CONT’D)
5. Clean the condensation traywith a
damp cloth.
6. Check the exterior air intake hood:
• Make sure there are no leaves, twigs,
ice or snow that could be drawn into
the vent.
• Clean if necessary.
7. Reassemble the components:
• Filters
• Door (The door is secured when you hear a click.)
8. Reconnect the power supply.
VD0101
CAUTION
Even a partial blocking of this air vent could cause the unit to malfunction.

14
3.2 ANNUAL MAINTENANCE (FALL)
Repeat steps 1 to 6 from the previous Section and continue with the following steps:
1. Clean the recovery core
A- Polypropylene core (heat recovery units: HRV100/HRV200)
• Remove the recovery core.
• Let it soak in a mixture of cold or
lukewarm water and mild soap
(dishwashing liquid).
• Rinse thoroughly.
• Shake the core to remove excess
water and let it dry.
B- Enthalpic paper core (heat and humidity recovery units: ERV100/ERV200)
• Remove the recovery core.
• Remove dust using a vacuum cleaner with a soft brush attachment.
VD
0
1
02
CAUTION
Handle the recovery core with care.
CAUTION
This type of recovery module cannot be washed with water.
WARNING
Dangerous voltage may be present. During maintenance and repairs, the
unit must always be turned off, then unplugged.
We take great care to minimize sharp edges; however, please proceed
with caution when handling all components.
0
!
2. Clean the centrifugal fan wheels
VD
0
1
03
ARemove the wing nut.
VE
0050
BDisconnect the fan motor wires.

3.2 ANNUAL MAINTENANCE (FALL)(CONT’D)
15
2. Clean the centrifugal fan wheels (cont’d)
3. Put the components back in place:
• Fan assembly (fan motor wires, wing nut)
• Recovery core
• Filters
• Door
4. Reconnect the power supply.
VD
0
1
06
CRemove the fan assembly.
DCheck for any dust accumulation
on the blades.
EClean with a small brush
if necessary.
VD
0
1
04
VD
0
1
05
CAUTION
Do not oil the motor! It is already permanently
lubricated.

16
TYPE OF PROBLEM TRY THIS...
1 Nothing works. • See if the unit is plugged in.
• See if the unit is receiving power
from the house circuit breaker or fuse.
2 All light indicators on the wall control • Unplug the unit, wait 30 seconds,
are flashing then reconnect. If the problem
(every 8 seconds). continues, contact your installer.
3 Noisy unit. • Clean the fan assembly (see
Section 3.2). If the problem continue,
contact your installer.
4 Condensation on windows. • Adjust the humidity control knob as
(Air too humid.) per instructions (see Section 2).
• Operate the unit at maximum speed
(MAX.) during activities generating
excess humidity (family gatherings,
extra cooking, etc.).
• Leave curtains half-open to allow air
circulation.
• Store all firewood in a close room with
a dehumidifier or in a well ventilated
room, or store the wood outside.
• Keep the temperature in your house
above 18°C (64°F).
5 Air too dry. • Do not adjust your humidity control
below -20°C (-4°F).
• Operate the unit at low speed (MIN.).
• Temporarily switch to the intermittent
mode.
• Temporarily use a humidifier.
6 Air too cold at the air supply grille. • Make sure the outside hoods are not
blocked.
• Operate the unit at low speed (MIN.).
• Have the system balancing checked.
• Have the unit defrost system checked.
• Install a duct heater.
If the problem persists, contact your installer at the telephone number and
address indicated on the first page of this manual or call for your local distributor.
4.0 TROUBLESHOOTING
If you think your unit is malfunctioning, check some of the following.
This manual suits for next models
3
Table of contents
Other protech Fan manuals
Popular Fan manuals by other brands

THOMSON
THOMSON THVEL470K instruction manual

Aereco
Aereco VTZ-0.5 Maintenance Instruction

Hunter
Hunter 7 Models Installation and operation manual

Eberg
Eberg HUX 40 instruction manual

Westinghouse
Westinghouse ETL-ES-Solana-WH09 use and care manual

Kichler Lighting
Kichler Lighting Meredith instruction manual