4/8/2013 Voltage Monitor – Instruction Manual
Model 520603-2V150
P/N 520603-
2V150 REV. B 9/11 © 2011 RAILWAY EQUIPMENT CO.
3
2.1.1 Figure 1. Front Panel of Voltage Monitor
2.1.2 Digital Display
The idle screen displays the input voltage. If only channel one has input voltage, only
channel one will be displayed. If both channels are monitoring voltage sources, both
will be displayed. If the optional current or temperature probes are being used, the
lower screen will alternate between displaying channel two voltage, temperature, and
current. With only channel one powered, the following screens will be scrolled through
when the MODE button is depressed:
PASSWORD ___- The password to adjust parameters is 5. It is entered by pressing
the INCREASE button until 5 appears in the parameter field.
MAX VCH1
SET __._ - This displays the high voltage setpoint parameter for channel one. It can
be adjusted from 0 to 50.0 VDC by use of the INCREASE or DECREASE push
buttons. If the input voltage rises above the setpoint, the channel one output relay will
change state and the channel one CHANNEL OK LED will go out. Factory default is
50.0 VDC.
LOW VCH1
SET __._ - Low voltage setpoint for channel one, adjustable from 0 to 50.0 VDC.
If the input voltage falls below the setpoint, the output relay will change state and the
CHANNEL OK LED will go out. Factory default is 0 VDC.
DELAY CH1
SET ___ - Delay time in seconds before a voltage falling outside the parameters
will trigger a fault. This parameter is adjustable from 1 to 600 seconds. Factory
default is 10 seconds.
If a voltage input is added on channel two, in addition to the input on channel one,
the following additional screens to appear as the MODE button is used:
MAX VCH2
SET __._ - High voltage setpoint for channel two. Voltage range is 0 to 150.0 VDC
Factory default is 150.0 VDC.
LOW VCH2
SET __._ - Low voltage setpoint for channel two. Voltage range is 0 to 150.0 VDC.
Factory default is 0 VDC.
DELAY CH2
SET ___ - Delay time in seconds for channel two. Range is 0 to 600 seconds.
Factory default is 10 seconds.
There is an optional amp probe available which can be set up to trip the same relay
as a voltage fault will trip on Channel two. The addition of the current probe will
cause the following additional screens to appear: