RBH Access Technologies Integra32 User manual

Integra32™
Integrated Alarm Monitoring
and Access Control
HARDWARE MANUAL
new generation
building security

Integra32™Hardware Guide RBH Access Technologies Inc.
Copyright Notice
Copyright ©1995 - 2013 by RBH Access Technologies Inc.
All rights reserved Worldwide. Printed in Canada. This publication has been provided
pursuant to an agreement containing restrictions on its use. No part of this book may be
copied or distributed, transmitted, stored in a retrieval system, or translated into any
human or computer language, in any form or by any means, electronic, mechanical,
magnetic, manual, or otherwise, or disclosed to third parties without the express written
consent of RBH Access Technologies Inc., Mississauga, Ontario, Canada.
Trademark
Integra32™is the trademark of RBH Access Technologies Inc. Windows is a trademark
of Microsoft Corporation. All other product names mentioned herein are the property of
their respective owners. Use of a term in this book should not be regarded as affecting
the validity of any trademark or service mark.
Disclaimer
This book is provided as is, without warranty of any kind, either express or implied,
including but not limited to performance, merchantability, or fitness for any particular
purpose. Neither RBH Access Technologies Inc. nor its dealers or distributors shall be
liable to any person or entity with respect to any liability, loss, or damage, caused or
alleged to have been caused directly or indirectly by this information. Further RBH
Access Technologies Inc. reserves the right to revise this publication, and to make
changes to the content hereof from time to time, without the obligation of RBH Access
Technologies Inc. to notify any person or organization of such revision or changes.
FCC
This device complies with part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference, and (2)
this device must accept any interference received, including interference that may cause
undesired operation.
Integra32 Revision 4.2 Printing Date 6 June, 2013
RBH ACCESS TECHNOLOGIES INC.
2 Automatic Road, Suite 108
Brampton, Ontario
CANADA
L6S 6K8

Table of Contents
RBH Access Technologies Inc. Integra32™Hardware Guide
i
T a b l e o f C o n t e n t s
CHAPTER 1 INTRODUCING INTEGRA32™........................................................................................................1
CHAPTER 2 INTELLIGENT FIELD PANEL........................................................................................................2
IRC2000 ....................................................................................................................................................................2
Connection Details................................................................................................................................................2
Earth......................................................................................................................................................................4
DIP Switch Settings ...............................................................................................................................................5
PC Connections.....................................................................................................................................................7
Controller Networks ............................................................................................................................................10
Status LED's ........................................................................................................................................................11
Jumpers................................................................................................................................................................12
URC2000.................................................................................................................................................................13
Connection Details ..............................................................................................................................................13
Earth....................................................................................................................................................................15
DIP Switch Settings .............................................................................................................................................15
PC Connections...................................................................................................................................................16
Status LED's ........................................................................................................................................................17
Jumpers................................................................................................................................................................17
ELEVATOR CONTROL................................................................................................................................................18
Connection Details ..............................................................................................................................................19
PC100......................................................................................................................................................................21
Connection Details ..............................................................................................................................................21
Status LED's ........................................................................................................................................................22
Jumpers................................................................................................................................................................22
CHAPTER 3 INPUT & OUTPUT CONNECTIONS............................................................................................23
INPUTS......................................................................................................................................................................23
RTE (Request to Exit) ..........................................................................................................................................23
DC (Door Contact)..............................................................................................................................................23
General Purpose..................................................................................................................................................23
INPUT CIRCUIT TYPES...............................................................................................................................................24
OUTPUTS ..................................................................................................................................................................28
Lock Output .........................................................................................................................................................28
Handicap Output .................................................................................................................................................28
Alarm Shunt Output.............................................................................................................................................28
Modem Power Output..........................................................................................................................................28
General Purpose Output......................................................................................................................................28
Switching Inductive Devices (Locks, Bells) .........................................................................................................29
RELAY OUTPUT OPERATION.....................................................................................................................................30
Lock Output .........................................................................................................................................................30
ACCESS POINT OPERATING MODES ..........................................................................................................................32
High Security.......................................................................................................................................................32
Unlocked..............................................................................................................................................................32
Door Held Open Warning ...................................................................................................................................32
Door Held Open Alarm .......................................................................................................................................32

Table of Contents
Integra32™Hardware Guide RBH Access Technologies Inc.
ii
Keypad / Reader Combination.............................................................................................................................32
Access Granted....................................................................................................................................................32
Access Denied......................................................................................................................................................32
EXIT READER INTERFACE CONNECTION DIAGRAMS.................................................................................................33
IRC-2000 Connection..........................................................................................................................................33
URC-2000 Connection ........................................................................................................................................34
IRC-2000 SPECIFICATION....................................................................................................................................36
URC-2000 SPECIFICATION...................................................................................................................................37
PC-100 SPECIFICATION........................................................................................................................................38
ELC-08 SPECIFICATION.......................................................................................................................................39
CABLE SPECIFICATION.......................................................................................................................................40
INDEX........................................................................................................................................................................41
LICENSE & WARRANTY.......................................................................................................................................43
APPENDIX A: PC-100 INTERFACE APPLICATIONS.......................................................................................44
WIRING.....................................................................................................................................................................44
DSC ALARM PANEL INTERFACE...............................................................................................................................45
BOSCH ALARM PANEL INTERFACE ...........................................................................................................................46
SUMMIT ALARM PANEL INTERFACE .........................................................................................................................48
APPENDIX B: DIALUP MODEM CONFIGURATION.......................................................................................51
REMOTE SITE MODEM:.............................................................................................................................................51
SERVER (HOST)SITE MODEM: .................................................................................................................................52
MODEM CONNECTION ..............................................................................................................................................60

Chapter 1
Introducing Integra32
RBH Access Technologies Inc. Integra32™Hardware Guide
1
C h a p t e r 1
I n t r o d u c i n g I n t e g r a 3 2 ™
The Integra32™system from RBH Access Technologies Inc. represents the latest in
access technology specifically designed for smaller applications. Its intuitive graphical
interface allows users to take advantage of the power of the Integra32™with a minimal
amount of training.
The IRC-2000 Intelligent Field Panels utilize flash firmware for easy upgrades. The
IRC-2000 panel uses fully distributed intelligence for off-line operations. In addition to
supporting two card readers, each IRC-2000 Intelligent Field Panel also has eight fully
supervised alarm inputs along with eight outputs (four dry contact outputs and four open
collector outputs). The IRC2000‟s memory has been increased to now hold 5,000 cards
and can be further extended to hold 8,000 cards.
An alternate panel the URC-2000 can be used along with or instead of the original IRC-
2000. This panel also uses fully distributed intelligence for off-line operations. In
addition to supporting two card readers, each URC-2000 panel has four fully supervised
alarm inputs and four outputs as well as a 3,000 card capacity. Communication is handle
through an RS485 port.
The PC is used for data entry, setting up the database, and monitoring activity on the
system. Once the database is downloaded to the controllers, the PC is not required for
system operation. Should the PC be powered down, the controller will perform all
access and other control functions (but of course not Global functions), including
logging history events. When the connection is restored, the log will then be reported to
the PC.
Up to thirty-two panels can be connected together, for a maximum capacity of sixty-four
doors. Connect the PC to the first control directly via RS232 or by an IP address (using
an existing Ethernet). Additional controls can be connected to the first control with
RS485 (maximum total wiring distance is four thousand feet) to a maximum of sixteen
panels per connection (or network).
Interfacing with intrusion alarm panels has been made possible. Connect to Bosch or
Summit panels through the PC-100 board.
Elevator control is accomplished with a modified URC2000 panel and ELC-08 relay
boards. Four relay boards can control up to thirty-two floors for two readers.
Other features include the capacity for forty holidays, one hundred and twenty-eight time
zones, as well as handicap access by cardholder. High security and lock/unlock modes
are also supported. Each panel can have up to sixty-four input/output links, and the
system is capable of holding two hundred and fifty-five pre-programmed operator
commands. Both local and timed Antipassback are also supported.

Chapter 2
Intelligent Field Panel
Integra32™Hardware Guide RBH Access Technologies Inc.
2
C h a p t e r 2
I n t e l l i g e n t F i e l d P a n e l
The Integra32™access control system consists of one or more controllers. All information
required by the controller is downloaded from the PC and stored locally in flash memory. This
information includes configuration data, cardholder records, access levels, schedules, and all
other records necessary for the operation of the system. The controller operates independent of
the PC and all decision-making is performed locally, even in the event of total power loss (while
operating on battery backup).
IRC2000
Connection Details
Power
The IRC-2000 requires 9 to 14 volts DC and draws about 250ma.
PC Interface
The Modem/Host interface connects the IRC-2000 to a PC or modem through an RS232 port.
TCP/IP Ethernet interface, or an RS485 (2-wire) interface [like a USB-485 module] can also be
used to connect the panels with the software. (The RS-485 connection is made in parallel with
the additional panels)
Inputs
There are two common terminals for each set of four inputs (one between inputs one and two,
another between three and four, one between five and six, and one between seven and eight).
Seven different input types are supported (including normally open, normally closed, one
resistor, and two resistor configurations).
Outputs
Four of the eight programmable outputs are dry contact relays (UL rated 2A @ 30v dc). These
are designated as outputs one, two, five, and six. The other four outputs are solid-state switches
(open collector to ground capable of sinking 100ma).
Readers
Readers are connected to non-programmable outputs BUZ, RED, & GRN, as well as data inputs
D0 and D1. Both readers have their own connection terminals, reader A on the left side of the
board and reader B on the right.

Chapter 1
Intelligent Field Panel
RBH Access Technologies Inc. Integra32™Hardware Guide 3

Chapter 2
Intelligent Field Panel
Integra32™Hardware Guide RBH Access Technologies Inc.
4
Earth
The controller contains several layers of protection against induced high voltage
transients from static discharge, lightning, and power line spikes. In order for this
protection to be fully effective, a good connection to earth ground is essential. Wire this
connection to a metal cold water pipe or similar structure. Do not connect directly to the
AC earth. Use 16 AWG or heavier cable and keep the length as short as possible (less
than 50 feet [15 meters]).
For multiple panels always use only a single point ground reference for all panels. Bring
the shields of all reader and communication cables back to one location. Do not connect
them to the panel or the panel‟s housing.
Grounding the Integra32 system
RS-485
Earth
To PC RS-232 Ground
12vdc 12vdc
16vac 16vac
External External
Transformer Transformer
AC Power Source
IRC 2000
Panel 1
Gnd
RX A,B
TX
IRC 2000
Panel 2
A,B
Reader A
Reader A
Reader B
Reader B
Reader B
P
o
w
e
r
S
u
p
p
l
y
P
o
w
e
r
S
u
p
p
l
y

Chapter 2
Intelligent Field Panel
RBH Access Technologies Inc. Integra32™Hardware Guide
5
DIP Switch Settings
The IRC-2000‟s DIP switches control a number of operating parameters including the
device address and serial port baud rate. The controller must be powered down to accept
any changes in the DIP switch settings. Use DIP switches one through five to set the
controller address. Switches six and seven set the communication baud rate, and switch
eight is used to set the connection type (modem or direct).
DIP Switch
DIP Switch
Function
1 - 5
Controller Address
6,7
Controller Baud Rate
8
Modem/Direct PC Connection
Controller Addressing
Use DIP switches 1, 2, 3, 4, and 5 to select the controller address. The address is binary
coded and the switch settings for all sixteen possible addresses are given below.
Controller Addressing
Switch 1
Switch 2
Switch 3
Switch 4
Switch 5
Address
On
Off
Off
Off
Off
1
Off
On
Off
Off
Off
2
On
On
Off
Off
Off
3
Off
Off
On
Off
Off
4
On
Off
On
Off
Off
5
Off
On
On
Off
Off
6
On
On
On
Off
Off
7
Off
Off
Off
On
Off
8
On
Off
Off
On
Off
9
Off
On
Off
On
Off
10
On
On
Off
On
Off
11

Chapter 2
Intelligent Field Panel
Integra32™Hardware Guide RBH Access Technologies Inc.
6
Off
Off
On
On
Off
12
On
Off
On
On
Off
13
Off
On
On
On
Off
14
On
On
On
On
Off
15
Off
Off
Off
Off
On
16
Direct Connect/Modem Selection
DIP switch 8 specifies whether the IRC-2000 is connected directly to a serial port on the
PC or communicates with the PC over a modem. Contact the RBH tech support office
for information on the optional TCP/IP Ethernet connection.
Direct Connect / Modem Selection
DIP Switch 8
Interface Type
OFF
Direct Connect To PC
ON
Modem
DIP switch 8 specifically turns on the password requirement and enables modem call-
back. The panel will still answer a modem call with DIP switch 8 off. You should
initially set up the panel with DIP switch 8 off, program the panel and download to it.
Then turn DIP switch 8 on to enable password checking.
Computer/Modem Port Baud Rate Selection
The controller's serial port baud rate is set with controller DIP switches 6 and 7. This
setting determines the speed used to communicate with the modem or PC serial port. If
the controller is connected directly to the PC, the controller baud rate must be the same
as the baud rate set for the port on the PC. The default PC baud rate is 38,400.
Controller Baud Rate Selection
DIP Switch 6
DIP Switch 7
Baud Rate
OFF
OFF
9,600
ON
OFF
28,800
OFF
ON
38,400
ON
ON
56,000

Chapter 2
Intelligent Field Panel
RBH Access Technologies Inc. Integra32™Hardware Guide
7
PC Connections
RS232 Connection
The PC serial port used to connect to the IRC-2000 panels is assigned under the
Communication Port Setup screen of Network properties window in the Integra32™
software. The baud rate is set by default to 9600 for direct connection to the PC using
the standard RS232 interface. The RS232 interface can be used to connect to a single
controller or to the first controller of a network. The distance between the PC and
controller can not be greater than 150 feet (45 meters), or 30 feet (9 meters) if the baud
rate is increased to 38,400.
For distances greater than 150 feet (45 meters), an RS485 interface must be used. RS485
is built into the IRC-2000 controller but is not part of the standard PC. The PC must be
fitted with either an RS485 serial card or an external RS232 to RS485 serial port
converter.
Additional controllers can be connected via the RS485 terminals.
Controller to PC Connection (RS232)
Controller
DB9 Connector
DB25 Connector
GND
Pin 5
Pin 7
TX
Pin 3
Pin 2
RX
Pin 2
Pin 3
PC to IRC-2000 - RS232 Interface Wiring
Cable Specification
3 or 4-conductor shielded, 18 to 22 AWG
Maximum Cable Length
9600 baud 150 feet (45 meters)
56000 baud 50 feet (15 meters)

Chapter 2
Intelligent Field Panel
Integra32™Hardware Guide RBH Access Technologies Inc.
8
Modem Connection
The IRC-2000 can be connected to the PC via a modem. The modem connection is
similar to the RS-232 connect with the inclusion of the DCD terminal. If multiple
controllers are used then the RS-485 connecter will be needed to connect the additional
controllers to the modem controller.
Cable Specification
4-conductor shielded, 18 to 22 AWG
Maximum Cable Length
9600 baud 150 feet (45 meters)
56000 baud 50 feet (15 meters)

Chapter 2
Intelligent Field Panel
RBH Access Technologies Inc. Integra32™Hardware Guide
9
TCP/IP Connection
For TCP/IP connections, wire to the TCP/IP interface as you would to the PC, with a
direct RS-232 connection. The TCP/IP interface is programmed with an IP address and
connected to the LAN (contact the local system administrator for an IP address).
Additional controllers can be connected via the RS-485 connection terminals.
RS485 Connection
The IRC-2000 controller supports a two-wire RS485 interface. Jumpers JP1 is to be set
on the lower two pins for RS485 operation.
The RS485 interface allows the distance between the controller and the PC to be
extended up to 4000 feet (1200 meters). RS485 requires one twisted pair shielded cable.
Cable Specification
Single twisted three-conductor, shielded, 18 to 22 AWG
Maximum Cable Length
4000 feet (1200 meters)

Chapter 2
Intelligent Field Panel
Integra32™Hardware Guide RBH Access Technologies Inc.
10
Controller Networks
Up to thirty-two controllers can be connected to a single PC. They can be connected to
the same network or distributed across multiple networks. After the first controller of
the network is connected to the PC, additional controllers can be connected to the
network via the RS485 terminals. Connect the TX/A terminal of one controller to the
TX/A terminal next one, and connect the RX/B terminal to the RX/B terminal. All of the
controllers on a network are connected in parallel.
Controller Network Connection Diagram

Chapter 2
Intelligent Field Panel
RBH Access Technologies Inc. Integra32™Hardware Guide
11
Status LED's
Computer/Modem Port
The computer/modem port has two LEDs to show the flow of data between the IRC-2000
controller and PC or modem. The red RX LED (LED3) flashes when the controller
receives data. The green TX LED (LED4) flashes when the controller transmits data. If
the controller is connected directly to the PC, the status LED's flash continuously.
Run LED
The run LED (LED2) flashes to indicate the controller is not communicating, it is on
solid when running normally, and off if power is missing.
Diagnostic LED
This LED (LED1) will be on if either (reader A or reader B) buzzer output is on.
Fuses
There are two 1-amp self-resetting Polyfuses on the IRC-2000 board. F1 is connected to
Reader Power and F2 is connected to Main Power.
Main Power Fuse
Reader Power Fuse

Chapter 2
Intelligent Field Panel
Integra32™Hardware Guide RBH Access Technologies Inc.
12
Jumpers
JP1 The upper position is for RS232, and the lower position is for RS485. (In a
multi-panel network with the first panel connected to the PC via RS-232 and all
other panel connected to the first panel via RS-485, set JP1 of panel #1 to RS-
232 and all other JP1s to RS-485)
JP2 Bias Low –RS485 tuning
JP3 Termination –RS485 tuning
JP4 Bias High –RS485 tuning
Leave jumpers JP2, JP3, and JP4 open. Do
not use these jumpers without consulting RBH.

Chapter 2
Intelligent Field Panel
RBH Access Technologies Inc. Integra32™Hardware Guide
13
URC2000
Connection Details
Power
The URC-2000 requires 9 to 14 volts DC and draws about 200ma.
PC Interface
The PC interface connects the URC-2000 to a PC through an RS485 (2-wire) connection.
Inputs
There are two common terminals for each set of inputs (one between inputs one and two,
another between three and four). Seven different input types are supported (including
normally open, normally closed, one resistor, and two resistor configurations).
Outputs
Two of the four programmable outputs are dry contact relays (UL rated 2A @ 30v dc).
These are designated as outputs one, and three. The other two outputs are solid-state
switches (open collector to ground capable of sinking 100ma).
Readers
Readers are connected to non-programmable outputs BUZ, & LED, as well as data inputs
D0 and D1. Both readers have their own connection terminals, reader A is designated as
P4 and reader B is designated as P5.

Chapter 2
Intelligent Field Panel
Integra32™Hardware Guide RBH Access Technologies Inc.
14

Chapter 2
Intelligent Field Panel
RBH Access Technologies Inc. Integra32™Hardware Guide
15
Earth
The controller contains several layers of protection against induced high voltage
transients from static discharge, lightning, and power line spikes. In order for this
protection to be fully effective, a good connection to earth ground is essential. Wire this
connection to a metal cold water pipe or similar structure. Do not connect directly to the
AC earth. Use 16 AWG or heavier cable and keep the length as short as possible (less
than 50 feet [15 meters]).
For multiple panels always use only a single point ground reference for all panels. Bring
the shields of all reader and communication cables back to one location. Do not connect
them to the panel or the panel‟s housing.
DIP Switch Settings
The URC-2000‟s DIP switches control a number of operating parameters including the
device address and serial port baud rate. The controller must be powered down to accept
any changes in the DIP switch settings. Use DIP switches one through five to set the
controller address. Switches six and seven set the communication baud rate, and switch
eight is used to set the connection type (modem or direct).
DIP Switch
DIP Switch
Function
1 - 5
Controller Address
6,7
Controller Baud Rate
8
not used
Controller Addressing
Use DIP switches 1, 2, 3, 4, and 5 to select the controller address. The address is binary
coded and the switch settings for all sixteen possible addresses are given below.
Controller Addressing
Switch 1
Switch 2
Switch 3
Switch 4
Switch 5
Address
On
Off
Off
Off
Off
1
Off
On
Off
Off
Off
2
On
On
Off
Off
Off
3
Off
Off
On
Off
Off
4

Chapter 2
Intelligent Field Panel
Integra32™Hardware Guide RBH Access Technologies Inc.
16
On
Off
On
Off
Off
5
Off
On
On
Off
Off
6
On
On
On
Off
Off
7
Off
Off
Off
On
Off
8
On
Off
Off
On
Off
9
Off
On
Off
On
Off
10
On
On
Off
On
Off
11
Off
Off
On
On
Off
12
On
Off
On
On
Off
13
Off
On
On
On
Off
14
On
On
On
On
Off
15
Off
Off
Off
Off
On
16
Computer Port Baud Rate Selection
The controller's RS485 port baud rate is set with DIP switches 6 and 7. This setting
determines the speed used to communicate with the PC. All controllers connected to the
software through the same port must have the same baud rate. The default PC baud rate
is 38,400.
Controller Baud Rate Selection
DIP Switch 6
DIP Switch 7
Baud Rate
OFF
OFF
9,600
ON
OFF
28,800
OFF
ON
38,400
ON
ON
56,000
PC Connections
RS485 Connection
The URC-2000 controller supports a two-wire RS485 interface. The RS485 interface
allows the distance between the controller and the PC to be up to 4000 feet (1200
meters). RS485 requires one twisted pair shielded cable.
Other manuals for Integra32
1
Table of contents
Other RBH Access Technologies Controllers manuals
Popular Controllers manuals by other brands

Automationdirect.com
Automationdirect.com DL05 user manual

Agrowtek
Agrowtek MX3i instruction manual

Woodward
Woodward EG-6P Installation and operation manual

National Instruments
National Instruments GPIB-232CT user manual

Bosch
Bosch Rexroth VT-HNC100 3X/S Series operating instructions

GeoVision
GeoVision GV-AS Series installation guide

Pride Mobility
Pride Mobility Microdrive Controller INFMANU2581 Operation instructions

Omron
Omron SYSMAC CJ Series Operation manual

Omega Engineering
Omega Engineering OMG-ULTRACOMM2-PCI RS-232 Start here

Evco
Evco EVFTFT219 installation guide

Bafo
Bafo BF-471 user manual

Hunter
Hunter X2-400 Quick programming guide