RBH Access Technologies UNC100 User manual

1 2 3 4 5 6 7 8
TX RX
A+
FG
B-
Input 1(RTE)
C
Input 2 (DC)
RTE “A”- Request to Exit
DC “A” - Door contact
RTE “B”- Request to Exit
DC “B” - Door contact
Input 3
C
Input 4
Reader B
GRN
BUZ
D0
D1
S
0V
12V
LED (For single LED readers)
Buzzer
Data 0
Data 1
0V, Power, Data Ground
+12VDC
Reader A
LED (For single LED readers)
Buzzer
Data 0
Data 1
0V, Power, Data Ground
+12VDC
GRN
BUZ
D0
D1
S
0V
+12V
1NO 1NC 1C 2OC
Output 1 Lock “A”
Output 2
Output 3 Lock “B”
Output 4
Lock
Lock Power Supply
12-24 VDC
- +
0V IN [email protected] A
+V OUT 12V@500 mA
THIS DOCUMENT IS FOR QUICK REFERENCE ONLY, REFER TO HARDWARE & SOFTWARE MANUALS FOR FULL DETAILS
Panel LEDs Run Trouble Host Comm TX RX
Function Heartbeat Trouble Com to
software
RS-485
transmitting
RS-485
receiving
Off Malfunction Normal No com No com No com
Solid Malfunction Trouble No Com Malfunction Malfunction
Blinking Normal Trouble Red/Green =
Normal
Normal Normal
Panel LEDs
Cycle power for DIP-switch changes to take effect!
Switch 1 2 3 4 5
Panel 1On
Panel 2On
Panel 3On On
Panel 4On
Switch 1 2 3 4 5
Panel 9On On
Panel 10 On On
Panel 11 On On On
Panel 12 On On
Switch 1 2 3 4 5
Panel 13 On On On
Panel 14 On On On
Panel 15 On On On On
Panel 16 On
Switch 1 2 3 4 5
Panel 5On On
Panel 6On On
Panel 7On On On
Panel 8On
Switch 6 7
9.6 K
38.4 K On
57.6K On
115.2 K On On
Switch 8: Always OFF!
DIP SWITCH SETTINGS : DIP-Switch: UP = ON / DOWN = OFF
Lock
Lock Power Supply
12-24 VDC
+ -
Link up to 15 additional
panels via RS-485
Belden 8723 20-22 AWG Twisted,
Shielded Pair. 4,000’ Max
To 12 VDC 7 Ah UL Listed
Rechargeable Battery (REQUIRED)
0VDC @ 2A
+12VDC @ 2A
PS-1224 Power Supply
BAT. TEST
16.5VAC 40Va
16.5VAC 40Va
Press “BAT. TEST” button on
PS-1224 for battery test, Yellow
LED will go ON if test failed
Power Supply (PS-1224) LEDs
LED On Off
Green LED Power On Power Off
Red LED Shorted OK
Yellow LED Battery Fail Battery OK
For Support Call : 01386 425810
All software and hardware manuals are included
on software DVD in “Documents” folder
!
Web site : www.rbhsecuritygroup.com E-mail : support.uk@rbh-access.com
UNC100
Universal Network Controller
with ENCL1 enclosure
and PS-1224 power supply
RUN
TROUBLE
HOST COM
CANADA
ETHERNET
PoE
RS-485
(max 100ma)
LOCK 1
3NO 3NC 3C 4OC(max 100ma)
LOCK 2
Firmware, use Axiom Lite
software to check
firmware version.
Verify it matches your
software, up/downgrade
as needed via firmware
upgrade utility.
REMEMBER TO REMOVE THE PAPER FROM THE BATTERY CONTACT PRIOR TO INSTALLATION
Belden 9538 20-22 AWG
8 core screened for
readers.
Belden 9538 20-22 AWG
8 core screened for
readers.

Output 1 Lock “A”
Output 2 Alarm shunt “A”
Output 3
Output 4
Output 5 Lock “B”
Output 6 Alarm shunt “B”
Output 7
Output 8
1 2 3 4 5 6 7 8
IRC-2000-5
158
JP1
JP2 JP3 JP4
P1 Outputs 1- 4
P2 Outputs 5 - 8
P3 Reader A
P4 Reader B
P5 Inputs 1- 4
P6 Inputs 5 - 8
P7 P8 P9
IRxxxxxxx
LED1 LED2
LED3 LED4
All jumpers off, change
only with tech support!
RS-485 BIAS
RS-232
RS-485
JP1 UP
if connector P7
is USED
JP1 DOWN
if NOT (Default)
Use RS-232 Cable on P7
to connect to a Serial port
on PC or LIF200 Network
Module, 50’ Max.
Verify it matches your
software, up/downgrade
as needed via Firmware
Upgrade Utility
FIRMWARE
Use Axiom Lite
software to check
firmware version
RX TX
See LED function
table below
Board model # Serial #
Panel LEDs LED1 (Red) LED2 (Red) LED3 (Red) LED4 (Green)
FUNCTION Door forced Host Receive Transmit
OFF No Power is off Host not polling Panel not responding
ON SOLID Yes Online Malfunction Malfunction
BLINKING Card read Ofine Receiving Transmitting
Cycle power for DIP-switch changes to take effect!
A+ B- GND
Link up to 16 panels via RS-485
To 12 VDC 7 Ah
Rechargeable Battery
0VDC @ 2A
+12VDC @ 2A
PS-1224 Power Supply
BAT. TEST
Press “BAT. TEST” button on
PS-1224 for battery test, Yellow
LED will go ON if test failed
16.5VAC 40Va
16.5VAC 40Va
+ -
DCD
GND
RX
TX
1
C
2
3
C
4
RTE “A”- Request to Exit
DC “A” - Door contact
RTE “B”- Request to Exit
DC “B” - Door contact
5
C
6
7
C
8
GRN
RED
BUZ
D0
D1
TMP
0V
12V
LED (For single LED readers)
Buzzer
Data 0
Data 1
0V, Power, Data Ground
+12VDC
LED (For single LED readers)
Buzzer
Data 0
Data 1
0V, Power, Data Ground
+12VDC
GRN
RED
BUZ
D0
D1
TMP
0V
12V
N.O.
N.C.
COM
N.O.
N.C.
COM
OC
OC
Lock Power Supply
12-24 VDC
N.O.
N.C.
COM
N.O.
N.C.
COM
OC
OC
20-22 AWG Twisted, Shielded Pair. 4,000’ Max
Relay
Output 1
5A@30V
Relay
Output 2
5A@30V
Relay
Output 5
5A@30V
Relay
Output 6
5A@30V
Switch 1 2 3 4 5
Panel 1On
Panel 2On
Panel 3On On
Panel 4On
Switch 1 2 3 4 5
Panel 9On On
Panel 10 On On
Panel 11 On On On
Panel 12 On On
Switch 1 2 3 4 5
Panel 13 On On On
Panel 14 On On On
Panel 15 On On On On
Panel 16 On
Switch 1 2 3 4 5
Panel 5On On
Panel 6On On
Panel 7On On On
Panel 8On
Switch 6 7
9.6 K
19.2 K On
38.4 K On
56 K On On
Switch 8: Always OFF!
12V 0V
THIS DOCUMENT IS FOR QUICK REFERENCE ONLY, REFER TO HARDWARE & SOFTWARE MANUALS FOR FULL DETAILS
RS-232 to PC or LIF-200
Panel LEDs
Power Supply (PS-1224) LEDs
DIP SWITCH SETTINGS : DIP-Switch: UP = ON / DOWN = OFF
DB9 RBH Cable
Pin 5 - GND Red
Pin 3 - TX Brown
Pin 2 - RX Black
50’ Max Shielded Cable Only
P7 P8
iButton
LED On Off
Green LED Power On Power Off
Red LED Shorted OK
Yellow LED Battery Fail Battery OK
Lock
+
Diode 1N4004
White stripe to +
-
For Support Call : 01386 425810
All software and hardware manuals are included
!on Axiom Lite software CD in “Documents” folder
Web site : www.rbhsecuritygroup.com E-mail : support.uk@rbh-access.com
IRC-2000
Intelligent Reader Controller
with ENCL1 enclosure
and PS-1224 power supply
Lock Power Supply
12-24 VDC
+
-
Lock
Reader Shielding
Refer to hardware manual
Communications Shielding
Refer to hardware manual
Reader Color code
Refer to reader manual
Voltage (Open Collector) Outputs
-12VDC@100mA Max
Voltage (Open Collector) Outputs
Install diodes for rated relays
Belden 9538 cable for Readers Belden 9538 cable for Readers
Belden 8723 cable for data
Belden 9538 cable for readers and Belden 8723 cable for data between panels

Panel LEDs LED1 (Red) LED2 (Green) LED3 (Red)
FUNCTION Receive Transmit Host
OFF Host not polling Panel not responding Power is off
ON SOLID Malfunction Malfunction Online
BLINKING Receiving Transmitting Ofine
Cycle power for DIP-switch changes to take effect!
To 12 VDC 7 Ah
Rechargeable Battery
0VDC @ 2A
+12VDC @ 2A
PS-1224
Power
Supply
BAT. TEST
Press “BAT. TEST” button
on PS-1224 for battery test,
Yellow LED will go ON if
test failed
16.5VAC 40Va
16.5VAC 40Va
Green LED
Buzzer
Data 0
Data 1
0V, Power, Data Ground
+12VDC
Switch 1 2 3 4 5
Panel 1On
Panel 2On
Panel 3On On
Panel 4On
Switch 1 2 3 4 5
Panel 9On On
Panel 10 On On
Panel 11 On On On
Panel 12 On On
Switch 1 2 3 4 5
Panel 13 On On On
Panel 14 On On On
Panel 15 On On On On
Panel 16 On
Switch 1 2 3 4 5
Panel 5On On
Panel 6On On
Panel 7On On On
Panel 8On
Switch 6 7
9.6 K
19.2 K On
38.4 K On
56 K On On
Switch 8: Always OFF!
THIS DOCUMENT IS FOR QUICK REFERENCE ONLY, REFER TO HARDWARE & SOFTWARE MANUALS FOR FULL DETAILS
Panel LEDs
Power Supply (PS-1224) LEDs
DIP SWITCH SETTINGS : DIP-Switch: UP = ON / DOWN = OFF
LED On Off
Green LED Power On Power Off
Red LED Shorted OK
Yellow LED Battery Fail Battery OK
For Support Call : 01386 425810
All software and hardware manuals are included
!on Axiom Lite software CD in “Documents” folder
Web site : www.rbhsecuritygroup.com E-mail : support.uk@rbh-access.com
URC-2002
Universal Reader Controller
with ENCL1 enclosure
and PS-1224 power supply
Communications
Shielding
Refer to hardware
manual
Reader Color code
Refer to reader manual
Output 1 Lock Door “B”
Output 2 (100mA max.)
Output 3 Lock Door “B”
Output 4 (100mA max.)
URC-2000-4
P2 Outputs
URxxxxxxx
LED3LED1 LED2
JP1- RS-485
Termination
JP2
JP3
All jumpers off, change
only with tech support!
RS-485 BIAS
158
FIRMWARE
Use Axiom Lite software
to check firmware
version Verify it matches
your software, up/
downgrade as needed
via Frmware Upgrade
Utility
RX TX
A+
B-
GND
1
C
2
N.O.
N.C.
COM
0V
20-22 AWG
Twisted,
Shielded Pair.
4,000’ Max.
Relay
Output 1
5A@30V
Relay
Output 3
5A@30V
RTE “A”- Request to Exit
DC “A”- Door contact
DIAG
LED
BUZ
D0
D1
A
0V
12V
LED
BUZ
D0
D1
A
0V
12V
N.O.
N.C.
COM
0V
3
C
4
-12V
D+
D-
+12V
P4 Reader A P5 Reader B P7 OutputsP3 Inputs P6 Inputs
RTE “B”- Request to Exit
DC “B”- Door contact
Lock Power
12-24 VDC
+
-
P1
RS485
12v
0v
+
-
P9 Exp. Bus
URC controlers in RBH-URC-2004 get addressed individually, con-
nect via RS-485 on P1 for both panels.
iButton
URC-2000-4
URxxxxxxx
LED3LED1 LED2
RX TX
Serial #
A+
B-
GND
DIAG
-12V
D+
D-
+12V
P1
RS485
12v
0
v
+
-
P9 Exp. Bus
Model #
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
URC-2004 contains 2 URC-2000-4 boards
Link up to 16 panels via RS-485
Add up to 4 ELV8 out-
put boards in Elevator
Control Conguration
(RBH-URC-2008)
See LED function
table below
Lock
Diode 1N4004
White stripe to +
+
-
Lock
Belden 9538 cable for readers and Belden 8723 cable for data between panels
Other manuals for UNC100
1
Other RBH Access Technologies Controllers manuals
Popular Controllers manuals by other brands

Nidec
Nidec Digitax HD M75X Series quick start guide

Pneumatic Division
Pneumatic Division R10 Installation & service instructions

Comnet
Comnet FVT109B Installation and operation manual

Seagull
Seagull REC user manual

echoflex
echoflex EREB-AP installation guide

RF Mogul
RF Mogul EAGLE RE-1 installation guide