
5
Connection to the hot water
heating system provided by
the customer
Before connection to the on-site
heating system, it must be ensured
that the respective unit-specific
output requirements can always be
provided.
■
The water-side unit connection
is to be carried out by the
customer with suitable water
hoses and shut-off valves in the
supply and return flow
■
The finned heat exchangers
are to be carefully bled after
installation is complete
Air pockets in the heat
exchanger cause a reduction in
the heating capacity!
Drainage when at risk
of freezing
Complete static drainage of the
finned heat exchanger is not
possible.
Complete drainage of the finned
heat exchanger is only possible
with compressed air.
Important information for anti-
freeze protection!
With systems that are
decommissioned in rooms at risk of
freezing, the heat exchanger may
never contain water. The residual
water should be blasted out with
compressed air.
If this is not possible, the heating
medium (water) must be mixed
with suitable anti-freeze protection
agent.
Heating medium connection
Before the initial
commissioning
1. Check that the unit has been
installed/assembled correctly.
2. Check that the connection to
the customer's hot water system
has been implemented correctly.
3. Check whether all blower
outlets are open.
4. Establish the power supply to
the switchgear and switch on
the unit with the temperature
controller.
Electrical wiring
■
The units are operated with
230V/50 Hz alternating current
■
The electrical connection is
made using a built-in mains
cable with earthed safety plug
■
Connect the power plug
to a properly installed and
appropriately safeguarded
mains socket
■
All cable extensions must only
be used in fully unreeled or
reeled off condition
Commissioning
NOTE
The electrical connection for
the units must be made at
a separate feed point with
a residual current device in
accordance with VDE 0100,
Section 55.
■
If there is a danger of frost,
the complete system should
be emptied if the heating
medium (water) has not been
mixed with suitable anti-freeze
protection agent
Shutdown
Care and maintenance
In normal operation, the units
are almost maintenance-free.
However, in order to guarantee
continuous fault-free operation,
they should be checked at regular
intervals and cleaned when
necessary.
■
The units should be fully
disconnected (all poles) from
the electrical power supply
and secured to prevent
unauthorised reactivation
Cleaning the units
■
Clean or replace the intake filter
at regular intervals
■
Clean all intake openings and
discharge fins
■
To clean the fan blades, it is
necessary to remove the intake
filter and the protection grid
beforehand
■
Clean the heat exchanger fins
by blowing, with suction or
using a smooth brush
■
Clean severe soiling on the fan
and the aluminium fins with
soap solution
■
Clean the units dry or with
a moistened cloth and some
soap solution if necessary
■
High pressure cleaners or steam
cleaners shall not be used under
any circumstances
■
Never use abrasive or solvent-
based cleaners
Set the temperature control of the
thermostat to the “0” position.
With longer breaks in
operation:
■
Disconnect the unit from the
electrical power supply
■
Shut off or decouple the
heating medium connections
No guarantee claims can be
accepted for frost damage on
the finned heat exchangers!
CAUTION
!