Resol GA1 User manual

RESOL large display GA1 page 1/8
© RESOL 05229 ga1.monen.pmd
Errors and technical changes exepted
• visualisation of system
temperatures, pump
speed and heat amout
volume flow
• 6-digit, seven segment-
LED-display
• simple connection via
RESOL VBus®
• antireflective filterglass
• power supply unit
The RESOL large display GA1 is developed for a simple connection to RESOL
controllers via RESOL VBus®. It is used for visualisation of the data recorded by the
controller, e. g. system temperatures, temporary pump speed, heat amount and volume
flow in the solar system.
For simultaneous presentation of different system characteristics, several large displays
can be directly connected to the RESOL VBus®-data line and mounted into a large
displaymodule table.The display module automatically detects the connected controller;
the selection of the indicated value is effected by DIP-switch.
The application of
highly efficient LEDs
and antireflective filter
glass generates
a highly optical
brilliance and a good
readability even with
bad light conditions
and from a greater
distance.
available versions:
GA1: with a housing
for wall mounting.
GA1N:without
housing for adap-
tation to customer’s
large display module
table..
GA1N
GA1
Technical data
RESOL large display
•Type GA1
plastic/aluminium-housing
Size:
365 x 89 x 44 mm
Protection type:
IP30 / DIN 40050
•Type GA1N
without housing, but filterglass.
Size:
361 x 85 x 15 mm
Protection type:
IP00 / DIN 40050
Display:
numerical seven segment-LED-
display
Segment-size:
45 x 26 mm, 10°-figures inclination
Ambient temperature:
0 ... 40 °C
Power supply:
by an optional 9V-plug-in power
supply
type NG1 (Input: 100 ... 240
V AC)
Power consumption:
max. 4,5 W
Bus-connection:
RESOL VBus®

RESOL large display GA1 page 2/8
© RESOL 05229 ga1.monen.pmd
Large display module board
The combination of several large
displays to a large display
module board is already
prepared: You just need to
connect the display via the
provided cinch-wire!
RESOL GA1
Large display in aluminium
housing
Art: 180 002 90
RESOL GA1 N
Large display without
housing, with filterglass
Art: 180 002 30
GA1N
It is possible to connect up to 8 large displays for
simultaneous presentation of system characteristics as
well as other VBus®-modules via RESOL VBus®.The
Bus wiring is an ordinary bifilar wire (bell wire) and
it can be easily extended.
RESOL NG1
Switched mode mains
power supply
Art: 280 006 60
Adapter-Set
for connection to DeltaSol
Plus
Art: 180 001 20
store temperatur
in °C
volume flow
in l / min
amount of heat
in kWh
collector temperature
in °C
pump speed
in %

RESOL large display GA1 page 3/8
© RESOL 05229 ga1.monen.pmd
Security advice
Please carefully read the manual for mounting and installation before commissionig the large display. In this way damages
to the system can be avoided. Please also note that the installation must be adapted to the conditions provided by the
customer. The installation and operation must be executed according to the approved technical regulations. The
regulations for prevention of industrial accidents of industrial injuries corporations must be observed.The improper use
as well as the incorrect modification of installation and construction result in the exclusion of any kind of liability.
1. Mounting
Mount the housing to a flat wall by means of the provided
drills and dowels. The mounting of the large display
exclusively take place in dry rooms. Please note that the
large display is not faced with electronical radiation to be
sure that there are no operating errors.
1.1 GA1 Drill hole on the back of
the housing for fastening at
the wall.
Power pack connection
Bus-Connection
1.2 GA1 N
For mounting to customized large display module boards
the circuit board needs to be drilled to the mounting plate
with a minimum distance of 10mm and the aid of the drill
holes. The provided antireflective filterglass has to be
installed positively to the plate.
Power pack connection
Bus-Connection
Note:
The choice of the shown system characteristic is effected
by a DIP-switch, which is located on the circuit board.

RESOL large display GA1 page 4/8
© RESOL 05229 ga1.monen.pmd
2. Commissioning
2.1.1 Connection to DD
DD
DeltaSeltaS
eltaSeltaS
eltaSolol
olol
ol®®
®®
®PP
PP
Prr
rr
roo
oo
o
The controller RESOL DeltaSol Pro offers the possibility to
transmit data via RESOLVBus® (terminals 7 and 8). Several
RESOLVBus® modules e.g. large displays can be connected
via the data-bus.
The connecting cable has to be connected to the bus
terminals of the controller with the screened endings.
Pay attention to the polarity!
The cable is included in delivery. Connect the chinch-plug
of the cable to the upper or lower (parallel connection)
cinch-connector of the large display.
RESOL VBus® (clamp 7 and 8)
VBus®
connection
Cinch-plug
2.1.2 Connection to MidiPMidiP
MidiPMidiP
MidiPrr
rr
roo
oo
o and
RESOL DeltaSolDeltaSol
DeltaSolDeltaSol
DeltaSol®®
®®
® MM
MM
M
VBus® connection
Midi Pro: Please connect the line with insulated ends and
any polarity (included in delivery) to the terminals marked
"Bus" and CON601.
DeltaSol M / ES: Please connect the line with insulated
ends and any polarity (included in delivery) to the termi-
nals marked "Bus" and "VBus®".You can also connect the
GA3 by RS232 interface (see 2.1.3. connection to RESOL
controllers by interface-set)
Connection to GA3:
The chinch-plug of the line with the upper or lower chinch-
bush (parallel switching) of the GA3 must be connected.
MidiPMidiP
MidiPMidiP
MidiPrr
rr
roo
oo
oDeltaSolDeltaSol
DeltaSolDeltaSol
DeltaSol®®
®®
® M/ESM/ES
M/ESM/ES
M/ES
VBus® connection
RS232 connection
2.1 Connection

RESOL large display GA1 page 5/8
© RESOL 05229 ga1.monen.pmd
2.1.3 Connection to the RESOL DeltaSolDeltaSol
DeltaSolDeltaSol
DeltaSol®®
®®
®PlusPlus
PlusPlus
Plus
2.1.4 Connection to the RESOL WMZ-M1
The controller RESOL DeltaSol Plus is equipped with a
RS232 interface for connection to other modules. The
connection between the controller and the large display is
made by an optional interface-set*. The connection needs
to be placed according to the drawing.
*Interface-Adapter-Set to conncet the large display
to the RESOL DeltaSol Plus
Art: 180 001 20
connector of modular plug, RS232 (housing-top)
modular-plug
Sub D 25-pin
interface-adapter
power supply unit-adapter
Cinch-plug Cinch-plug
switch mode power
supply
VBus®-connection
The caliometer module RESOL WMZ-M1 possesses a
RESOL VBus® connection (clamps 3 and 4) to transfer
datas. How to connect the large display to the controller is
defined in 2.1.1 .
Note:
If you use the WMZ-M1 as a single device, you would
need to adjust the module’s channel S to value:“1“ (for an
independent checking of system values) and addiotionally
the channel I to value: “0“ (cp. the manual RESOL WMZ-
M1). If the calorimeter is connected via the RESOL VBus®
to a superior RESOL controller, the channel S would be
needed to be adjusted to the value “0“ as well as the
channel I.
Adapter-Set
Interface-Adapter-Set to
connect the large display to
the RESOL DeltaSol Plus
Art: 180 001 20

RESOL large display GA1 page 6/8
© RESOL 05229 ga1.monen.pmd
on
1234
on
5 6 7 8
Displayed value 1 23 4 5 6 7 8
Sensor 1 x x x
Sensor 2 x x x
Sensor 3 x x x
Rotation speed relay 1 x x x
Rotation speed relay 2 x x x
Displayed value 1 23 45 6 7 8
Sensor 1 x x x
Sensor 2 x x x
Sensor 3 x x x
Sensor 4 x x x
Sensor 5 x x x
Rotation speed relay 1 x x x
Rotation speed relay 2 x x x
Volume flow (l/h) x x x
Heat quantity Wh x x x
Heat quantity kWh x x x
Heat quantity MWh x x x
System time x x x
Displayed value 1 2 3 45 6 7 8
Sensor feed flow
x x
Sensor return flow
x x
Volume flow (l/h)
x x
Heat quantity Wh
x x
Heat quantity kWh
x x
Heat quantity MWh x x
DeltaSol Pro
DeltaSol Plus
WMZ-M1
1.Depending on the local conditions, the brightness of the
display segments must be adjusted by means of the
potentiometer.
2. DIP-switches 1 … 4 are to be adjusted as per required
values and superior controller or module (please see
enclosed schedule).
3.DIP-switch 7 is to be adjusted for right-justified (= off)
or left-justified (= on) value indication with less than 6
numbers.
4.DIP-switch 8 is to be adjusted for a 4-or 6-digit value
indication:
off = 4-digit indication
on = 6-digit indication
5. DIP-switch 5 is to be adjusted for utilization of a RESOL
WMZ-M1:
off = no WMZ-M1 is connected to the data bus line
on = WMZ-M1 is connected to data bus line
Please note:
The DIP-switch 6 is used for control purpose, please don´t
change the adjustment made by RESOL.
Dip-switch 6 = off
2.3 Dip switches
socket for power supply
brighness potentiometer net-LED
DIP switches
bus connections
2.2 Adjustments

RESOL large display GA1 page 7/8
© RESOL 05229 ga1.monen.pmd
Displayed value 1 2 34 5678
Sensor 1 x x x
Sensor 2 x x x
Sensor 3 x x x
Sensor 4 x x x
Sensor 5 x x x
Sensor 6 x x x
CS10 (W/m²) x x x
Rotation speed Relais 1 x x x
Rotation speed Relais 2 x x x
Rotation speed Relais 3 x x x
System time x x x
Displayed value 1 2 3 4 5 6 7 8
Sensor 1 x x
Sensor 2 x x
Sensor 3 x x
Sensor 4 x x
Sensor 5 x x
Sensor 6 x x
Sensor 7 x x
Sensor 8 x x
Volume flow (l/h) x x
CS10 (W/m²) x x
Rotation speed relay 1 x x
Rotation speed relay 2 x x
Rotation speed relay 3 x x
System time x x
Hours of operation relay 1 x x
Hours of operation relay 2 x x
Hours of operation relay 3 x x
Hours of operation relay 4 x x
Hours of operation relay 5 x x
Hours of operation relay 6 x x
Heat quantity Wh
x x
Heat quantity kWh (from DeltaSol ES v1.1) x x
Heat quantity MWh (from DeltaSol ES v1.1)
x x
Anzeigewert 1 2 34 5 6 7 8
Sensor 1 x x x
Sensor 2 x x x
Sensor 3 x x x
Sensor 4 x x x
Sensor 5 x x x
Sensor 6 x x x
Sensor 7 x x x
Sensor 8 x x x
Sensor 9 x x x
Sensor 10 x x x
Sensor 11 x x x
Sensor 12 x x x
Rotation speed relay 1 x x x
Rotation speed relay 2 x x x
Rotation speed relay 3 x x x
Displayed value 1 2 34 5 6 7 8
Sensor 1 x x x
Sensor 2 x x x
Sensor 3 x x x
Rotation speed 1 x x x
Displayed value 1 2 34 5 6 7 8
Sensor 1 xx x
Sensor 2 xx x
Sensor 3 xx x
Rotation speed xx x
Displayed value 1 2 3 4 5 6 7 8
Sensor 1 x x
Sensor 2 x x
Sensor 3 x x
Sensor 4 x x
System time x x
Rotation speed relay 1 x x
Rotation speed relay 2 x x
Heat quantity Wh x x
Heat quantity kWh x x
Heat quantity MWh x x
DeltaSol B
DeltaSol BS DeltaSol BS Plus
DeltaSol M
Midi Pro DeltaSol ES

RESOL large display GA1 page 8/8
© RESOL 05229 ga1.monen.pmd
Displayed value 1 2 34 5 6 7 8
Sensor 1 x x
Sensor 2 x x
Sensor 3 x x
Sensor 4 x x
Sensor 5 x x
Sensor 6 x x
Sensor 7 x x
Volume flow (l/h) x x
CS10 (W/m²) x x
System time x x
Rotation speed relay 1 x x
Rotation speed relay 2 x x
Rotation speed relay 3 x x
Rotation speed relay 4 x x
Rotation speed relay 5 x x
Displayed value 1 2 34 5 6 7 8
Sensor 1 x x x
Sensor 2 x x x
Sensor 3 x x x
Sensor 4 x x x
Rotation speed relay 1 x x x
EL2 / EL3
Solex Friwa
Your wholesaler:
Notes
Design and specifications are subject to change without notice.
Illustrations may differ slightly from production models.
Displayed value 1 2 3 4 5 6 7 8
Sensor 1 x x
Sensor 2 x x
Sensor 3 x x
Sensor 4 x x
Sensor 5 x x
Sensor 6 x x
Sensor 7 x x
Volume flow (l/h) x x
System time x x
Rotation speed relay 1 x x
Rotation speed relay 2 x x
Heat quantity Wh x x
Heat quantity kWh x x
Heat quantity MWh x x
RESOL - Elektronische Regelungen GmbH
Heiskampstraße 10
D - 45527 Hattingen
Tel.: +49 (0) 23 24 / 96 48 - 0
Fax: +49 (0) 23 24 / 96 48 - 55
www.resol.de