Riello MultiCOM 392 User manual



3
INTRODUCTION
Thank you for choosing our product.
The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent
performance.
This manual contains detailed instructions on how to install and use the product.
This manual must be stored in a safe place and CONSULTED BEFORE USING THE DEVICEfor proper usage instructions
as well as maximum performance from the device itself.
NOTE: Some images contained in this document are for informational purposes only and may not faithfully demonstratethe parts
of the product they represent.
Symbols used in this manual:
Danger
Indicates the possible presence of dangerous voltages and the risk of electric shock.
Warning
Indicates important information that must not be ignored.
Information
Provides notes and useful suggestions for the User.
SAFETY
This part of the manual contains SAFETY precautions that must be followed scrupulously.
Ensure that the connectors subjected to high voltages are correctly isolated.
❖The device has been designed for professional use and is therefore not suitable for use in the home.
❖The device has been designed to operate only in closed environments. It should be installed in rooms where there are
no inflammable liquids, gas or other harmful substances.
❖Take care that no water or liquids and/or foreign bodies fall into the device.
❖In the event of a fault and/or impaired operationofthe device, do not attempt to repair it but contactthe authorized service
centre.
❖The device must be used exclusively for the purpose for which it was designed. Any other use is to be considered
improper and as such dangerous. The manufacturer declines all responsibility for damage caused by improper, wrong
and unreasonable use.

4
ENVIRONMENTAL PROTECTION
Our company devotes abundant resources to analysing environmental aspects in the development of its products. All our products
pursue the objectives defined in the environmentalmanagement system developed by the companyin compliance with applicable
standards.
Hazardous materials such as CFCs, HCFCs or asbestos have not been used in this product.
When evaluating packaging, the choice of material has been made favouring recyclable materials.
Please separate the different material of which the packaging is made and dispose of all material in compliance with applicable
standards in the country in which the product is used.
DISPOSING OF THE PRODUCT
The device contains internal material which (in case of dismantling/disposal) are considered TOXIC, such as electronic circuit
boards. Treat these materials according to the laws in force, contacting qualified centres. Proper disposal contributes to respect
for the environment and human health.
©The reproduction of any part of this manual, even in part, is prohibited unless authorised by the manufacturer.
The manufacturer reserves the right to change the product described at any time without prior notice for improvement purposes.

5
CONTENTS
DESCRIPTION 7
INPUTS 8
OUTPUTS 8
SERIES MST / MSM / MCT / MCM 9
JUMPER SETTINGS ON INTERFACE BOARD OF THE UPS 9
SAFETY TESTS 11
JUMPER SETTINGS AND INSTALLATION OF THE MULTICOM 392 12
CONFIGURATION 14
SERIES C1T / C1M 16
JUMPER SETTINGS AND INSTALLATION 16
CONFIGURATION 18
SERIES GMI 20
JUMPER SETTINGS AND INSTALLATION 20
CONFIGURATION 22
SERIES S3T / S3M / S3U 24
JUMPER SETTINGS AND INSTALLATION 24
CONFIGURATION 26
SERIES MPW / MPX 30
JUMPER SETTINGS AND INSTALLATION 30
CONFIGURATION 32

6

7
DESCRIPTION
MultiCOM 392 is a device that, inserted in the proper slot of the UPS, provides 8 configurable dry contact outputs and up to four
inputs for the control and monitoring of the UPS.
The device is compatible with the following UPS series:
•MST / MSM / MCT / MCM
•C1T / C1M
•GMI
•S3T / S3M / S3U
•MPW
Refer to the code on the UPS data plate to trace back to the UPS model you own (ex. P/N: DS3TK10...).

8
INPUTS
The four inputs, IN1 / IN2 / IN3 / SWMB, can be configurable or not according to different UPS series. Check the features that are
compatible and the default configuration in the chapter dedicated to your UPS model.
Some UPS may not handle all inputs.
OUTPUTS
For all UPS series, each of the eight outputs (OUT1 –OUT8) can be associated with an event such as an operating state or a
UPS alarm condition. You can also configure the function logic of the relay and set a delay for the event signalling.
The outputs can be configured via the configuration software of the UPS.
Check the default configuration of the outputs in the chapter dedicated to your UPS model.
In order to know the events that can be associated with the outputs, refer to the configuration software of the UPS.
Maximum ratings for each output
Maximun load current
1 A
Maximun voltage AC
25 Vac
Maximun voltage DC
30 Vdc

- MST / MSM / MCT / MCM -
9
SERIES MST / MSM / MCT / MCM
For series MST / MSM / MCT / MCM, MultiCOM 392 is compatible only if the UPS is provided with the interface
board mounted B0056 Rev.01C / B0056 Rev.02C or higher.
JUMPER SETTINGS ON INTERFACE BOARD OF THE UPS
CAUTION
ALL OPERATIONS DESCRIBED IN THIS CHAPTER MUST
ONLY BE CARRIED OUT BY PERSONNEL WHO ARE
QUALIFIED AND PROPERLY TRAINED
All the operations listed below must be carried out while the UPS is completely disconnected from the mains and
from the batteries and with all disconnectors and fuse holders open.
Refer to the relative user manual to turn off the UPS. Then wait about 15 minutes to allow the internal capacitors to
discharge.
•Remove the top UPS panel in order to access to the interface board of the UPS.
•Set the jumpers JP3 and JP4 of the interface board referring to the following table and image.
•Replace the top panel of the UPS.
•Perform the safety tests (see following pages).

- MST / MSM / MCT / MCM -
10
JP1
OPEN
JP2
OPEN
JP3
CLOSED (DEFAULT) for using the REMOTE OFF function through the AS400 port of the UPS
OPEN for using the REMOTE OFF function through IN2 of the MultiCOM 392
JP4
OPEN
JP6
CLOSED

- MST / MSM / MCT / MCM -
11
SAFETY TESTS
CAUTION
ALL OPERATIONS DESCRIBED IN THIS CHAPTER MUST
ONLY BE CARRIED OUT BY PERSONNEL WHO ARE
QUALIFIED AND PROPERLY TRAINED
The tests described below should be performed after the UPS is completely closed with the wrapping and all the panels. In
addition, all operations must be carried out with the UPS off and completely disconnected from themains, batteries and any other
equipment.
▪Equipment required
1. Earth resistance meter, fitted with RS28 ELEKTROTECHN Laboratorium electrodes (or similar).
2. UH28 .. ELEKTROTECHN LABORATORIUM strength test instrument complete with high voltage rectifier BRIDGE
adapter (or similar).
▪Measurement of contact resistance to earth (CRITICAL FOR SAFETY)
Connect one electrode from the “RS 28” generator to the earth terminal. Inject the test current through the other electrode
(tip) in all the different parts that make up the metal frame. In the test on painted frames, before the test, pierce the painted
layer with the tip.
The test is passed if all the metal parts of the equipment are earthed.
The earth resistance reading on the instrument should be 0.1 Ohm.
▪Strength test (CRITICAL FOR SAFETY)
With theUPS off and disconnected from themains, batteries and any other equipment, short circuit themainsinput terminals
(L1, L2, L3, N) (and bypass input terminals if present).
Close all the disconnectors SWIN, SWOUT, SWBATT (if present on the UPS), and SWMB and SWBYP (if present). With
the machine for the strength test and relative rectifier bridge, set at 1500Vac with a 10mA limit, apply a voltage of about
2100Vdc for at least 2 seconds between the short circuit created beforehand and an earth terminal.
The test is passed if the test equipment gives no indication of an anomaly.
Remove the short circuit between the phases and the neutral. Open all the disconnectors.

- MST / MSM / MCT / MCM -
12
JUMPER SETTINGS AND INSTALLATION OF THE MULTICOM 392
Set the jumper of the MultiCOM 392 referring to the following table and image.
JP1
OPEN (DEFAULT) for using the REMOTE OFF function through the AS400 port of the UPS
CLOSED for using the REMOTE OFF function through IN2 of the MultiCOM 392
JP2
OPEN
JP3
OPEN
JP4
OPEN
JP5
OPEN

- MST / MSM / MCT / MCM -
13
MultiCOM 392 must be inserted only in the UPS slot dedicated to the contacts boards: “AUX RELAY SLOT”.
▪Remove the cover of the UPS slot dedicated to the contacts boards (AUX RELAY SLOT) by removing the two retaining
screws.
▪Wire appropriately MultiCOM 392.
▪Insert MultiCOM 392 in the slot dedicated to the contacts card (AUX RELAY SLOT).
▪Fix the cover provided with the MultiCOM 392 using the screws previously removed.

- MST / MSM / MCT / MCM -
14
CONFIGURATION
MultiCOM 392 can be configured using the configuration software of the UPS.
Before setting the input/output, you must select “Multicom 392 [8out]” for I/O card model.
INPUT
DESCRIPTION
IN1
REMOTE ON: By closing the contact for at least 3 seconds, the UPS will switch on.
IN2
REMOTE OFF: By closing the contact, the UPS will immediately switch off.
This feature is disabled by default. To use it you must disable the corresponding feature
available on the AS400 port of the UPS (see “Jumper settings on interface board of the UPS”
and “Jumper settings and installation of the MultiCOM 392”).
IN3
CONFIGURABLE INPUT: use the UPS configuration software to select the function that has to be
associated with IN3 (Input 3 mode default: Load on bypass).
SWMB
Manual bypass auxiliary contact (for the management of an auxiliary contact of a possible remote
bypass). The auxiliary contact must be anticipated type, normally open.
The transition takes place regardless of the status of the bypass line and of the bypass/inverter
sync.
The inputs IN1 / IN2 / IN3 have to be used as alternative to the corresponding inputs on the AS400 port of the UPS.

- MST / MSM / MCT / MCM -
15
For each of the eight outputs can be selected: the associated event (Output mode), the operating logic of the relay
(Logic) and a delay (in seconds) in reporting the event.
OUTPUT CONTACTS DEFAULT CONFIGURATION
Output
Output mode
Logic
Delay (s)
OUT 1
Battery low
Normal OFF
0
OUT 2
Battery working
Normal OFF
0
OUT 3
Inverter locked
Normal OFF
0
OUT 4
Load on bypass
Normal OFF
0
OUT 5
UPS OK
Normal OFF
0
OUT 6
Battery fail
Normal OFF
0
OUT 7
Overload
Normal OFF
0
OUT 8
Any alarm
Normal OFF
0
EXAMPLE 1 - if you set an output in this way:
Output mode
Logic
Delay (s)
Battery working
Normal OFF
0
the relative contact will be:
UPS working by mains
UPS in battery working mode
EXAMPLE 2 - if you set an output in this way:
Output mode
Logic
Delay (s)
Battery working
Normal ON
10
the relative contact will be:
UPS working by mains
UPS in battery working mode for at least 10 seconds

- C1T / C1M -
16
SERIES C1T / C1M
JUMPER SETTINGS AND INSTALLATION
Set the jumpers of the MultiCOM 392 referring to the following table and image.
JP1
CLOSED
JP2
OPEN
JP3
OPEN
JP4
OPEN
JP5
OPEN

- C1T / C1M -
17
MultiCOM 392 must be inserted only in the CSS slot dedicated to the contacts boards: “AUX RELAY SLOT”.
▪Remove the cover of the CSS slot dedicated to the contacts boards (AUX RELAY SLOT) by removing the two retaining
screws.
▪Wire appropriately MultiCOM 392.
▪Insert MultiCOM 392 in the slot dedicated to the contacts card (AUX RELAY SLOT).
▪Fix the cover provided with the MultiCOM 392 using the screws previously removed.

- C1T / C1M -
18
CONFIGURATION
MultiCOM 392 can be configured using the configuration software of the CSS.
Before setting the input/output, you must select “Multicom 392 [8out]” for I/O card model.
INPUT
DESCRIPTION
IN1
REMOTE ON: By closing the contact for at least 3 seconds, the UPS will switch on.
IN2
REMOTE OFF: By closing the contact, the UPS will immediately switch off.
IN3
CONFIGURABLE INPUT: use the UPS configuration software to select the function that has to be
associated with IN3 (Input 3 mode default: Load on bypass).
SWMB
Manual bypass auxiliary contact (for the management of an auxiliary contact of a possible remote
bypass). The auxiliary contact must be anticipated type, normally open.
The transition takes place regardless of the status of the bypass line and of the bypass/inverter
sync.
The inputs IN1 / IN2 / IN3 have to be used as alternative to the corresponding inputs on the AS400 port of the UPS.

- C1T / C1M -
19
For each of the eight outputs can be selected: the associated event (Output mode), the operating logic of the relay
(Logic) and a delay (in seconds) in reporting the event.
OUTPUT CONTACTS DEFAULT CONFIGURATION
Output
Output mode
Logic
Delay (s)
OUT 1
Battery low
Normal OFF
0
OUT 2
Battery working
Normal OFF
0
OUT 3
Inverter locked
Normal OFF
0
OUT 4
Load on bypass
Normal OFF
0
OUT 5
UPS OK
Normal OFF
0
OUT 6
Battery fail
Normal OFF
0
OUT 7
Overload
Normal OFF
0
OUT 8
Any alarm
Normal OFF
0
EXAMPLE 1 - if you set an output in this way:
Output mode
Logic
Delay (s)
Battery working
Normal OFF
0
the relative contact will be:
UPS working by mains
UPS in battery working mode
EXAMPLE 2 - if you set an output in this way:
Output mode
Logic
Delay (s)
Battery working
Normal ON
10
the relative contact will be:
UPS working by mains
UPS in battery working mode for at least 10 seconds

- GMI -
20
SERIES GMI
JUMPER SETTINGS AND INSTALLATION
Set the jumpers of the MultiCOM 392 referring to the following table and image.
JP1
OPEN
JP2
OPEN
JP3
OPEN
JP4
OPEN
JP5
OPEN
This manual suits for next models
4
Table of contents
Popular Computer Hardware manuals by other brands

Conrad
Conrad 97 19 46 operating instructions

Delta Electronics
Delta Electronics Suppression Inductors CKI24H Specification sheet

ekwb
ekwb EK-FB GA AMD KIT INSTALLATION AND MOUNTING MANUAL

Telit Wireless Solutions
Telit Wireless Solutions EVK2 user guide

NEC
NEC N8141-75F user guide

Intel
Intel 80C186EA Preliminary information