Salicru CS141 Instruction manual

Manuel d’installation rapide
Quickstart Manual
Kurzanleitung
Manuale di avvio rapido
Manual rápido
CS141 Quick start manual
ES
EN
FR
DE
IT

Descripción Función
1 Puerto COM1 Interfaz serie para conectar el SAI u otro dispositivo mediante el cable original RS-232
2 Puerto COM2
Para conectar otros dispositivos tales como (Modem GSM, sensor de temperatura y humedad,
SENSORMANAGER_II , dispositivos Fieldbus (MODBUS RS232, Profibus, LONbus, etc.)
Disponible en los CS141 CS141L, CS141SC = RS232, CS141LM, CS141SCM = RS485
No disponible en los CS141BL, CS141_BSC
3 Puerto RJ45 LAN Interfaz Ethernet 10/100 Mbit con LED de estado integrados
(LED verde: conexión establecida con la red , LED amarillo: tráfico de red).
4 Entrada DC Dispositivo externo: alimentado por un adaptador de 12V (se suministra con el equipo)
Dispositivo interno: alimentado a través del slot del equipo
5 AUX Disponible en los dipositivos CS141L, CS141LM, CS141SC y CS141SCM para conectar con
CON_R_AUX4 y BACS etc.
6 LEDs de estado
(rojo / verde)
Estado de funcionamiento LED
Descomprimiendo el sistema operativo (proceso de actualización) Rojo intermitente
Error durante la descompresión del sistema operativo Rojo intermitente
rápido
Proceso de inicio del sistema operativo rojo permanente
Comunicación perdida con el equipo externo (por ejemplo SAI) rojo y verde
Funcionamiento normal – conexión establecida con el equipo externo verde intermitente
7 Micro-interruptor
DIP Switch
Para intercambiar entre las diferentes opciones de inicio:
Micro-interruptor en posición central / 1+2 en posición OFF: Para ajus-
tar el CS141 en modo configuración y activar la dirección IP por defecto
a 10.10.10.10 después de un reinicio .
Micro-interruptor en posición derecha / 1 en posición OFF, 2 en posi-
ción ON:
Modo DHCP, la IP está configurada por el servidor DHCP. Comprueba
la dirección MAC de su dispositivo para identificar su dispositivo en la
red
Micro-interruptor en posición izquierda / 1 en posición ON, 2 en posi-
ción OFF: Se utilizan los ajustes de red del interfaz HTTP, también es
posible configurar el modo DHCP .
8 USB
5
3267
1
84
CS141SC CS141L CS141MINI
5
32672
36
7
Versión
slot Versión
caja
CS141 GESTIÓN SNMP / WEB / MODBUS
Version: 2019-01-16
ES

Procedimiento 1
1. Desplace el micro-interruptor a la posición central
y los 1 y 2 a la posición OFF.
2. Conecte el puerto LAN del CS141 directamente a
un PC con un cable cruzado Ethernet.
Configuración recomendada:
Se recomienda configurar el PC y la puerta de enlace
en el mismo segmento de red, por ejemplo
10.10.10.11 y 10.10.10.11 respectivamente.
Procedimiento 2
1. Desplace el micro-interruptor a la posición central
y los 1 y 2 a la posición OFF.
2. Mediante dos cables de red conecte el PC y el
puerto LAN del dispositivo a un Switch o Hub
(concentrador).
Versión caja
Conecte el SAI con el cable original del SAI al puerto
COM1 del CS141.
Versión slot
Insertar el dispositivo en el slot del SAI.
Para su instalación en el SAI, consulte el manual de
usuario del CD de documentación o bien descárguelo
de la página web del fabricante de SAIs.
Todas las funciones del SAI y la utilización de los
eventos flexibles, etc…están descritos en el ma-
nual de usuario del CS141!
2. Conecte el dispositivo al SAI
IP 10.10.10.10
Micro-interruptor 1 + 2 = off
Micro-interruptor pos. "central"
IP: 10.10.10.11
Subnet: 255.255.255
Gateway: 10.10.10.11
Ethernet
cross
cable
Ethernet
cables IP: <Your IP Address>
Gateway: <Your Gateway>
IP 10.10.10.10
Micro-interruptor 1 + 2 = off
Micro-inerruptor pos. "central"
Hub/Switch
Alimentación eléctrica
3. Conecte la alimentación del CS141
Versión caja
Conecte el adaptador de alimentación suministrado al
CS141.
Versión slot
Los dispositivos versión tarjeta se alimentan a través
del slot del equipo. Siempre es posible insertar y
quitar el CS141 del SAI sin dañarlo. Para cortar la
alimentación, quite el dispositivo del slot e insértelo
de nuevo.
Instalación e integración del CS141 en la red
1. Activación del modo de configuración

4.1. Añada la ruta de la dirección IP estándar a su PC
1. Abra el "Símbolo del sistema" o bien
2. Ejecute "cmd.exe"
3. Introduzca el siguiente comando:
"Route add 10.10.10.10 <dirección IP local>"
(por ejemplo: "route add 10.10.10.10
192.168.222.54")
4. Ejecute el comando "ping 10.10.10.10" para com-
probar si el dispositivo está accesible.
Consejo: El CS141 necesita unos 30 segundos para
iniciar el servidor web. Cuando el servidor web funci-
ona, el LED cambia de rojo (inicio) a verde y empieza
a parpadear.
4.2. Búsqueda automática con la herramienta “Netfinder "
El siguiente vínculo nos lleva al software “Netfinder”
el cual buscará automáticamente su dispositivo en la
red :
http://www.generex.de/generex/download/software/
install/NetFinder.zip
1. Inicie el navegador Web
2. Introduzca la dirección http://10.10.10.10
3. Para el inicio de sesión, introduzca:
nombre de usuario "admin"
contraseña por defecto "cs141-snmp"
5. Acceso mediante conexión HTTP y nombre de usuario
4. Acceso al CS141 a través de la red
6. Seleccione su idioma
1. Seleccione la opción
- Sistema
- General
en el menú desplegable de la izquierda.
2. Seleccione el idioma deseado.
ES

1. Seleccione la opción
- Sistema
- Red
en el menú desplegable de la izquierda.
2. Introduzca los valores de
- Dirección IP
- Máscara de subred
- Puerta de enlace predeterminada
("Servidor DNS ", si se desea)
3. Haga clic en el botón "Aplica“ para guardar los
cambios.
4. Seleccione la opción
- Sistema
- Fecha & Hora
en el menú desplegable.
5. Introduzca la „dirección IP“ de su servidor de ho-
rario y sincronice el CS141 con dicho servidor.
La configuración del servidor de horario es importan-
te para el registro de alarmas y eventos (En el caso
que no se configurase ningún servidor de horario, la
hora se configurará a 01/01/2000 00:00)
6. Los cambios realizados en cada página de confi-
guración tienen que ser guardados haciendo clic en
el botón "Aplica".
7. Escoja la opción
- Dispositivos
- SAI
- Configuración
en el menú desplegable de la configuración de SAI.
8. Escoja el “modelo de SAI” al que el CS141 estará
conectado.
9. Haga clic en el botón "Aplica“ para guardar los
cambios.
Para más información sobre la configuración del SAI
consulte el manual de usuario del CS141.
7. Configuración de la dirección IP del CS141 . Ajustes básicos de red

Conecte el puerto LAN del dispositivo a la red medi-
ante un cable de red RJ45 (no incluido).
El CS141 se encuentra en la dirección IP
10.10.10.10!
1. Para cambiar el modo de trabajo ponga el micro-
interruptor en la posición izquierda y el 1 en la posi-
ción ON.
2. Para reiniciar corte la alimentación del CS141.
3. Conecte el CS141 a la alimentación de nuevo. El
CS141 se encuentra en la dirección IP configurada
(en la dirección IP 10.10.10.10 ya no estará disponib-
le)
10. Envío del comando de apagado a los PCs en la red informática
Para apagar un PC en caso de un fallo de red, es
necesario instalar un cliente RCCMD en él. Adicio-
nalment algunas configuraciones en la gestión de
eventos del adaptador deben ser realizadas.
Instalación del cliente RCCMD
1. Descargue el archivo de instalación del CD de
documentación del SAI o desde internet.
2. Cada instalación RCCMD requiere una clave de
licencia individual. En algunos productos, se incluye
una clave de licencia. En caso de precisar licencias
extras están disponibles en su proveedor.
http://www.salicru.com
Network
8. Conecte el CS141 con la red informática
9. Cambie el modo de funcionamiento
3. En el primer menú, se tiene que introducir la di-
rección IP del adaptador de cuyas señales de apaga-
do deben recibir. Confirme la siguiente configuración
por defecto. El archivo de apagado se encuentra en
la última ventana. Para la edición de la secuencia de
apagado del cliente, haga clic en el botón
"Configuración" (También es posible editar el archivo
“batch“ para cambiar o agregar eventos) la instala-
ción finaliza cuando se haga clic en "instalar" y el
servicio se iniciará.
Alimentación
eléctrica
ES

1. Escoja la opción
- Dispositivos
- SAI
- Eventos
en el menú desplegable.
2. Haga clic en el botón "+" al lado del evento "Fallo
de red".
3. Se inicia el Editor de Trabajos. Escoja la opción
„RCCMD shutdown“ en el menú.
4. Introduzca la „dirección IP“ de su cliente (El pu-
erto de escucha habitualmente es el 6003). En la
parte derecha se puede especificar cuando la señal
de apagado va a ser ejecutada, por ejemplo “At 240
seconds remaining time“.
5. Haga clic en el botón "Aplica“.
6. Por razones de seguridad se recomienda hacer
las mismas entradas de apagado RCCMD en "Fallo
de red" y para el Evento de "baja batería" - pero aquí
sin ningún retraso para evitar que la caída del ser-
vidor debido a la alarma de batería baja!
El CS141 dispone de una gran variedad de sensores
ambientales y otros dispositivos de medición combi-
nados, como la temperatura, la humedad, el fuego y
humo, movimiento e intrusión, presión, niveles, etc,
para ser monitorizados.
Además, hay disponibles otros componentes tales
como diversos soportes de montaje, Conversor
BACnet, Conversor PROFIBUS etc. Por favor, preg-
unte a su fabricante / proveedor de SAI para obtener
información más detallada sobre las opciones dispo-
nibles.
11. Configuración de eventos para el CS141
12. Opciones del CS141

Description Function
1 COM1 Port Serial Interface to connect an UPS or another device with a original RS232 cable
2 COM2 Port
To connect additional devices for example (GSM Modem, temperature and humidity sensor,
SENSORMANAGER_II, Fieldbus devices (MODBUS RS232, Profibus, LONBus, etc.).
Available at CS141L, CS141SC, CS141MINI & CS141R_2 = RS232
Available at CS141LM & CS141SCM =RS485
(not equipped CS141BL, CS141BSC)
3 LAN Port RJ 45 Ethernet 10/100 Mbit Interface with integrated status LEDs
(green LED: Connection to network established, yellow LED: network traffic)
4 DC Input external device: supplied by a 12V switching adapter (delivered with the device)
internal device: supplied via the slot interface of the device
5 AUX Equipped at CS141L, CS141LM, CS141SC and CS141SCM to connect CON_R_AUX4
and BACS etc.
6 Status LEDs
(red / green)
Operation Status CS141 LED Notification
Unpacking the operating system (update procedure) red blinking
Error while unpacking the operating system red fast blinking
Boot process of the operating system red long on
Communication to external device lost (e. g. UPS) red and green
Normal operation - connection to external device established green blinking
7 Slide Switch
DIP Switch
For switching between different boot options
.
Slide Switch in the middle position / 1 + 2 position OFF: To set the
CS141 in the configuration mode and activated the default IP address
10.10.10.10. after a cold start.
Slide Switch in the right position / 1 position OFF + 2 position ON:
DHCP Mode, the IP is set by the DHCP Server. Check the MAC address
of your device to identify your device in the network.
Slide Switch in the left position / 1 position ON + 2 position OFF:
The network settings of the HTTP interface are used it is also possible
to configure DHCP Mode.
8 USB
5
3267
1
84
CS141SC CS141L CS141MINI
5
32672
36
7
Slot
Version External
Version
CS141 SNMP / WEB / MODBUS MANAGER
Version: 2019-01-16
EN

Variant 1
1. Move the Slide Switch in the middle position / DIP
SW 1 & 2 in the position OFF.
2. Connect the LAN port of the CS141 directly with
an Ethernet Cross Cable to the PC / workstation.
Important:
It is recommended to set the PC to the same network
segment, for example 10.10.10.11 AND for the Gate-
way 10.10.10.11 .
Variant 2
1. Move the Slide Switch in the middle position / DIP
SW 1 & 2 in the position OFF.
2. Connect the PC with a Switch or Hub and two
Network Cables on the LAN port of the device.
External Version
Connect the UPS with the original UPS cable to the
COM1 port of the CS141.
Slot Version
Put the device into the slot interface of the UPS.
For the installation of the UPS, have a look into the
User Manual which is part of the documentation CD
or could be downloaded from the homepage of your
UPS manufacturer.
All UPS functions and the usage of flexible events
etc. are described in the CS141 User Manual!
2. Connect device to the UPS
IP 10.10.10.10
DIP Switch 1+2 = off
Slide Switch „middle“
IP: 10.10.10.11
Subnet: 255.255.255
Gateway: 10.10.10.11
Ethernet
cross
cable
Ethernet
cables IP: <Your IP Address>
Gateway: <Your Gateway>
IP 10.10.10.10
DIP Switch 1+2 = off
Slide Switch „middle“
Hub/Switch
Power Supply
3. Connect the CS141 to the power supply
External Version
Connect the CS141 to the provided power supply.
Slot Version
The CS141 slot devices are supplied via the slot in-
terface of the device. It is always possible to insert or
remove the CS141 without damaging the UPS. To
interrupt the power supply, remove the device from
the slot and insert it again.
Installation/Network Integration of a CS141
1. Enabling of configuration mode

4.1. Add the route of the standard IP address on your computer
1. Open the “DOS Command Prompt” or
2. execute “cmd.exe”
3. Enter the following command:
„route add 10.10.10.10 <local IP Address>”
(for example:
“route add 10.10.10.10 192.168.222.54” )
4. Execute the command "ping 10.10.10.10" to check
if the device is reachable.
Advice: The CS141 needs approximately 30 seconds
to start the webserver. If the webserver runs, the LED
will changes from red (booting) to green and starts
blinking.
4.2. Automatic search with the tool "Netfinder"
The following link leads to the software "NetFinder"
that search your device on the network automatically:
http://www.generex.de/generex/download/software/
install/NetFinder.zip
1. Start a Browser
2. Enter the address http://10.10.10.10
3. For the login choose the
user name: „admin“
Default password: „cs141-snmp“
5. Access via HTTP connection and login
4. Access to the CS141 over the network
6. Choose language
1. Choose the entry
- System
- General
At the drop-down menu on the left side.
2. Choose the preferred „Language“.
EN

1. Choose the entry
- System
- Network
at the drop-down menu on the left side.
2. Enter the values for
- IP Address
- Subnet Mask
- Default Gateway
("DNS-Server", if desired)
3. Press the button “Apply” to commit the changes.
4. Choose the entry
- System
- Date & Time
in the drop-down menu.
5. Enter the „IP Address“ of your timeserver and
synchronize the CS141 with this server.
The timeserver settings are important for the event- /
alarm logging. (If no timeserver is configured the time
will be set to 01.01.2000 00:00).
6. The changes of each configuration page have to
commit by pressing the button “Apply”.
7. Choose the point
- Devices
- UPS
- Setup
in the drop-down menu for the UPS configuration.
8. Choose the „UPS Model“, which is connected to
the CS141.
9. Click on the button “Apply” to save the changes.
More Information about the UPS settings are
available in the CS141 User Manual.
7. Configure the IP address of the CS141
Basic Network Settings

Connect the LAN port of the device with a RJ45 net-
work cable (not included) to the network.
The CS141 is reachable on the
IP address 10.10.10.10 !
1. For changing into the operating mode push the
Slide Switch in the left position / DIP SW 1 in the po-
sition ON.
2. For Cold-Boot remove the power supply from the
CS141.
3. Connect the CS141 to the power supply again.
The CS141 is reachable at the configured IP address.
(The address 10.10.10.10 isn't reachable anymore!)
10. Sending shutdown signals to computers on the network
For shutting down a computer in case of a power fai-
lure it is necessary to install an RCCMD client on it.
Some configurations into the event management of
the adapter have to be done, too.
Installation of the RCCMD client
1. Download the setup file from the UPS-
Management CD or from from the internet.
2. Each RCCMD installation requires a seperate li-
cense key. For some products, a license key is in-
cluded. More licenses are available at your supplier.
http://www.salicru.com
Network
8. Connect the CS141 with the network
9. Switch into the operation mode
Power Supply
3. In the first menu, you have to enter the IP address
of the adapter whose shutdown signals should recei-
ve. Commit the following default configuration. Note
the shutdown file in the last window. For editing the
shutdown sequence of the client, press the button
"configure" (It is also possible to edit the batch file to
change or add events.) the installation finishes by
pressing "install" and the service will start.
EN

1. Choose the entry
- Devices
- UPS
- Events
from the drop-down menu.
2. Click the Button “+” next to the event “Powerfail”.
3. The Job-Editor starts. Choose the option
“RCCMD Shutdown” from the menu.
4. Enter the „IP Address“ of your client (The Liste-
ner Port is usually 6003). At the right side you can
specify when the shutdown signal is going to be
released, for example „At 240 seconds remaining
time“.
5. Click the button „Apply“.
6. For security reasons it is recommended to make
the same RCCMD shutdown entries at „Powerfail“ for
the Event “Battery low” - but here without any delays
to avoid that the server crashes because of low bat-
tery alarm!
The CS141 can be a variety of environmental sen-
sors and other measuring devices are combined, to
temperature, humidity, fire and smoke, motion and
intrusion, pressure, levels etc. to be monitored.
In addition, other components such as various
mounting brackets, BACnet Converter, PROFIBUS
Converter etc. available. Please ask your UPS manu-
facturers / suppliers for more detailed information
about the options available.
11. Event configuration for the CS141
12. Options for the CS141

description fonction
1 COM1-Interface Interface série (câble RS232) pour la communication avec un onduleur ou un autre appareil
2 COM2-Interface
Pour connecter des périphériques supplémentaires (par exemple le modem GSM,
le capteur d'humidité ou de température, le SENSORMANAGER II ou d’autres appareils
qui communiquent par le bus (par exemple Modbus-RS232, Profibus et LonBus, etc.)
Connexion CS141L, CS141SC, CS141MINI & CS141R_2 (avec RS232 ),
CS141LM et CS141SCM (avec RS485).
Pas disponible pour CS141BL et CS141_BSC.
3 RJ45 interface LAN Interface Ethernet 10/100 Mbit avec des diodes d'état à LED
(couleur verte: indique que la connexion au réseau est établi,
couleur jaune: indique qu'il ya du trafic sur le reseau)
4 DC entrée de
puissance
Dispositif externe: equipé d’un adaptateur de commutation de 12 V (livré avec l'appareil)
Dispositif interne: via l'interface de la fente de l'ASC
5 AUX Disponible en tant que CS141L, CS141LM, CS141SC et CS141SCM: il peut être connecté à
CON_R_AUX4 et BACS etc..
6 Status-LED
(rouge et vert)
Etat de fonctionnement du CS141 signalisation LED
Déballage du système d'exploitation (processus de mise à jour) Diode rouge clignote
Erreur lors du déballage du système d'exploitation Diode rouge
clignote rapidement
Lancement du système d'exploitation Diode rouge fixe
Perte de la communication au dispositif externe (par exemple UPS) Diode clignote en
rouge et vert
Fonctionnement normal - Connexion avec un appareil externe est établi Diode clignote en vert
7 Interrupteur à
glissière
Commutateur DIP
Pour la commutation entre les différentes options de démarrage
Interrupteur à glissière en position médiane / Commutateur DIP 1
+ 2 en position OFF: Pour mettre le CS141 en mode configuration et
activer l'adresse IP standard 10.10.10.10 (après un démarrage à froid).
Interrupteur à glissière en position droite / DIP-Switch 1 Position
OFF, 2 Position ON: Adressage IP automatique : DHCP mode est
activé et l'adresse IP est défini par le serveur DHCP automatiquement.
Vérifiez l’adresse MAC de votre appareil (CS141) pour identifier votre
appareil dans le réseau.
Interrupteur à glissière en position gauche / Commutateur DIP 1
en position ON, 2 position OFF: Les paramètres de réseau de l'inter-
face HTTP sont utilisés. Il est également possible de configurer le
mode DHCP.
8 USB
5
3267
1
84
CS141SC CS141L CS141MINI
5
32672
36
7
Version
de slot Version
externe
CS141 SNMP / WEB / MODBUS MANAGER
Version: 2019-01-16
FR

Variante 1
1. Placez le commutateur en position médiane / DIP
SW 1 et 2 en position OFF.
2. Connectez le port LAN du CS141 directement
avec un câble Ethernet Croise au PC / poste de
travail.
Important:
Il est recommandé de donner au PC et au port
(gateway) la mème adresse IP, par exemple
10.10.10.11 .
Variante 2
1. Placez le commutateur en position médiane / DIP
SW 1 et 2 en position OFF.
2. Connectez le CS141 et le PC avec un hub ou
switch et deux câbles Ethernet sur le port LAN de
l'appareil.
Dispositif externe
Connectez l'onduleur avec le cable d’origine UPS au
COM1 du CS141.
Dispositif interne
Lors de l'utilization d'une carte interne insérer la dans
la fente de l'UPS prévue à cet effet.
Pour l'installation de l'onduleur, veuillez lire le manuel
qui est inclus dans le CD ou la documentation qui
peut être téléchargée sur la page internet du fabricant
de votre UPS.
Toutes les fonctions de l'onduleur et l'utilisation
d'événements flexibles, etc., sont décrits dans le
Manuel de l'utilisateur du CS141 !
2. Connectez l'adaptateur à l'ASC
IP 10.10.10.10
Interrupteur en position médiane
Commutateur DIP 1 + 2 = off
IP: 10.10.10.11
Subnet: 255.255.255
Gateway: 10.10.10.11
Ethernet
cross
cable
Ethernet
cables IP: <Your IP Address>
Gateway: <Your Gateway>
IP 10.10.10.10
Interrupteur en position médiane
Commutateur DIP 1 + 2 = off
Hub/Switch
Power Supply
3. Connectez le CS141 à l'alimentation
Dispositif externe
Connectez le CS141 à l'alimentation fournie.
Dispositif interne
Le CS141 recoit du courant à travers l'alimentation
interne de l'onduleur. Il est toujours possible d'insérer
ou de retirer le CS141 sans endommager l'onduleur.
Pour déconnecter la carte, retirez le périphérique de
la fente et placez-le à nouveau.
Installation / Intégration au réseau du CS141
1. Activer le de mode de configuration

4.1. Ajouter l'adresse IP standard sur votre ordinateur
1. Ouvrez un „DOS command“ fenêtre ou
2. Exécutez la commande „cmd.exe“
3. Entrez la commande suivante:
„Route add 10.10.10.10 <adresse IP locale“
(par exemple: „route add 10.10.10.10
192.168.222.54")
4. Exécutez la commande „ping 10.10.10.10" pour
vérifier si l'appareil est accessible.
Conseils: Le CS141 a besoin d'environ 30 secondes
pour démarrer le serveur web. Quand le serveur Web
fonctionne, la diode change de couleur du rouge en
vert (démarrage) et se met à clignoter.
4.2. Détection de l'appareil avec l'outil "NetFinder"
Le lien suivant mène au logiciel "NetFinder" qui cher-
che votre appareil automatiquement sur le réseau:
http://www.generex.de/generex/download/software/
install/NetFinder.zip
1. Ouvrez le navigateur de Web.
2. Entrez l'adresse http://10.10.10.10
3. Pour la connexion choisir:
nom d'utilisateur: „admin“
mot de passe par défaut: „cs141-snmp“
5. Accès via une connexion HTTP et login
4. Accès au CS141 via le réseau
6. Choisissez la langue
1. Alley sur
- Système
- Général
dans le menu à gauche.
2. Ensuite choisissez la „langue“.
FR

1. Choisissez
- Système
- Réseau
dans le menu à gauche.
2. Entrez les valeurs de
- Adresse IP
- Masque de sous-réseau
- Passerelle
("Serveur DNS" si désiré)
3. Appuyez sur le bouton „Appliquer“ pour valider
les modifications.
4. Choisissez
- Système
- Date & Heure
dans le menu déroulant.
5. Entrez „l'adresse IP“ de votre serveur de synchro-
nisation et synchronisez le CS141 avec ce serveur.
Les paramètres temporels du serveur sont importants
pour l'enregistrement / d'alarme d’un événement (Si
aucun serveur de synchronisation est configuré le
temps sera mis à 01.01.2000.
6. Configure les modification en appuyant sur le bou-
ton „Appliquer“.
7. Choisissez les points
- Appareils
- ASC
- Configuration
dans le menu déroulant pour la configuration d' ASC.
8. Choisissez le modèle ASC qui est relié avec le
CS141.
9. Cliquez sur le bouton „Appliquer“ pour enregistrer
les modifications.
Plus d'informations sur le paramètre d‘ ASC sont
disponibles dans le CS 141 Mode d'emploi.
7. Configurez l'adresse IP du CS141
Paramètres réseau de base

Raccordez le port LAN de l'appareil avec un câble
réseau RJ45 (non inclus) au réseau.
Pour le moment le CS141 est toujours accessible sur
l'adresse IP 10.10.10.10!
1. Pour changer le mode de fonctionnement, déplac-
er le commutateur vers la gauche / DIP-Switch 1 en
position ON.
2. Pour un démarrage à froid (Cold-Boot) retirer l'ali-
mentation électrique du CS141.
3. Ensuite connectez le CS141 à l'alimentation à
nouveau. Le CS141 sera joinable à l'adresse IP con-
figurée. (L'adresse n’est plus accessible à
10.10.10.10)
10. Envoyez signales d'arrêt aux ordinateurs sur le réseau
Pour arrêter un ordinateur en cas de panne de
courant, il est nécessaire d'installer un client RCCMD
à chaque ordinateur qui doit etre arreté. En outre il y
à certaines configurations à faire dans la gestion de
l'événement de l'adaptateur.
Installation du client RCCMD
1. Télécharger le fichier d'installation de l'ASC-
Management CD ou de Internet.
2. Chaque installation RCCMD nécessite une clé de
licence distinct. Pour certains produits, une clé de
licence est inclus. Licences supplémentaires sont
disponibles chez votre fournisseur.
http://www.salicru.com
Network
8. Connectez le CS141 avec le réseau
9. Mettre le CS141 en mode de fonctionnement
Power Supply
3. Dans le premier menu, vous devez entrer
l'adresse IP de l'adaptateur dont le client de RCCMD
doit recevoir les signaux d'arrêt. Validez la configura-
tion par défaut suivant. Remarquez le fichier d'arrêt
dans la dernière fenêtre. Pour modifier la séquence
d'arrêt du client, appuyez sur le bouton "configure" (Il
est également possible d'éditer le fichier batch pour
modifier ou ajouter des événements.) L'installation se
termine en appuyant sur "Install" et le service dé-
marre.
FR

1. Choisissez l'entrée
- Appareils
- ASC
- Évènements
dans le menu déroulant.
2. Cliquez sur le bouton "+" à côté de l'événement
"Perte d‘alimentation".
3. Le Job-Editor démarre. Choisissez l'option
“RCCMD Shutdown” dans le menu.
4. Saisissez „l'adresse IP“ de votre client (Le Liste-
ner-Port est habituellement 6003). Sur le côté droit,
vous pouvez spécifier quand le signal doit être arrêté,
par exemple „At 240 seconds remaining time“.
5. Cliquez sur le bouton „Appliquer“.
6. Pour des raisons de sécurité, nous vous recom-
mandons de faire un RCCMD d'arrêt en cas de
“panne de courant” ("Power Fail") comme dans le
cas de "batterie faible" - mais, dans ce cas, sans
aucun retard pour éviter que les pannes de serveur
aient raison de l'alarme de batterie faible.
Le CS141 peut être complète par une variété de cap-
teurs d’environnement et d’autres dispositifs pour
surveiller température, humidité, feu et fumée,
mouvement et intrusion, pression, niveaux de replis-
sage etc.
En outre, d'autres composants tels que de divers
fixations de montage, BACnet convertisseur,, PROFI-
BUS convertisseur etc. disponibles. S'il vous plaît
demandez à votre ASC fabricants / fournisseurs pour
d’informations plus détaillées sur les options disponi-
bles.
11. Configuration de l'événement pour le CS141
12. Options pour CS141

Beschreibung Funktion
1 COM1-Anschluss Serielle Schnittstelle für den Anschluss einer USV oder anderen Endgeräten
mit dem original RS232-Kabel
2 COM2-Anschluss
Für den Anschluss weiterer Geräte, wie z. B. GSM-Modem, Temperatur- und Feuchtesensor,
SENSORMANAGER_II, Feldbusgeräte (MODBUS RS232, Profibus, LONBus, etc.).
Anschluss bei CS141L, CS141SC, CS141MINI & CS141R_2 = RS232
Anschluss bei CS141LM & CS141SCM =RS485
(nicht bei CS141BL, CS141BSC)
3 LAN-Buchse RJ 45 Ethernet 10/100 Mbit Schnittstelle mit integrierten Status LED‘s
(Grüne LED: Verbindung ins Netzwerk besteht, Gelbe LED: Netzwerkaktivität)
4 DC-Eingang Versorgung über 12VDC geregeltes Steckernetzteil extern,
DC-Stecker außen (-) Minus, innen (+) Plus
5 AUX Bei CS141L, CS141LM, CS141SC und CS141SCM Anschluss für CON_R_AUX4 und BACS
6 Status-LEDs
(rot und grün)
Betriebszustand CS141 LED-Signalisierung:
Entpacken des Betriebssystems (Update-Vorgang) rot blinkend
Fehler beim Entpacken des Betriebssystems rot schnell blinkend
Bootphase des Betriebssystems rot lange an
Verbindung zu externem Gerät verloren (z. B. USV) rot und grün
Normalbetrieb—Verbindung zu externem Gerät aktiv grün blinkend
7 Schiebeschalter
DIP Switch
Zur Umschaltung Konfigurations-/Betriebsmodus und DHCP
.
Schalterknopf mittig / 1 + 2 Position OFF: setzt den CS141 in den
Konfigurationsmodus und aktiviert die Standard IP-Adresse 10.10.10.10.
nach einem Kaltstart.
Schalterknopf rechts / 1 Position OFF + 2 Position ON: Automatische
IP Adressierung: DHCP ist aktiviert und eine IP Adresse wird automa-
tisch gesetzt. Prüfen Sie die MACAdresse von Ihrem CS141, um die IP-
Adresse in der DHCP Server-Tabelle identifizieren zu können.
.
Schalterknopf links / 1 Position ON + 2 Position OFF: Verwendung
der im HTTP-Interface konfigurierten Werte. Mit gesonderter Einstellung
auch DHCP möglich.
8 USB
5
3267
1
84
CS141SC CS141L CS141MINI
5
32672
36
7
Slot
Version
Externe
Version
CS141 SNMP / WEB / MODBUS MANAGER
Version: 2019-01-16
DE