8
MODEL FLUE TERMINATIONAPPROVALS
ST-38HV-AU DVK-01DA, DVK-01TR
DVK-03DA DVK-TVCD
TABLE1
1.3 FLUE SYSTEM APPROVALS AND
INSTALLATIONS
This model is approved to use D-Series flue pipe
components.ADVK-01DA, DVK-03DAorDVK-01TR
Termination Cap must be used to terminate vent sys-
temsinahorizontalposition. DVK-TVCDvertical Ter-
minationCapsmustbeusedtoterminateventsystems
in a vertical position.
Figures 6 through 10 show the flue systems approved
for use with these models.Approved flue system com-
ponentsarelabeledforidentification.NOOTHER FLUE
SYSTEMS OR COMPONENTS MAY BE USED. De-
tailed installation instructions are included with each
flue termination kit and should be used in conjunction
with this manual.
WARNING:THIS GASAPPLIANCE AND FLUEAS-
SEMBLYMUST BE FLUED DIRECTLYTO THE OUT-
SIDEAND MUST NEVER BEATTACHED TO ACHIM-
NEY SERVING ASEPARATE SOLID FUEL BURNING
APPLIANCE. EACH GAS APPLIANCE MUST USE A
SEPARATEFLUESYSTEM-COMMONFLUESYSTEMS
AREPROHIBITED.
CAUTION:UNDERNOCONDITION SHOULDCOM-
BUSTIBLE MATERIAL BE CLOSER THAN 3 INCHES
(21/2 INCHESATWALLFIRESTOPS)FROM THETOP
OF THE 8 5/8-INCH PIPE OR 1-INCH TO THE SIDES
ANDTHEBOTTOMFORHORIZONTALSECTIONSOF
THISFLUE SYSTEM. VERTICALSECTIONSOF THIS
SYSTEM REQUIRE A MINIMUM OF 1-INCH CLEAR-
ANCETOCOMBUSTIBLE MATERIALSALLAROUND
THE 8 5/8 - INCH PIPE.
For alternative installations, other than depicted, con-
tactyourdealer for furtherinformation.
Refer to Figure 4 for required clearances to flue termi-
nals.
STRAIGHT OUT HORIZONTAL FLUE
SYSTEM
Figure6shows straight outhorizontalflue systemsand
straight up vertical flue systems approved for use on
this model.
ELBOWS
Thefluesystems installed onthisgas heatermayalso
includeone(1),two (2),orthree(3) 90 -degreeelbow
assemblies, in addition to the 45 - degree elbow re-
quired at the unit.
Figures7through10andtheircorrespondingtablesshow
examplesofventconfigurationsusingelbows.Therela-
tionships of vertical rise to horizontal run in vent con-
figurationsusingelbowsMUST be strictly adheredto.
ONE (1) 90-DEGREE ELBOW
Figure7shows aninstallationusingone(1) 90-degree
elbow. Dimension V is listed as MINIMUM vertical di-
mensionsanddimensionH is listed ascorresponding
MAXIMUMhorizontal dimensions.
TWO (2) 90-DEGREE ELBOWS
Figure8showsexamples of possible installationsus-
ingtwo(2) 90-degreeelbows.Dimension Vislisted as
MINIMUM vertical dimensions, dimension H is listed
as MAXIMUM beginning horizontal dimensions, and
dimension H+H1is listed as corresponding TOTAL
MAXIMUM horizontaldimensions.
THREE (3) 90-DEGREE ELBOWS
Figures 9 and 10 show examples of possible installa-
tionsusingthree (3) 90-degreeelbows.Dimensions V
are listed MINIMUM first vertical dimensions and di-
mensions H are listed as beginning MAXIMUM hori-
zontaldimensions. DimensionsH+H1 andH+H1+H2 are
listed as TOTAL MAXIMUM horizontal dimensions.
DimensionsV+V1are listedasTOTALMAXIMUM ver-
tical dimensions.
NOTE: When the 450elbow is attached horizontally,
thesuppliedheatshieldmustbeinstalled(seeFigure5).
Figure 5
HEAT SHIELD