S&C IntelliRupter PulseCloser SDA-4650R2 User manual

Instruction Sheet 766-557
S&C IntelliRupter®PulseCloser®Fault Interrupter
Outdoor Distribution (15.5 kV, 27 kV, and 38 kV)
July 31, 2017
©S&C Electric Company 2013-2017, all rights reserved.
Docking Station Instructions
Table of Contents
Section Page Section Page
Introduction
Qualified Persons ............................. 2
Read this Instruction Sheet ...................... 2
Retain this Instruction Sheet ..................... 2
Special Warranty Provisions ..................... 2
Safety Information
Understanding Safety-Alert Messages ............. 3
Following Safety Instructions ..................... 3
Replacement Instructions and Labels .............. 3
Overview ..................................... 4
Setup .........................................5
Establishing Wi-Fi Connection ..................7
Serial Connection with a Docking Station.......11
Serial Connection—Rev. 3.4.x and Earlier
Connect with IntelliLink® Setup Software...........12
Reloading Firmware with Download Utility ..........13
Verification of Correct Operation .................16
Serial Connection—Rev. 3.5.x and Later
Connect with IntelliLink Setup Software ............17
Reloading Firmware with Download Utility ..........19
Verification of Correct Operation .................21
Shutting Down. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
BMM Revisions for the Docking Station ........23

2 S&C Instruction Sheet 766-557
Qualified Persons ÇWARNING
The equipment covered by this publication must be installed, operated, and maintained by
qualified persons who are knowledgeable in the installation, operation, and maintenance
of overhead electric power distribution equipment along with the associated hazards. A
qualified person is one who is trained and competent in:
• The skills and techniques necessary to distinguish exposed live parts from non-live
parts of electrical equipment.
• The skills and techniques necessary to determine the proper approach distances
corresponding to the voltages to which the qualified person will be exposed.
• The proper use of the special precautionary techniques, personal protective equip-
ment, insulating and shielding materials, and insulated tools for working on or near
exposed energized parts of electrical equipment.
These instructions are intended only for such qualified persons.They are not intended
to be a substitute for adequate training and experience in safety procedures for this type
of equipment.
Read this
Instruction Sheet
Thoroughly and carefully read this instruction sheet before programming, operating, or
maintaining your S&C IntelliRupter PulseCloser Fault Interrupter. Familiarize yourself
with the safety information on page 3. The latest version of this instruction sheet is avail-
able online in PDF format at sandc.com/Support/Product-Literature.asp
Retain this
Instruction Sheet
This instruction sheet is a permanent part of your S&C IntelliRupter PulseCloser Fault
Interrupter. Designate a location where you can easily retrieve and refer to this publication.
Special Warranty
Provisions
The standard warranty contained in S&C’s standard conditions of sale, as set forth in Price
Sheet 150, applies to IntelliRupter®fault interrupter and its associated options except
for the control group (the protection and control module and communication module)
and S&C SpeedNet™ Radio, as applicable. For these devices the rst paragraph of said
warranty is replaced by the following:
(1) General: Seller warrants to immediate purchaser or end user for a period of
10years from the date of shipment that the equipment delivered will be of the kind and
quality specified in the contract description and will be free of defects of workmanship
and material. Should any failure to conform to this warranty appear under proper and
normal use within ten years after the date of shipment the seller agrees, upon prompt
notification thereof and confirmation that the equipment has been stored, installed, oper-
ated, inspected, and maintained in accordance with recommendations of the seller and
standard industry practice, to correct the nonconformity either by repairing any dam-
aged or defective parts of the equipment or (at seller’s option) by shipment of necessary
replacement parts.
Replacement control groups and S&C SpeedNet Radios provided by seller or repairs
performed by seller under the warranty for the original equipment will be covered by
the above special warranty provision for its duration. Replacement control groups and
S&C SpeedNet Radios purchased separately will be covered by the above special war-
ranty provision.
This warranty does not apply to major components not of S&C manufacture, such
as batteries and communication devices, as well as hardware, software, resolution of
protocol-related matters, and notification of upgrades or fixes for those devices. However,
S&C will assign to immediate purchaser or end user all manufacturers’ warranties that
apply to such major components.
Introduction

S&C Instruction Sheet 766-557 3
Understanding
Safety-Alert Messages
There are several types of safety-alert messages which may appear throughout this
instruction sheet as well as on labels attached to the IntelliRupter fault interrupter.
Familiarize yourself with these types of messages and the importance of the various
signal words, as explained below.
ÇDANGER
“DANGER” identifies the most serious and immediate hazards that will likely result in
serious personal injury or death if instructions, including recommended precautions,
are not followed.
ÇWARNING
“WARNING” identifies hazards or unsafe practices that can result in serious personal
injury or death if instructions, including recommended precautions, are not followed.
ÇCAUTION
“CAUTION” identifies hazards or unsafe practices that can result in minor personal injury
if instructions, including recommended precautions, are not followed.
NOTICE
“NOTICE” identifies important procedures or requirements that can result in product or
property damage if instructions are not followed.
Following
Safety Instructions
If you do not understand any portion of this instruction sheet and need assistance,
contact your nearest S&C Sales Ofce or S&C Authorized Distributor. Their tele-
phone numbers are listed on S&C’s website sandc.com Or call S&C Headquarters
at (773) 338-1000; in Canada, call S&C Electric Canada Ltd. at (416) 249-9171.
NOTICE
Read this instruction sheet thoroughly and carefully
before installing or operating your S&C IntelliRupter
PulseCloser Fault Interrupter.
Replacement
Instructions
and Labels
If you need additional copies of this instruction sheet, contact your nearest S&C Sales
Ofce, S&C Authorized Distributor, S&C Headquarters, or S&C Electric Canada Ltd.
It is important that any missing, damaged, or faded labels on the equipment be replaced
immediately. Replacement labels are available by contacting your nearest S&C Sales
Office, S&C Authorized Distributor, S&C Headquarters, or S&C Electric Canada Ltd.
Safety Information

4 S&C Instruction Sheet 766-557
Overview
These instructions cover the procedure for operating the IntelliRupter PulseCloser Fault
Interrupter Docking Station. This device powers the protection and control module
when it is removed from the IntelliRupter fault interrupter, and permits uploading and
downloading conguration settings, by using a dedicated base memory module. The
docking station can also be used with a communication module when it is removed from
the IntelliRupter fault interrupter and installed in the docking station with a protection
and control module. The protection and control module provides the power for the com-
munication module and permits programming the radio, verifying radio operation, and
charging the communication module battery.
The docking station may be used to monitor serial communication traffic between
the protection and control module and the communication module, using either a secure
Wi-Fi connection to your personal computer or a direct connection to your serial-port-
equipped personal computer. A user-furnished DNP test set, such as manufactured by
ASE, may be connected to the docking station to monitor DNP messages.
The docking station includes a Wi-Fi radio antenna. Connectors are provided for a
user-furnished SCADA radio antenna and a user-furnished GPS receiver antenna.
The docking station may be powered from 88 to 264 V, 50/60 Hz. It is intended for
indoor use only.
NOTICE
To ensure that previously programmed settings in the protection and control module
are not lost when the module is installed in the docking station, you must unplug the
base memory module from the docking station. If the base memory module is not
unplugged from the docking station when the docking station is powered up,
the protection and control module will upload the most recently applied settings
stored in the base memory module.

S&C Instruction Sheet 766-557 5
Setup
Step 1
Set up the docking station on a sturdy work surface. If Global Positioning System opera-
tion is to be checked, place the docking station near a window, so that satellite signals
can be received by the user-furnished GPS antenna.
Step 2
Connect the power cord to the docking station. Then plug the power cord into an ac outlet.
Step 3
If a SpeedNet Radio is installed: Insert the “Radio Ethernet to Control / Radio Ethernet
to Comm” jumper into the docking station.
Step 4
If you wish to directly connect your personal computer to the docking station to com-
municate with the protection and control module, instead of using the Wi-Fi connection:
a. Remove the factory-installed “Wi-Fi Serial to Control / Wi-Fi Serial to Comm” jumper
from the docking station.
b. Plug the computer into the “Wi-Fi Serial to Control” port.
Step 5
Carefully attach the protection and control module to the docking station. Make sure that
the connector guide pins are aligned properly, then insert them fully.
Step 6
Carefully attach the communication module to the docking station. Make sure that the
connector guide pins are aligned properly, then insert them fully.
Step 7
If serial trafc between the protection and control module and the radio is to be moni-
tored through a DNP test set: Plug the DNP test set into the “RX” port.

6 S&C Instruction Sheet 766-557
Setup
Step 8
To preserve previously programmed settings in the protection and control module:
Unscrew the locking ring of the base memory module and unplug the module.
NOTICE
If the base memory module is not unplugged from the docking station when the docking
station is powered up, the protection and control module will upload the most recently
applied settings stored in the base memory module.
Step 9
Turn on the docking station power switch. The red lamp on the docking station will light.
And the status indicator on the protection and control module will start ashing, for 1/2
second every 30 seconds.
NOTICE
The Global Positioning System requires up to 5 minutes to “lock on” and provide tim-
ing signals. If desired, the protection and control module clock can be set manually in
IntelliLink Setup Software. Select Setup > General,Tab:Time. See Figure 1. Follow the
instructions provided on the screen.
Figure 1. Setup—General—Time screen.

S&C Instruction Sheet 766-557 7
Establishing Wi-Fi Connection
The Wi-Fi transceiver provides secure wireless point-to-point communication to a wireless-
equipped personal computer operating under IEEE 802.11b standard. Transmission range
is typically 150 feet or less.
Click the IntelliLink software or LinkStart icon or select Program Start >S&C Electric
>LinkStart V3 on the personal computer.The LinkStart connection screen will appear.
See Figure 2.
Figure 2. LinkStart connection screen.
If the base memory module is unplugged: The default universal access serial number
(00-0000000) will be used. If the base memory module is plugged in: Type in its serial
number (in this example 08-9000014).
Click Connect. The Wi-Fi connection process will begin. See Figure 3.
Figure 3. Wi-Fi connection in progress.

8 S&C Instruction Sheet 766-557
Establishing Wi-Fi Connection
The secure connection device driver will begin transmitting an encrypted, invisibly
addressed “wake-up” message to the communication module. Progress is noted on the
horizontal indicator bars. In addition, the status indicator on the protection and control
module pulsates, dim to bright, while Wi-Fi connection is being established.
After IntelliRupter fault interrupter recognizes the wake-up message and its source, it
will proceed with authentication. Encrypted messages are exchanged that require correct
decryption keys in both the personal computer and the protection and control module.
When the link is successfully established, the Active status indicator becomes green.
Signal strength is continuously shown on the vertical indicator bars. See Figure 4.
Figure 4. Successful Wi-Fi connection screen.

S&C Instruction Sheet 766-557 9
Establishing Wi-Fi Connection
Click the IntelliLink button. IntelliLink Setup Software will open.
After logging in, you can review the settings in the protection and control module, and
change them as appropriate. You can also review and download event logs and diagnostic
screens. Refer to S&C Instruction Sheet 766-530, “IntelliRupter PulseCloser Protection
and Communication Setup” Instructions.
NOTICE
Settings suitable for radial, IntelliTeam®II Automatic Restoration System, and loop resto-
ration can be entered into the protection and control module while it is connected to the
docking station. But only the settings actually suitable for the control group—specified by
the IntelliRupter fault interrupter catalog number suffix (“-C0” through “-C6”)—can be used
when the protection and control module is installed in the IntelliRupter base.
NOTICE
Commands to open or close IntelliRupter fault interrupter will result in errors because the
docking station does not provide operation feedback.To clear the errors, select Diagnos-
tics > Errors. See Figure 5.
Click the Clear Errors button.
Figure 5. Error Diagnostics screen.

10 S&C Instruction Sheet 766-557
If you have programmed new settings in the protection and control module and wish
to use them when the module is installed in the IntelliRupter fault interrupter base, select
Setup > General, Tab: IntelliRupter. See Figure 6.
Select “On Next Power-up, Use Settings From Control.”
Remember to select Setup > Validate/Apply and click the Apply button before shut-
ting down.
Figure 6. Setup—General—Validate/Apply screen.
Establishing Wi-Fi Connection

S&C Instruction Sheet 766-557 11
Serial Connection with a Docking Station
In the event that communication with an IntelliRupter Control cannot be established over
the Wi-Fi link, a direct serial connection can be made to an IntelliRupter Control when it
is installed in the IntelliRupter Docking Station. The serial connection will permit inspec-
tion of control operation, and if necessary, allow reloading control rmware.
To establish a serial connection you will need:
• IntelliRupter Docking Station, Communication Module, and the Control
Module.
• Straight-Through 9-Pin Serial Cable
• PC Computer loaded with the latest IntelliRupter Fault Interrupter Software
Step 1
Power the Docking Station and check that the red LED is on.
Step 2
Locate the serial jumper cable on top of the docking station. It should connect the two
ports labeled Wi-Fi Serial to Control and Wi-Fi Serial to Comm. Unplug the end of the
jumper connected to Wi-Fi Serial to Comm, and plug the male end of your serial cable
into the jumper. See Figure 7. The jumper functions as a gender changer.
Step 3
Plug the other end of the serial cable into the serial port on your computer, and make
note of the COM Port number. If you do not have a serial port on the computer, use a
Serial to USB adapter cable.
Figure 7. Serial Cable connected to the Wi-Fi Serial to Control input.

12 S&C Instruction Sheet 766-557
Serial Connection—Rev. 3.4.x and Earlier
Step 1
IntelliLink Setup Software is installed by default in the C:\Program Files\
S&C Electric\IntelliLink folder. Double click the application ilink.exe to launch the
IntelliLink software. The location of this le is shown in Figure 8.
Connect with
IntelliLink® Setup
Software
Figure 8. Location of the IntelliLink Setup Software application file.
Step 2
When the IntelliLink software is launched, it is congured by default to connect to the
control over a wireless link. It automatically attempts to establish this connection. Wait
for the connection attempt to time-out. Messages in the Connect dialog window should
be approximately the same as Figure 9.
Figure 9. IntelliLink Connect dialog window.
NOTICE
The following procedure is used with IntelliRupter Installer versions 3.4.x and earlier. For
newer installer revisions see the next section, that starts on page 17.

S&C Instruction Sheet 766-557 13
Step 3
Select the Change Setup... button. This will launch the IntelliLink Options
menu. Navigate to the Communications tab, shown in Figure 10. Change the
connection from UDP/IP to Serial and then select the correct COM Port. In this case the
port is COM1. The Baud Rate should be set at 57600. No other options should be changed.
Figure 10. IntelliLink Options dialog window.
Step 4
When you have set the communications parameters on the Options window, click the
Save & Exit button.
Step 5
After the Options window closes, the Connect window will be visible. Click the Retry
button. See Figure 9. The IntelliLink software will attempt to establish a connection using
the new communication parameters.
Depending on the state of rmware in the control, you may receive a warning or an
error message once a connection has been established.
If you receive an error message or were unable to download rmware through the
Wi-Fi connection to upgrade your control, follow the instructions for Reloading Firmware
with Download Utility.
If you performed this procedure to determine if your control is operational and did
not receive warnings or errors, please contact S&C Electric Company for support. Your
problem is probably not related to control rmware.
Reloading control rmware should only be started after an attempt to connect to the con-
trol with the IntelliLink software has generated errors or warning messages that indicate
incorrect versions or maintenance mode conditions.
Step 1
In order to avoid communication conicts, close any open instances of the IntelliLink
software before launching Download Utility (DU).
Reloading Firmware
with Download Utility
Serial Connection—Rev. 3.4.x and Earlier

14 S&C Instruction Sheet 766-557
Figure 11. Download Utility (DU) file location.
The Download Utility will try to automatically establish communication with the con-
trol, but will eventually time-out. The connection status for DU is displayed in the lower
left hand corner. See Figure 12.
Figure 12. Download Utility connection status, shown on the Control Software Loader
window.
Step 2
The DU application, by default, is installed in the C:\Program Files\
S&C Electric\IntelliLink folder shown in Figure 11.
Serial Connection—Rev. 3.4.x and Earlier

S&C Instruction Sheet 766-557 15
Step 3
When DU connection status changes from Trying connection on 127.0.0.1 to Not con-
nected, select the Communications Setup tab at the top center of the window. The new
tab window is shown in Figure 13.
Figure 13. Download Utility (DU) file location.
Step 4
Your settings may not exactly match Figure 13, but the important parameters are shown
there. Set the Conn. Type to Serial and that the correct Comm Port is selected. The Baud
Rate should be set to 57600.
Do not change the DNP Settings: the Peer Addr, or Our Addr settings. Use the settings
congured in Download Utility.
Step 5
When you have set all parameters on the Control Software Loader
Communication Setup tab, click the Connect button.
Step 6
When status indicates that Download Utility is connected, navigate to the Download/
Upload tab and click the Start Download button. When prompts appear asking whether
or not to Skip a Download, you should click the No button.
Step 7
When download is complete, do not exit Download Utility. Navigate back to the Com-
munication Setup tab and change the Conn. Type back to UDP/IP. Then click the Exit
button to close the Download Utility.
Serial Connection—Rev. 3.4.x and Earlier

16 S&C Instruction Sheet 766-557
After control rmware has been successfully loaded, it is recommended that you verify
that the control is operating correctly, by using the IntelliLink software.
Step 1
After closing the update window the IntelliLink software will prompt you to log in. Enter
the appropriate Use Name and Password.
Step 2
On the IntelliRupter Operation screen, check the Control Status in the upper right hand
corner. Verify that the control is in the Okay state. If there are any alarms, warnings, or
errors—please contact S&C Electric Company.
Step 3
Check the Setup > General > Revisions screen, shown in Figure 14, to see that the cor-
rect rmware has been installed.
Verification of
Correct Operation
Figure 14.The IntelliRupter Setup > General > Revisions screen.
After you complete verication, change the communication parameters of IntelliLink
back to the default settings.
Step 4
Locate the Tools menu option at the top of the screen. The communication parameters
are on the Tools > Options menu. See Figure 15. Change the Connection Type to UDP/
IP and then click the Save & Exit button. Close the IntelliLink software.
Step 5
Disconnect the serial cable from the jumper, and reconnect the jumper to the Wi-Fi Serial
to Comm connector on the Docking Station.
The Control and Communication Modules should now correctly respond to a LinkStart
connection attempt.
Serial Connection—Rev. 3.4.x and Earlier

S&C Instruction Sheet 766-557 17
Step 1
IntelliLink Software is installed in the C:\Program Files (x86)\S&C Electric\IntelliLink6
folder. Double Click the ILink6.exe application to launch the IntelliLink software. The
location of the le is shown in Figure 15.
Connect with
IntelliLink Setup
Software
Figure 15. Location of the IntelliLink Setup Software application file.
Step 2
When the IntelliLink software is launched, it is congured by default to connect to the
control over a wireless link. It automatically attempts to establish this connection. Wait
for the connection attempt to time-out. Messages in the Connect dialog window should
be approximately the same as Figure 16.
Figure 16. IntelliLink Connect dialog box.
NOTICE
The following procedure is used with IntelliRupter Installer versions 3.5.x and later. For
earlier installer revisions see the previous section, starting on page 12.
Serial Connection—Rev. 3.5.x and Later

18 S&C Instruction Sheet 766-557
Serial Connection—Rev. 3.5.x and Later
Step 3
Click the Cancel button. Then select Tools > Options… on the main menu. See
Figure 17.
Figure 17. Location of the Tools—Options button.
Step 4
This will launch the S&C IntelliLink Options menu. Navigate to the Connection
tab, shown in Figure 18. Make sure the Protocol is DNP. Change if needed. Change the
RTU: to self or 65532. Change the connection from UDP/IP to Serial and then select the
correct COM Port. In this case the port is COM5. The Baud Rate should be set at Auto.
Verify the Timeout ms: is set for 1000, and Retries: 5. Make changes as necessary. Click
the OK button. Refer to Figure 18.
Figure 18. S&C IntelliLink Options—Connection tab.
Step 5
Select Connection > Connect to Device... from the main menu. See Figure 19.
Figure 19. Menu selection Connect to Device....

S&C Instruction Sheet 766-557 19
Serial Connection—Rev. 3.5.x and Later
Step 6
Login with your User Name and Password or use the default User Name: admin and
Password: 1135Atlantic if you haven’t change the defaults.
Reloading control rmware should only be started after an attempt to connect to the con-
trol with the IntelliLink software has generated errors or warning messages that indicate
incorrect versions or maintenance mode conditions.
Step 1
Connect with the IntelliLink software as shown in the previous section.
Select Tools > Firmware Update... from the main menu. See Figure 20.
Reloading Firmware
with Download Utility
Figure 20. Menu selection Fimrware Update....
Step 2
Click the Yes button in the Conrmation dialog box. See Figure 21.
Figure 21. Confirmation dialog box.

20 S&C Instruction Sheet 766-557
Serial Connection—Rev. 3.5.x and Later
Step 3
The Firmware Update dialog box opens. See Figure 22.
Figure 22. Firmware Update dialog box.
Step 4
If any of the software components installed in the control have the same or higher version
number as the versions being downloaded a message similar to that shown in Figure 23
will appear. It is recommended that you select the Yes button unless instructed otherwise
by an S&C representative.
Figure 23. Confirmation dialog box.
Step 5
After the software components have been installed the control will automatically be
restarted and the Enter your credentials dialog will open. See Figure 24.
Figure 24. Enter your credentials dialog box.
Step 6
Enter your User Name and Password or the factory default User Name: admin and
Password: 1135Atlantic if you have not changed them.
After the process has completed click the Close button to proceed.