SECOLink GSV4M User manual

GSV4M
Universal GSM / GPRS communicator Wiring manual
1
The device must be installed in a place with limited access.
Please act according to your local rules and do not dispose of your unusable alarm system or its components with other household
waste. This product utilization in EU is covered by European Directive 2002/96/EC.
The device must be connected to an AC power supply with Protective Earthing. Cable colours mean: Phase or Live line (L) - black
or brown cable, Neutral line (N) - blue cable, Protective Earth line (PE) - green cable with a vertical yellow dash. Double isolated
2
cables with minimum cross-sectional area of 0,75 mm for 230V power supply must be used.
The device uses two power supplies: main and back-up.
2V, 7Ah/20HR capacity, rechargeable hermetically sealed Lead-Acid battery.
Main power supply: a power transformer with:
- primary winding: ~230V, 50 Hz;
- secondary winding: ~20V, 1.5A, 50Hz.
Back-up power supply: 1
GSV4M is compliant with EN 60950-1 safety requirements.
Power supplies described above must comply with the EN 60950-1 safety requirements.
All devices being connected with the alarm system (sirens, detectors, computer for programming and etc.) must comply with
EN 60950-1 safety requirements.
The communicator contains a radio transceiver operating within GSM900/1800 frequency ranges.
DO NOT USE the communicator where interferences can arise because of the influence with other devices and this may causethe
potential danger.
DO NOT USE the communicator close to medical devices.
DO NOT USE the alarm system device in a dangerous environment with the risk of fire and explosion.
Additional automatic Two-Pole Circuit Breaker should be installed in an AC electric power circuit in order to protect against
over-current, short circuits and earthing faults.
The circuit breaker contact gap should be no less than 3mm, protective circuit breaker current must be in 0,5A - 2A range .
The circuit breaker should be placed close to the system's housing and should be easily accessed.
Before performing any work of installation or service always disconnect the device from power supplies in sequence as described
below:
- cut off 230 VAC power line with the automatic Two-pole Circuit Breaker;
- disconnect 12V back-up battery by removing battery female plug from Control Panel male socket BAT.
Two-pole Circuit-Beaker installation on flexible cables is forbidden.
General safety requirements:
- do not touch any part of the main power supply under voltage: transformer, a fuse block, connection wires;
- it is forbidden to perform any device installation or service work during lightning;
- use batteries according to manufacturer recommendations. The use of improper battery type may cause an explosion;
- be sure battery terminals are isolated, battery terminals short-wiring may cause an explosion.battery replacement :
It is not recommended to connect the device to a fully discharged battery.
Inoperative or expired batteries should be recycled according to the local rules or EU directives 2006/66/EC and 93/86/EEC.
Collection and separate utilization of waste battery is mandatory!
To avoid system malfunction use an adequate charger to
charge a new or discharged battery before connecting battery to the device.
The connection to the mains supply must be made as per the local authorities rules and regulations.
The end of a stranded conductor shall not be consolidated by soft-soldering, insulated pins shall be used. Insulated pins shall be
connected in a manner that they are and with remain mechanically efficient.
Power supply distribution board
Automatic two-pole
circuit breaker
L N
NL
Cable from power
distribution board
Power cable to the
cabinet
The device installation and service should be performed by trained personnel with sufficient knowledge about the device and
general safety requirements for work with low voltage (up to 1000V) AC power lines. In the case of a device malfunction repair
works can be performed by qualified personnel only. If the system is malfunctioning, the end user should inform the qualified
personnel as soon as possible. User doesn't have right to repair the system.
GSV4M, installed in the metal cabinet (device)
Picture 1. Automatic two-pole circuit breaker and power cable wiring diagram
Universal GSM / GPRS communicator communicatorcomes with in-built LED indicator. LED blinks when is powered up.
SAFETY WARNINGS

GSV4M –GSM / GPRS communicator is designed to be used with other manufacturers' intruder alarm systems. The communicator expands
the functionality of other manufacturers’ intruder alarm systems by giving the options to report to the receiver of central monitoring station via
GPRS, to send a notification via SMS or phone call.
(for example, to trigger a key-switch zone and arm / disarm the system).
It is possible to connect GSV4M to control the panel in few different ways:
Connection to the PSTN dialer of control panel. By simulating an analog telephone line GSV4M enables the control panel with PSTN dialer to
report to CMS or the user. Compatible with control panels that communicate using the Contact ID format.
Connection to the control panel keybus. GSV4M analyses the control panel keybus, and when it is necessary, sends a report to CMS or
notification to the user.
Connection to control panel PGM outputs. In case of alarm, the control panel output triggers GSV4M input. The communicator acts as
programmed and sends the report to CMS or notification to the user.
The communicator has two open collector outputs capable of a maximum of 50mA. User can
trigger the outputs to turn on an LED or activate an input on the host panel
GSV4M communicator
Connection to PSTN dialer of control panel. The communicator is powered from independent power supply
GSV4M
S1
12V battery
7Ah/20HR
Live
wire
L
Neutral
wire
N
Protective
Earth wire
PE
Main Protective
Earthing terminal AC power transformer:
Primary winding: 230V AC 50Hz
Secondary winding: 20V AC 50Hz
~
~
Power supply
distribution board
Enabled
Contact ID
12345
Disabled
Disabled
Control panel PSTN dialer
programming
Reporting:
Format:
Phone number for dialling:
Phone line monitoring:
Dial tone search:
Control panel
Grounding
place Grounding
place
Protective
Earth wire
PE
Main Protective
Earthing terminal
GSM/GPRS communicator GSV4M is powered from an independent power supply. The independent power supply that contains a fuse block, power
transformer and 12V 7Ah battery together with the communicator have to be placed in a grounded metal housing.
Connection to PSTN dialer of control panel. The communicator is powered from control panel power supply
2
GSV4M
Universal GSM / GPRS communicator Wiring manual
+12V
RING
COM
IN1
IN3
IN4
IN5
IN6
20 VAC
PGM1
PGM2
TIP
IN2
Fuse
250mA
R-1
T-1
RING
TIP
+12V
COM
TIP RING T-1 R-1 COM+12V
TIP
RING
Mounting communicator in cabinet
Communicator has to be fastened in cabinet by
using plastic studs. Communicator mounting holes
should correspond to cabinet's rear wall holes. Do
not forget to fix the plastic studs in the rear holes
before fastening the cabinet on a wall.
Plastic stud
Cabinet
GSV4M
GSV4M
S1
Control panel
+12V
RING
COM
IN1
IN3
IN4
IN5
IN6
20 VAC
PGM1
PGM2
TIP
IN2
R-1
T-1
RING
TIP
+12V
COM
TIP RING T-1 R-1 COM +12V
Enabled
Contact ID
12345
Disabled
Disabled
Control panel PSTN dialer
programming
Reporting:
Format:
Phone number for dialling:
Phone line monitoring:
Dial tone search:

GSV4M
Universal GSM / GPRS communicator Wiring manual
Connection to control panel keybus (reading only)
Connection to control panel keybus (reading and writing)
Connection to control panel zone inputs / PGM outputs
GSV4M
S1
+12V
RING
COM
IN1
IN3
IN4
IN5
IN6
20 VAC
PGM1
PGM2
TIP
IN2
3
COM
PGM1
Control panel
+12V
COM
COM
Z1
Alarm
Control
COM
+12V
COM PGM1 Z1 COM COM +12V
GSV4M
S1
Control panel
+12V
RING
COM
IN1
IN3
IN4
IN5
IN6
20 VAC
PGM1
PGM2
TIP
IN2
GRN
+12V
COM
YEL
GRN
YEL COM +12V
GSV4M
S1
Control panel
+12V
RING
COM
IN1
IN3
IN4
IN5
IN6
20 VAC
PGM1
PGM2
TIP
IN2
GRN
+12V
COM
YEL
GRN
YEL COM +12V
COM
+12V
+12V
COM
Compatible control panels:
PC580 PC585 PC1555MX PC1565
PC1616 PC1832 PC1864 PC5005
PC5008 PC5010 PC5015 PC5016
PC5020
Important! GSM4M communicator firmware
version should be v.4.000 or higher; programming
software GSV4M Loader version should be
v.3.000 or higher.
Compatible control panels:
PC580 PC585 PC1555MX PC1565
PC1616 PC1832 PC1864 PC5005
PC5008 PC5010 PC5015 PC5016
PC5020
Important! GSM4M communicator firmware
version should be v.4.000 or higher; programming
software GSV4M Loader version should be
v.3.000 or higher.
The GSV4M has six inputs that can be used to
trigger specific communications. If control panel
doesn't have a PSTN dialer or dialer is already in use
the communication between control panel and
communicator can be established by connecting
control panel PGM outputs to communicator inputs.
Communicator inputs are monitored and on their
status change the communicator will start to report to
monitoring station via GPRS or will send a notification
to user via SMS or phone call.
The GSV4M also has two programmable PGM
outputs to activate in response to the user control
commands via SMS, phone call. If it is necessary to
control the alarm system it can be done by connecting
GSV4M output to control panel zone input. Control
panel zone inputs are monitored and on their status
change the system can armed /disarmed and etc.
Note: in the wiring diagram on right is shown the
connection of open collector type PGM output to zone
input (NO/NC loop type). If the output type is different
please use relays and control the devices through
them. It is recommended to use diode to supress
voltage surges on relay.

+12V
COM
20 VAC
PGM1
PGM2
GSV4M
+12V DC external
power supply
Load
20VAC COM
+12V PGM2
PGM1
PGM output wiring
3
Inputs
Normally open contact
(NC)
Normally closed
contact
(NC)
Technical information
Overall dimensions L x W
Operating temperature:
120,0 x63,5 mm
-10°C + 50°C–
9
years.A
Calculated life expectancy for communicator at 40 ambient temperature is
mbient temperature over 40 may reduce life expectancy.
°C
°C
Maximum load ratings and electrical characteristics
Maximum battery charging current:
DC voltage:
+0,035A
9 - 14V
Maximum current into PGM1:
Maximum current into PGM2:
-0,05A
-0,05A
Minimum AC voltage on 20 VAC:
Current consumption (idle running):
~16V
50mA
Maximum AC voltage on :
Note: higher than V voltage can damage communicator.
20 VAC
~22
~22V
Maximum current of fast blowing fuse used in battery circuit:
Current consumption (within data transmission):
3,15A
365mA
Maximum current of slow blowing fuse used in primary AC:
Maximum AC power consumption:
250mA
15mA
Communicator is powered from independent power supply
Communicator is powered from control panel power supply
GSV4M
Universal GSM / GPRS communicator Wiring manual
Note: do not use +12V
terminal for powering other
devices, the external +12V
DC power supply must be
used.
Additional information
Firmware upgrade Status LED
Required softwares:
Firmware Upgrade Tool v.1.xx
GSV4M Loader v.3.000
GSV4M
S1
Status
LED
Modem
LED
Status LED:
Off – GSM network problem (SIM not active,
poor signal strength, antenna not connected);
1 flash –GSM signal strength: ;
2 flashes –GSM signal strength: ;
3 flashes –GSM signal strength: ;
4 flashes –GSM signal strength: ;
5 flashes –GSM signal strength: ;
On (2 seconds) –event is received (from
PSTN dialer or keybus), input is triggered.
Upgrade steps:
1. Disconnect the communicator from power supply.
2. Press and hold S1 button.
3. Connect USB cable while holding S1 button.
4. In order to upgrade the GSV4M, double-click on the latest firmware
upgrade file (for example: GSV4M v.4.000c.dfu ).
6. Follow the instructions in software Firmware Upgrade Tool to complete
the firmware upgrade procedure.
7. Restore GSV4M settings to default values with a software GSV4M loader.
8. GSV4M firmware is now upgraded. You can disconnect GSV4M from the
computer. Modem LED:
Off – modem problem;
Flashing (0,5 seconds on, 0,5 seconds off) –GSM network problem (SIM
not active, poor signal strength, antenna not connected);
Short flash every 2 seconds –registered on GSM network;
On –dialling or data transmission is in progress.
IN1
GSV4M
NO
COM
IN1
GSV4M
NC
COM
In order to program GSV4M connect device to computer using USB cable. Software GSV4M loader is used to program GSV4M
communicator. It can be downloaded from out web page: www.secolink.eu. GSV4M loader automatically downloads the present settings
from GSV4M when USB cable is connected. Carefully choose the GSV4M operation mode before starting the programming. Entered
phone number, ticked setting checkbox and etc. are automatically saved in software (in temporal memory), but aren't automatically sent to
GSV4M. Do not forget to send them to GSV4M when programming is finished. Entered settings also can be saved in file (press button
Export template).
GSV4M Loader software
GSV4M settings are split in different categories for easier programming:
Users – user phone numbers, dialling and messaging settings can be changed in this tab. User phone numbers must be entered starting with a country
code, for example +4466454xxxxx. Plus sign „+“ is automatically entered by software. If user wants to control GSV4M he should enter PIN during the call. If
commonicator is not connected to other manufacturer control panel module keybus, user should enter PIN that is programmed in this tab. By default this PIN
is 1111 and is common for all GSV4M users. If GSV4M is connected to other manufacturer control panel module keybus, user should enter the same PIN
which is used to operate alarm system via keypad.
GPRS reporting - all settings related to reporting to monitoring station can be changed in this tab. GSV4M can send reporting to two receivers, in 3 diferent
protocols.
Inputs - GSV4M has 6 inputs to trigger specific communications. It is possible to assign a specific Contact ID event or a simple text message to be sent
when input is triggered.
Outputs – GSV4M has has two programmable outputs to activate in response to
–
Security settings – the GSV4M contains two diferent level security options: it is possible to limit the access to GSV4M GPRS settings only or limit the
access to all GSV4M settings. Keep security password in safe place.
GSM modem settings – in this tab is possible to enter SIM card PIN, review the information about GPRS communication, GSM signal strenght.
Phrases – all phrases that are used in SMS messages are stored in this tab. In order receive readable SMS with a actual zone, partition or user names it is
necessary to fill all related fields. When communicator receives the report from PSTN dialer it is checking the phrase list and when received event element id
numer matches it uses that phrase in SMS.
Voice messages – this tab allows the voice message to be assigned to a zone. It is possible to choose any from 243 available voice files. GSV4M loader
interface language must be the same as written on GSV4M communicator sticker.
Summary – all GSV4M settings can be reviewed and printed in this tab.
user control commands via SMS, phone call.
Outputs control with a short call if it is necessary to control GSV4M output without sending DTMF tone string or SMS command this can be don by
entering users phone number phone number section of this tab and assigning output to number. In order to trigger the output user should call to GSV4M.
User should hear the dialling tone and reject the call. This actions will trigger an output. Note: if user phone number is saved in users tab phone number list
and user wants to control the GSV4M by sending DTMF tone string he should not reject the call and wait 5 seconds. After 5 seconds communicator will
answer the call and will "ask" to enter PIN and hash.
Table of contents