Date Code 20010214 SEL-2505 Remote I/O Module
Configuring the SEL-25 5
Table 2 Data Sec urityepl Count Sett ings
For example, in Figure 8 on page 6, SW7 is set to “ON.” This requires
two consecutive messages to be confirmed before asserting/deasserting
OUT5 and OUT6, while all other outputs require only one message.
Setting
the Baud Rate
Table 3 lists the settings for the three baud rate options. For applications
using fiber connections between SEL devices, baud rate 38400 is
recommended. This recommendation is based on operating time. For
applications where a multiplexer or other communications device is
between the two MIRRORED BITS devices, baud rates 19200 or 9600 are
recommended. If the channel is operating intermittently, lowering the
baud rate will provide more stable performance in most cases.
Table 3 Prot ocol/Baud R ate Settings
Connecting
the SEL-2505 to
Other SEL Devices
The SEL-2505 uses the MB8 MIRRORED BITS protocol, transmits and
receives data at the baud rate set by switches 9 and 10, and is fiber
optic. When connecting the SEL-2505 to a MIRRORED BITS port of a
relay or the SEL-2100, the following are required:
1. An SEL-2800, SEL-2815, or SEL-2830 fiber modem.
2. The MIRRORED BITS protocol must be set to MB8; the MB
protocol is incompatible with the SEL-2505.
3. The SPEED setting must be set to match the setting of the
SEL-2505.
4. The transmit address of the local device must match the
receive address of the remote device.
If your relay does not have MB8 protocol, contact SEL for a firmware
upgrade.
The following examples show how to configure the SEL-351, SEL-321,
and the SEL-2100 to operate with the SEL-2505. Only the minimum
settings required to configure the communication interface between the
relays, SEL-2100, and SEL-2505 are shown. Consult the appropriate
instruction manual to ensure proper settings for your particular
MIRRORED BITS application.
Table 2 Data Security Count Settings
Switch Message 1 Message 2
Switch 5 (OUT1, OUT2) OFF ON
Switch 6 (OUT3, OUT4) OFF ON
Switch 7 (OUT5, OUT6) OFF ON
Switch 8 (OUT7, OUT8) OFF ON
Table 3 Protocol/Baud Rate Settings
Switch 10 Switch 9
OFF OFF MB8 Protocol @ 38400 Baud
OFF ON MB8 Protocol @ 19200 Baud
ON OFF MB8 Protocol @ 9600 Baud
ON ON Reserved