Selec RPS15-12-CE User manual

Doc. name: OP INST RPS15-12-CE OP2058 - V01 ( Page 1 of 2 )
WIRING INSTRUCTIONS
1. To prevent risk of electric shock, power supply equipment must be
kept OFF while wiring.
2. Terminals and electrically charged parts must not be touched when
the power is ON.
3. Wiring shall be done strictly according to terminal layout provided
in the operating manual.
17.5 mm x 90 mm x 65 mm ( W x H x D )
< 100 gms
DIMENSIONAL DIAGRAM
DIMENSION
WEIGHT
INPUT SPECIFICATIONS
100 - 240 VAC ( 141 - 340 VDC )
INPUT VOLTAGE RANGE
AC CURRENT ( TYP. )
0.3 A @ 115 VAC; 0.15A @ 230 VAC
EFFICIENCY ( TYP. )
≥ 80 % @ 230 VAC
Ø
Ø
Ø
Ø
Ø
Ø
Ø
Ø
Ø
Ø
AC 100 - 240 V Wide-range Input.
Cost optimized without compromising quality or reliability.
Full power between - 25 C and + 50 C.
Compact size.
Plastic case, Ultra slim.
Support wide range of AC / DC auxiliary supply.
Efficiencies up to 82 %.
Protection against short circuit, overload.
Cooling by free air convection.
0 0
FEATURES
SPECIFICATION
selec
WIRING DIAGRAM
FREQUENCY RANGE
50 / 60 Hz
INTENDED USE
This device is designed for installation in an enclosure and is intended for the
general professional use such as in
ndustrial control communication .
Do not use this power supply in equipment where malfunction may cause
severe personal injury or threaten human life.
instrumentation equipment, office,
i and
SAFETY INSTRUCTION
64.35
64.35
START UP TIME
1 Sec, Full Load
<
Operating Instruction
EMS IMMUNITY
Compliance to IEC61000-4-4,5,11
CISPR22; Class A
RADIATED EMISSION
CISPR32; Class B
CONDUCTED EMISSION
DIELECTRIC WITHSTAND
VOLTAGE
I/P to O/P: 4000 VAC
100 M min. ( between all outputs and all inputs /
PE terminals ) at 500 VDC
INSULATION RESISTANCE
Ω
SAFETY & EMC
Designed to meet IEC 62368-1
SAFETY STANDARDS
ENVIRONMENT
- 40 C to + 70 C; De-rate linearly above 50 C from
100 % load at 50 C to 50 % load at 70 C.
Note: Only start up guaranteed at - 40 C with spec
deterioration.
0 0 0
0 0
0
OPERATING TEMPERATURE
STORAGE TEMPERATURE
COOLING
- 40 C to + 85 C
0 0
Natural Cooling
ALTITUDE
2000 m
5 to 95 % RH, Non Condensing
HUMIDITY
Possible for up to two power supplies
( with external diode )
SERIES OPERATION
OUTPUT SPECIFICATIONS
30 ms @ 230 VAC & 10 ms @ 115 VAC, Full Load
HOLD UP TIME
12 to 14 VDC
< 1 % of Vout
1.25 A at 12 VDC
OUTPUT VOLTAGE
OUTPUT CURRENT
RIPPLE AND NOISE
LINE AND LOAD REGULATION
± 1 %
PROTECTIONS
110 % to 150 % of rated output current
Protection type: Hiccup mode; recovers
automatically after fault condition is removed.
1.25 A - 250 VAC Internal
INPUT FUSED
OUTPUT SHORT CIRCUIT
OUTPUT OVER LOAD
25 C Ambient, Cold Start
0
< 30 Amps; Measured at 264 VAC,
RPS15-12-CE
4.30
90 90
17.50
Hiccup mode when output is shorted; Recovers
automatically after fault condition is removed.
VIBRATION
Component : 10 500 Hz, 2 G 10 min. / cycle,
period for 60 min. each along X, Y, Z axes.
~
DC ON
Vo ADJ.
selec
N
L
V+ V-
Ripple & Noise measured at 20 MHz of bandwidth by using 0.1uf &10uf parallel capacitor.
INRUSH CURRENT
( TYP. )

Attention: ( Fig. 1 )
1. Do not block the ventilation holes of power supply.
2. Keep at least 20 mm clearance around the switching power supply.
3. The Equipment should not be installed in environmental conditions other than
those specified in this manual.
Mounting: ( Fig. 2 )
1. Slightly tilt the unit to engage on the top side of Din Rail mounting.
2. Press it downward until it gets locked in Din Rail.
Removal: ( Fig. 3 )
1. Before removing power supply unit from Din Rail ensure that supply has been
switched off.
2. Unscrew all the wire connections of power supply unit.
3. Insert a screw driver into the mounting clamp slot & pull it down to remove the
power supply from Din Rail.
Doc. name: OP INST RPS15-12-CE OP2058-V01 ( Page 2 of 2 )
OUTPUT
INPUT
Fig. 1Fig. 1
Fig. 2
Fig. 3
This power supply is not field serviceable product. In case of failure or
malfunction, send back the power supply to factory.
Please contact service center for repair on the following numbers:
Tel. No. : +91-7498077172;
Email : [email protected]m
NO WARRANTY ON UNIT DAMAGED DUE TO WRONG CONNECTION OF
POWER SUPPLY.
( Specifications are subject to change, since development is a
continuous process. )
Factory Address :
91-22-28476443 / 1882
I
EL-27/1, Electronic Zone, TTC Industrial Area,
MIDC, Mahape, Navi Mumbai - 400 710, INDIA.
Tel. No. : +
Fax No. : +91-22-28471733 I Toll free : 1800 227 353
Website: www.selec.com Email: sale[email protected]
INSTALLATION INSTRUCTIONSINSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONSMEANING OF PRODUCT SAFETY SYMBOL
SERVICE
DETAILS
1. Do not use the power supply without proper grounding ( Protective Earth )
2. Do not use in wet locations or in areas where moisture or condensation can
be expected.
3. Make sure mains power supply is off before wiring the power supply unit.
Make sure of correct wiring. Incorrect wiring may
cause electrical shock or damage.
4. Do not touch the power supply during operation or immediately
after turning off because some parts get hot or are at high
voltage which may cause burns or electrical shock.
5. Do not install the power supply where human body may come into
contact while power is supplied to the power supply.
6. Do not repair the power supply at user end. Modification or
repairing of the power supply by users may cause electrical
shocks, damage & other accidents.
7. If damage or malfunction occurs during operation, immediately turn off
mains power.
WARNING : Risk of electrical shock, fire, personal injury or death.
Minor burns may occasionally occur. Do not touch the
product while power is being supplied or immediately
after power is turned OFF.
CAUTION
Minor injury due to electric shock may occasionally occur.
Do not touch the terminals while power is being supplied.
If the external breaker or fuse is tripped, the equipment may
have been seriously damaged. Do not turn ON the input
again.
Minor electric shock, fire or product failure may occasionally
occur. Do not allow any pieces of metal or conductors or any
clippings or cuttings resulting from installation work to enter
the product.
Ø
Ø
This manual is meant for personnel involved in wiring installation
operation & routine maintenance of the equipment.
Disconnect power supply of your system before starting any
installation operation or wiring.
Improper installation operation or wiring may impair safety & failure
of the unit or electrical shock or damage.
Connect the ground completely. A protective earthing terminal
stipulated in safety standards is used. Electric shock or
malfunction may occur if ground is not connected properly.
Ø
Ø
SAFETY INSTRUCTIONS
Indicates the possibility of electrical shock under
specific conditions
Indicates the possibility of injuries by high temperature
under specific condition
Indicates the instructions of unspecified general action.
Other Selec Power Supply manuals
Popular Power Supply manuals by other brands

Altronix
Altronix ALTV2432UL3 Series installation guide

Cross Technologies
Cross Technologies 2000-318 instruction manual

Matsusada Precision
Matsusada Precision EPR Series instruction manual

ANSMANN
ANSMANN DCPS-Netbook operating instructions

Ryobi
Ryobi OP40HB Operator's manual

SECO-LARM
SECO-LARM ENFORCER EVP-1SD2P4UL installation manual