
MI00360-2-EN INSTALLATION MANUAL 4/4
SETTING THE DIP-SWITCHES
The position of the DIP-switches denes the Modbus communication parameters of the module: Address and Baud Rate
The following table shows the values of the Baud Rate and the Address according to the setting of the DIP-switches:
Note:
When DIP switches 3 to 8 are OFF, the communication settings are taken from programming (EEPROM).
Note 2:
The RS485 line must be terminated only at the ends of the communication line.
DIP-Switch status
SW1 POSITION BAUD
RATE
SW1 POSITION
ADDRESS
POSITION
TERMINATOR
1 2 3 4 5 6 7 8 3 4 5 6 7 8 10
9600 #1 Disabled
19200 #2 Enabled
38400 #...
57600 #63
From
EEPROM
From
EEPROM
The settings of the dip-switches must be compatible with the settings on the registers.
The description of the registers is available in the USER MANUAL.
ANALOGUE INPUT SETTING VIA DIP-SWITCH:
DIP-Switch SW2 denes the type of input for each individual channel.
Channels 1 to 4 can be set in current or voltage.
For the settings, refer to the SW2 table on the side.
ELECTRICAL CONNECTIONS
2
3
-Vac/Vdc
+ Vac/Vdc
1
Power supply
The upper limits must not be exceeded as this can seriously damage the module.
If the power supply source is not protected against overload, a safety fuse with a 2.5A
max permissible value must be installed in the power supply line.
GND
B
A
4
5
6
ModBus RS485
Connection for RS485 communication using the MODBUS master system as an alternative
to the Z-PC-DINx bus.
N.B. The indication of the RS485 connection polarity is not standardised and in some
devices may be inverted.
INPUTS
A) Voltage input with sensor supply from the
MODULE (13 Vdc)
B) Voltage input with sensor supply NOT coming
from the MODULE
C) Current input with sensor supply NOT coming
from the MODULE
D) Current input with sensor supply from the
MODULE (13 Vdc)
E) Current input with EXTERNAL sensor supply
#I 2n
#I 4n
#I 3n
#I 1n
gn d
++++
TX
TX
TX
TX
ve xt
TX
TX
TX
TX
+
S
S
S
S
va ux*
vauxvaux
va ux *(
g en erat a da l m odu lo
) = 13 Vd c
AB C D A
SW2 ANALOGUE INPUTS
ON CURRENT INPUT
OFF VOLTAGE INPUT
vaux* (generated by the module) = 13 Vdc
ATTENTION
The upper power supply limits must not be exceeded, as this might cause serious damage to the module. Switch the mod-
ule off before connecting inputs and outputs.
To meet the electromagnetic immunity requirements:
• use shielded signal cables;
• connect the shield to a preferential instrumentation earth system;
• separate shielded cables from other cables used for power installations (inverters, motors, induction ovens, etc...).
• make sure that the module is not supplied with a supply voltage higher than that indicated in the technical specications
in order not to damage it.