MI00597-0-EN INSTALLATION MANUAL 1/4
INSTALLATION MANUAL
SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY; Tel. +39.049.8705359 - Fax +39.049.8706287
WARNING: The full content of this manual must be read before any operation. The module must only be used by
qualied electricians. Specic documentation is available via QR-CODE shown on page 1.
Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling).
The symbol on the product or its packaging shows the product must be surrendered to a collection centre
authorized to recycle electrical and electronic waste.
The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to
electrostatic discharges. Take appropriate measures during any operation.
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions that put the user's safety at risk.
The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the
instrument or the connected equipment. The warranty shall become null and void in the event of improper use or
tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if
the instructions contained in this manual are not followed.
CONTACT INFORMATION
Technical support [email protected] Product information [email protected]
This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised.
The content of this document corresponds to the described products and technologies.
Stated data may be modied or supplemented for technical and/or sales purposes.
Z-8TC-SI
Z-8TC-SI-LAB
DOCUMENTATION
Z-8TC-SI
DOCUMENTATION
Z-8TC-SI-LAB
MI00597-0-EN INSTALLATION MANUAL 2/4
CERTIFICATIONS
https://www.seneca.it/products/z8tc-si/doc/CE_declaration
https://www.seneca.it/products/z8tc-si-lab/doc/CE_declaration
POWER SUPPLY Voltage: 10 ÷ 40Vdc; 19 ÷ 28Vac; 50-60 Hz; absorption: 0.6W max
ENVIRONMENTAL
CONDITIONS
Operating temperature: -25°C ÷ +70°C.
Humidity: 30% ÷ 90% non condensing.
Storage temperature: -30°C ÷ +85°C
Altitude: Up to 2000 m above sea level
Protection rating: IP20
ASSEMBLY 35mm DIN rail IEC EN60715
CONNECTIONS 4-way removable terminal block, 3.5mm pitch, 1.5 mm2 cable section max
COMMUNICATION
PORTS
IDC10 rear connector for IEC EN 60715 DIN bar, ModBUS-RTU, 1200÷115200 Baud
Micro USB on the front, ModBUS protocol, 2400 Baud
INSULATION
COMMUNICATION
PORTS RS485 on IDC10 connector
PROTOCOL ModBUS- RTU
TC INPUTS
No. of channels: 8; Type of thermocouples: J, K, E, N, S, R, B, T, L (individually activated and congurable in pairs)
MODULE LAYOUT
SIGNALS VIA LED ON FRONT PANEL
17.5 mm
Dimensions: 17.5 x 102.5 x 111 mm
Weight: 100 g
Container: PA6, black
111 mm
102.5 mm
LED STATUS LED meaning
PWR ON The device is powered correctly
FAIL ON Instrument in error state
RX Flashing Data receipt on port #1 RS485
TX Flashing Data transmission on port #1 RS485
TECHNICAL SPECIFICATIONS
N.B.: A delayed fuse with a maximum rating of 2.5 A must be installed in series with the power supply connection, near the module.
Power
Supply
TC4
TC5
TC6
TC7
TC8
TC3
TC2
TC1
Comm.
1500 Vac
40 Vac
RS485
Z-8TC-SI Z-8TC-SI-LAB
MI00597-0-EN INSTALLATION MANUAL 3/4
SETTING THE DIP-SWITCHES
The position of the DIP-switches denes the Modbus communication parameters of the module: Address and Baud Rate The fol-
lowing table shows the values of the Baud Rate and the Address according to the setting of the
DIP-switches:
Note:
When DIP - switches 1 to 8 are OFF, the communication settings are taken from programming (EEPROM).
Note 2: The RS485 line must be terminated only at the ends of the communication line.
DIP-Switch status
SW1 POSITION BAUD
RATE
SW1 POSITION
ADDRESS
POSITION FUNCTION
1 2 3 4 5 6 7 8 3 4 5 6 7 8 9 BOOTLOADER
9600 #1 Enabled
19200 #2 Disabled
38400 #... 10 TERMINATOR
57600 #63 Enabled
From
EEPROM
From
EEPROM
Disabled
The position of the dip-switches denes the communication parameters of the module.
The default conguration is as follows: Address 1, 38400, no parity, 1 stop bit.
FACTORY SETTINGS
12345678
KEY
ON
OFF
SPAN mV ±150mV.
IMPEDANCE
> 4
MΩ.
ADC 24 bit.
TEMPERATURE DRIFT < 100ppm/K.
COLD JUNCTION ERROR
<1°C.
TEST CURRENT
<100nA.
CMRR
70dB @ 100ms
DMRR
60 dB.
SUPPORTED INPUT SPECIFICATIONS
SENSOR ACCURACY (AT 23°C) SOLUTION MEASURING RANGE STANDARD
J± (0.03% + 0.2°C) (**) 0.5µV (~0.01°C @ 0°C) -210 ÷ +1200°C EN 60584-1:1997
K± (0.03% + 0.2°C) (**) 0.5µV (~0.02°C @ 0°C) -200 ÷ +1372°C EN 60584-1:1997
R± (0.03% + 0.3°C) (**) 0.5µV (~0.1°C @ 0°C) -50 ÷ +1768°C EN 60584-1:1997
S± (0.03% + 0.3°C) (**) 0.5µV (~0.1°C @ 0°C) -50 ÷ +1768°C EN 60584-1:1997
T± (0.03% + 0.1°C) (**) 0.5µV (~0.01°C @ 0°C) -200 ÷ +400°C EN 60584-1:1997
B± (0.03% + 0.3°C) (**) 0.5µV (~0.2°C @ 0°C) +250 ÷ +1820°C (*) EN 60584-1:1997
E± (0.03% + 0.2°C) (**) 0.5µV (~0.01°C @ 0°C) -200 ÷ +1000°C EN 60584-1:1997
N± (0.03% + 0.2°C) (**) 0.5µV (~0.02°C @ 0°C) -200 ÷ +1300°C EN 60584-1:1997
L± (0.03% + 0.15°C) (**) 0.5µV (~0.01°C @ 0°C) -200 ÷ +800°C Gost 8.585-2001
mV 0.03% + 15µV 0.5µV ± 150 mV
(*) Up to 250°C a zero temperature value is assumed.
(**) Acquisition speed 100ms, no cold junction compensation.
CAUTION
Even at constant room temperature, the declared accuracies are achieved after at least 30 minutes from switching on the device.
MI00597-0-EN INSTALLATION MANUAL 4/4
ELECTRICAL CONNECTIONS
Z-8TC-SI Z-8TC-SI-LAB
Power supply and Modbus interface are available using the Seneca DIN rail bus, via the IDC10 rear connector, or the Z-PC-DI-
NAL-17.5 accessory.
RS485GND
RS485A
RS485B
Power Supply AC / +
Power Supply AC / -
IDC 10
1
Back connector (IDC 10)
The illustration shows the meanings of the various IDC10 connector
pins if signals are to be sent via them directly.
To meet the electromagnetic immunity requirements:
- use shielded signal cables;
- connect the shield to a preferential instrumentation earth system;
- separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc.).
INSTALLATION REGULATIONS
MODBUS CONNECTION RULES
The module has been designed for vertical installation on a DIN 46277 rail. For optimal operation and long life, adequate ventila-
tion must be provided. Avoid positioning ducting or other objects that obstruct the ventilation slots. Avoid mounting modules over
heat-generating equipment. Installation in the bottom part of the electrical panel is recommended.
These are open type devices intended for installation in a nal casing/panel that offers mechanical protection and protection
against the spread of re.
1) Install the modules in the DIN rail (120 max)
2) Connect the remote modules using cables of an appropriate length. The following table shows cable length data:
-Bus length: maximum length of the Modbus network according to the Baud Rate. This is the length of the cables that connect
the two farthest modules (see Diagram 1).
-Derivation length: maximum length of a derivation 2 m (see Diagram 1).
Lunghezza
bus
Lunghezza
derivazione
1200 m 2 m
Schema 1
Modulo 2Modulo 1
Modulo 3
Modulo 4
Modulo 5
Lunghezza del Bus
Ld= Lunghezza derivazione
Ld
For maximum performance, it is recommended to use special shielded cables manufactured specically for RS485 communication.
Bus length Derivation
length Module 1 Module 2 Module 5
Module 4
Module 3
Diagram 1
Bus length
Ld= Derivation length
CAUTION
CAUTION

Other manuals for Z-8TC-SI

1

This manual suits for next models

1

Other Seneca I/O System manuals

Seneca Z-8TC User manual

Seneca

Seneca Z-8TC User manual

Seneca Z-D-IN User manual

Seneca

Seneca Z-D-IN User manual

Seneca Z-3AO User manual

Seneca

Seneca Z-3AO User manual

Seneca Z-4AI User manual

Seneca

Seneca Z-4AI User manual

Seneca R-32DIDO User manual

Seneca

Seneca R-32DIDO User manual

Seneca ZC-24DO User manual

Seneca

Seneca ZC-24DO User manual

Seneca Z-D-IN User manual

Seneca

Seneca Z-D-IN User manual

Seneca Z-SG User manual

Seneca

Seneca Z-SG User manual

Seneca Z-8TC-1 User manual

Seneca

Seneca Z-8TC-1 User manual

Seneca Z-5DI-2DO User manual

Seneca

Seneca Z-5DI-2DO User manual

Seneca ZE-4DI-2AI-2DO User manual

Seneca

Seneca ZE-4DI-2AI-2DO User manual

Seneca R-P Series User manual

Seneca

Seneca R-P Series User manual

Seneca Z-4TC-1 User manual

Seneca

Seneca Z-4TC-1 User manual

Seneca Z-4RTD2 User manual

Seneca

Seneca Z-4RTD2 User manual

Seneca Z-4TC User manual

Seneca

Seneca Z-4TC User manual

Seneca Z-4RTD2-SI User manual

Seneca

Seneca Z-4RTD2-SI User manual

Seneca R-32DIDO-P User manual

Seneca

Seneca R-32DIDO-P User manual

Seneca Z-4AI User manual

Seneca

Seneca Z-4AI User manual

Seneca ZE-4DI-2AI-2DO User manual

Seneca

Seneca ZE-4DI-2AI-2DO User manual

Seneca Z-DAQ-PID User manual

Seneca

Seneca Z-DAQ-PID User manual

Seneca ZE-4DI-2AI-2DO User manual

Seneca

Seneca ZE-4DI-2AI-2DO User manual

Seneca ZC-24DI User manual

Seneca

Seneca ZC-24DI User manual

Popular I/O System manuals by other brands

Siemens PPM-1U32.BPR owner's manual

Siemens

Siemens PPM-1U32.BPR owner's manual

National Instruments NI USB-6000 quick start

National Instruments

National Instruments NI USB-6000 quick start

WAGO I/O-SYSTEM 750 manual

WAGO

WAGO I/O-SYSTEM 750 manual

NI R Series user manual

NI

NI R Series user manual

National Instruments NI REM-11100 Getting started guide

National Instruments

National Instruments NI REM-11100 Getting started guide

INIM Electronics EM322AC quick start guide

INIM Electronics

INIM Electronics EM322AC quick start guide

M-system R3-PC16A instruction manual

M-system

M-system R3-PC16A instruction manual

Phoenix Contact FLS FLM PB SYS PRO UM E user manual

Phoenix Contact

Phoenix Contact FLS FLM PB SYS PRO UM E user manual

Mobotix MX-OPT-RS1-EXT Quick install

Mobotix

Mobotix MX-OPT-RS1-EXT Quick install

Intelix INT-HD52 owner's manual

Intelix

Intelix INT-HD52 owner's manual

Cloud Remote Dante DLM-1 Series installation guide

Cloud

Cloud Remote Dante DLM-1 Series installation guide

Valcom VE8048 quick start guide

Valcom

Valcom VE8048 quick start guide

Rockwell Automation Allen-Bradley 1794-IJ2XT user manual

Rockwell Automation

Rockwell Automation Allen-Bradley 1794-IJ2XT user manual

AutomationDirect Terminator Installation and I/O Manual

AutomationDirect

AutomationDirect Terminator Installation and I/O Manual

BlueChip AIP-8d user manual

BlueChip

BlueChip AIP-8d user manual

Keithley KUSB-3160 user manual

Keithley

Keithley KUSB-3160 user manual

Curtis Instruments 1351 manual

Curtis Instruments

Curtis Instruments 1351 manual

System Sensor M201E installation instructions

System Sensor

System Sensor M201E installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.