5. Troubleshooting
description
Cause
14B
Service time Depending on the intensity of
unit operation, at a certain time
a periodic inspection message
appears on the control panel.
– After disconnecting the unit
from power supply, it is nec-
essary to carry out periodic
inspection of the unit, i.e. to
check the air filter clogging
and the condition of the heat
exchanger, the heater and
fans.
19A
Low supply air
temperature
If the supply air temperature falls
below the permitted value: +5
°C, unit will stop operating with
10 min. delay.
Malfunction of the
heat exchanger
and/or heater.
Check temperature and sea-
son settings. Check the heat
exchanger and heater opera-
tion.
20A
Supply air
overheating
If the supply air temperature is
above the permitted value: +45
°C, unit will stop operating with
10 min. delay.
Malfunction of the
heat exchanger
and/or heater.
Check temperature and
season settings. Check the
heat exchanger and heater
operation.
13B
Heater off Unit with electric heater has
protection from overheating,
which can be activated if the
heater blow-cooling is
insufficient. Unit operation is not
terminated.
Heater is
disconnected due to
low air flow.
When heater cools down,
protection restores
automatically. It is
recommended to increase
ventilation intensity level.
4A
Electric heater
overheating
Unit with electric heater has
emergency protection from
overheating, which can be
activated in case of the heater
failure. Unit operation is
terminated.
Electric heater
overheating
protection is on.
Restore emergency
overheating protection after
electric heater overheating
cause has been eliminated.
27A
Return water low
temperature
In the unit with water heater,
when the water temperature
falls below the permitted value
of +10°C, the unit will stop op-
erating.
Failure of the hot
water preparation and
supply function in the
heating system.
Check circulation pump and
heating system condition,
heating valve actuator
performance.
28A
Frost possibility In the unit with plate heat ex-
changer, if the freezing protec-
tion of the heat exchanger is
activated and is not restored, the
unit will stop operating.
Temperature of the air
passing through plate
heat exchanger,
dropped lower
allowable level.
Check by-pass damper con-
dition and actuator perfor-
mance. It is recommended to
decrease ventilation level.
3A
Rotor stopping When there is no signal from the
rotor’s rotation sensor, if the
“Winter” season is set, the unit
will stop operating in 2 min.
The belt is broken,
failure of the rotor
motor or rotor sensor.
Check rotor drive and
rotation sensor condition.
11B
Rotor stopping When there is no signal from the
rotor’s rotation sensor, if the
“Summer” season is set, the
warning message appears in 2
min. on the control panel. The
unit operation is not terminated.
The belt is broken,
failure of the rotor
motor or rotor sensor.
Check rotor drive and
rotation sensor condition.
9A
B1 sensor failure When temperature exceeds the
maximum permitted limits: -30
°C...+75 °C, the unit stops
operating immediately.
Supply air
temperature sensor is
not connected or
broken down.
It is necessary to check sen-
sor connections or change
the sensor.