Simplex 2050 User manual

2050 / 2250 Panels IP Communicator /
Connected Services Gateway Module
Installation Guide
579-1463 Rev. C
*05791463C*

This page is intentionally blank

Contents 1 Introduction................................................................................................................................................... 3
2 Cautions, Warnings, and Regulatory Information.....................................................................................4
3 Important information..................................................................................................................................5
4 Compatibility..................................................................................................................................................7
5 Related documentation................................................................................................................................8
6 Overview.........................................................................................................................................................9
6.1 Specifications........................................................................................................................................................................................ 9
6.2 Central station transmission paths.................................................................................................................................................. 10
6.3 Central station receiver protocol support....................................................................................................................................... 10
6.4 Connected services transmission paths..........................................................................................................................................10
7 Getting started.............................................................................................................................................11
7.1 Reviewing the IP Communicator / Connected Services Gateway PIDs........................................................................................ 11
7.2 Understanding the work flow........................................................................................................................................................... 11
7.3 Installing the telephone lines............................................................................................................................................................11
8 Mounting the module in a 2050-9101 / 2250-9101 FACU...................................................................... 12
9 Field wiring...................................................................................................................................................13
9.1 Connecting to the LAN.......................................................................................................................................................................13
9.2 Connecting to the telephone lines................................................................................................................................................... 13
10 Confirming connection and additional operations...............................................................................14
10.1 Consulting the LEDs......................................................................................................................................................................... 14
10.2 Resetting the module...................................................................................................................................................................... 16
10.3 Accessing Connected Service Gateway..........................................................................................................................................16
10.4 Configuring the APN for a cellular network.................................................................................................................................. 17
10.5 Configuring the DNIS....................................................................................................................................................................... 18
10.6 CSG build upgrade........................................................................................................................................................................... 18

This page is intentionally blank

2050 / 2250 Panels IP Communicator / Connected Services Gateway Module Installation Guide
1 Introduction
This guide describes the procedure to install the IP Communicator (IPC) / Connected Services Gateway (CSG) Module in 2050-9101 and
2250-9101 Fire Alarm Control Units (FACU).
page 3 579-1463 Rev. C

2 Cautions, Warnings, and Regulatory Information
READ AND SAVE THESE INSTRUCTIONS Follow the instructions in this installation manual. These instructions must be followed to avoid
damage to this product and associated equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY Simplex™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect
the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an
authorized Simplex product supplier.
ELECTRICAL HAZARD Disconnect electrical field power when making any internal adjustments or repairs. All repairs should
be performed by a representative or an authorized agent of your local Simplex product supplier.
STATIC HAZARD Static electricity can damage components. Handle as follows:
• Ground yourself before opening or installing components.
• Prior to installation, keep components wrapped in anti-static material at all times.
FCC and Innovation, Science and Economic Development Canada RULES AND REGULATIONS This equipment has been tested
and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
page 4 579-1463 Rev. C
2050 / 2250 Panels IP Communicator / Connected Services Gateway Module Installation Guide

3 Important information
This equipment complies with Part 68 of the FCC Rules. On the side of this equipment is a label that contains, among other information,
the FCC registration number and ringer equivalence number (REN) for this equipment. If requested, this number must be provided to the
Telephone Company.
IP Communicator / Connected Services Gateway Module Product Identifier US: 5QWAL01ACSGM
REN:0.1A
USOC Jack:RJ-31X
Telephone connection requirements
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part
68 rules and requirements adopted by the ACTA. A compliant telephone cord and modular plug is provided with this product. It is designed
to be connected to a compatible modular jack that is also compliant. See installation instructions for details.
Ringer equivalence number (REN)
Use the REN to determine the number of devices that may be connected to a telephone line. Excessive RENs on a telephone line may
result in the devices not ringing in response to an incoming call. In most but not all areas, the sum of RENs should not exceed five. To be
certain of the number of devices that may be connected to a line, as determined by the total RENs, contact the local Telephone Company.
For products approved after July 23, 2001, the REN is part of the product identifier that has the format: US: AAAEQ##TXXXX. The digits
represented by ## are the REN without a decimal point, for example, 03 is a REN of 0.3. For earlier products, the REN is separately shown
on the label.
Incidence of harm
If this equipment causes harm to the telephone network, the telephone company will notify you in advance that temporary discontinuance
of service may be required. If advance notice is not practical, the Telephone Company will notify the customer as soon as possible. Also,
you will be advised of your right to file a complaint with the FCC if you believe it is necessary.
Changes in telephone company equipment or facilities
The Telephone Company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the
equipment. If this happens the Telephone Company will provide advance notice in order for you to make necessary modifications to
maintain uninterrupted service.
Equipment maintenance facility
If you experience trouble with this equipment, contact the facility indicated below for repair or warranty information. If the equipment is
causing harm to the telephone network, the Telephone Company may request that you disconnect the equipment until the problem is
solved. This equipment is of a type that is not intended to be repaired by the end user.
Simplex Time Recorder Co., D/B/A Simplex-US 50 Technology Drive, Westminster, MA. 01441 USA.
page 5 579-1463 Rev. C
2050 / 2250 Panels IP Communicator / Connected Services Gateway Module Installation Guide

Additional information
Connection to party line service is subject to state tariffs. Contact the state public utility commission, public service commission, or
corporation commission for information.
Alarm dialling equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this
even if other equipment, for example telephone, answering system, computer modem and so forth, already has the telephone line in
use. To do so, alarm dialling equipment must be connected to a correctly installed RJ-31X jack that is electrically in series with and ahead
of all other equipment attached to the same telephone line. Proper installation is depicted in the figure below. If you have any questions
concerning these instructions, consult your telephone company or a qualified installer about installing the RJ-31X jack and alarm dialling
equipment for you.
Figure 1: Customer premises equipment and wiring
page 6 579-1463 Rev. C
2050 / 2250 Panels IP Communicator / Connected Services Gateway Module Installation Guide

4 Compatibility
The FACU firmware must be at the correct revision, or higher, to be compatible with the IP Communicator / Connected Services Gateway
Module. See Table 1 for compatible firmware revisions.
Table 1: Compatible FACU firmware
FACU Compatible revision
2050-9101 1.02
2250-9101 1.02
page 7 579-1463 Rev. C
2050 / 2250 Panels IP Communicator / Connected Services Gateway Module Installation Guide

5 Related documentation
You may need to refer to the following additional documentation:
• IP Gateway Cellular Module Installation Guide (579-1248)
• IP Gateway External Box Installation Guide (579-1249)
• 2050 and 2250 Foundation Series Fire Alarm Control Units Operation Guide (579-1405)
• 2050 and 2250 Foundation Series Fire Alarm Control Units Programming Manual (579-1421)
page 8 579-1463 Rev. C
2050 / 2250 Panels IP Communicator / Connected Services Gateway Module Installation Guide

6 Overview
The IPC/CSG provides permanent connected services, central station reporting, or both for FACUs. You can mount the IPC/CSG internally in
the FACU or close-nippled. The IPC/CSG connects using telephone lines, LAN Ethernet, or with a cellular connection.
The IPC/CSG provides the following capabilities:
• Central station reporting features: IP, cellular, and telephone line capabilities (IP Communicator)
• Enterprise server monitoring features: IP and cellular capabilities (Connected Services Gateway)
Use the 2050-9101 / 2250-9101 Panel User Interface or Addressable Panel Programmer Tool to program the IPC/CSG. Refer to 2050 and
2250 Foundation Series Fire Alarm Control Units Operation Guide (579-1405) and 2050 and 2250 Foundation Series Fire Alarm Control Units
Programming Manual (579-1421) for information.
Callout Description
1 Reset switch
2 Port 3: LAN side Ethernet port
3 Ports 1 and 2 Local Ethernet ports
4 P2 power connector
5 P1 serial connector
6 LEDs
7 Configuration switch
8 Screw terminal telephone line connectors
Figure 2: IPC/CSG module
1
3
4
6
5
2
7
9
8
9Optional: Cellular Module, see Table 5
6.1 Specifications
See Table 2 for IPC/CSG module electrical requirements and environmental limitations. The voltage is provided by the FACU.
Table 2: Electrical and environmental specifications
Electrical Specifications
Voltage D.C. Nominal 24 V Battery Powered from auxiliary power
supply.
Current D.C. 125 mA 125 mA 125 mA
Environmental Specifications
Temperature Normal operation with ambient temperature outside the cabinet at 32°F to 120°F (0°C to 49°C).
Humidity Normal operation under non-condensing humidity conditions up to 93% relative humidity at 100.4°F (38°C).
page 9 579-1463 Rev. C
2050 / 2250 Panels IP Communicator / Connected Services Gateway Module Installation Guide

6.2 Central station transmission paths
The module can perform central station reporting. Central station reporting can be configured with one path, or dual paths with a Primary
and Secondary path. The Primary and Secondary paths can be configured to use any of the external connections, telephone line, cellular,
or LAN Ethernet connections. Both IP (cellular and Ethernet) and telephone line connection types can communicate with the Digital Alarm
Communications Receiver (DACR) at the central station. See Table 3 for possible UL combinations.
Packet switched data network interface equipment that is not required for the processing of the signals shall be evaluated to the
applicable requirements of the Standard for Information Technology Equipment – Safety – Part 1: General Requirements, UL 60950-1,
either as burglar alarm equipment or communication equipment. You can configure both communication paths as telephone line.
The IPC/CSG receives system status messages from the host FACU, and communicates the information over the public telephone network
to a DACR at the central station.
The telephone lines do not need to be dedicated to the fire alarm. You can connect the lines to other telecom equipment, but you must
wire the module electrically first in the chain. The Ethernet connections are standard Ethernet that have access to the Internet.
Wire the telephone line connection such that the FACU takes precedence, see Field wiring.
Use the 2050-9101 / 2250-9101 Panel User Interface or Addressable Panel Programmer Tool to configure the module. Refer to the 2050
and 2250 Foundation Series Fire Alarm Control Units Operation Guide (579-1405) , and 2050 and 2250 Foundation Series Fire Alarm Control Units
Programming Manual (579-1421) for information about programming. Central station communications are monitored for integrity.
Table 3: UL allowed path configurations
Scenario Primary path Secondary path
Scenario 1 IP (see Note) IP (see Note)
Scenario 2 Telephone IP (see Note)
Scenario 3 Telephone Telephone
Note: IP can be cellular or wired (1 maximum each).
6.3 Central station receiver protocol support
The following protocols are supported for central station reporting:
Phone line transmission:
• ADEMCO Contact ID Alarm Communication Protocol
IP based transmission (cellular or Ethernet):
• DSC Fibro protocol
6.4 Connected services transmission paths
You can use any IP connection for connected services to the Enterprise Server but you cannot use telephone lines for connected services.
Refer to 2050 and 2250 Foundation Series Fire Alarm Control Units Operation Guide (579-1405) and 2050 and 2250 Foundation Series Fire
Alarm Control Units Programming Manual (579-1421) for information about programming the module for connected services.
page 10 579-1463 Rev. C
2050 / 2250 Panels IP Communicator / Connected Services Gateway Module Installation Guide

7 Getting started
7.1 Reviewing the IP Communicator / Connected Services Gateway PIDs
Confirm that you have everything required to perform the installation. Depending on the connections used for the module, you may need
to order additional parts specified in this section.
The following tables list the PIDs
Table 4: IP Communicator and Connected Services Gateway PIDs
PID Description
2250-9800 Connected Services Gateway and IP Communicator Module, 2050-9101 and 2250-9101 panels
Cellular connections require an optional cellular module kit specified in Table 5. Cellular module kits include antennas. In the case of
poor signal strength at the FACU, you may also require an additional antenna extension kit. For additional information about the cellular
modules and antenna extension kits, refer to IP Gateway Cellular Module Installation Guide (579-1248).
Table 5: Cellular Module PIDs
Cellular module kit description Cellular module kits for external box mounted IPC/CSG modules
AT&T, LTE 4007-6417
For additional mounting options refer to IP Gateway External Box Installation Guide (579-1249).
7.2 Understanding the work flow
This section outlines the possible use cases and work flows. Most steps are explained in further detail in this document. You need
additional documentation to install the cellular module kit, extension antenna, or external box.
Note: Installations do not require all of the following connection options: cellular, Ethernet, and telephone line. Typically, an installation
comprises of two of the connection types listed.
There are two possible installation scenarios. These are as follows:
• FACU with internally installed IPC/CSG
• FACU with externally installed IPC/ CSG in external box
NOTICE: Power off the FACU before mounting or connecting the IPC/CSG.
The process for installing the IPC/CSG internally, or close-nippled, in the FACU is as follows:
1. Mount the IPC/CSG as required.
2. Optional: Mount the cellular module and antenna if required, in external box only
3. Optional: Connect the IPC/CSG to the LAN, or telephone lines if required.
4. Connect the IPC/CSG to the serial port, CPU, and power.
5. Power on the FACU.
To mount the IPC/CSG module or close-nippled, to the FACU, refer to IP Gateway External Box Installation Guide (579-1249).
7.3 Installing the telephone lines
If the installation requires telephone line connection to the central station, ask the telephone company to install the required number of
telephone lines before installing the IPC/CSG. The lines must be terminated with an RJ-31X jack immediately above, or as close as possible
to the FACU. Be prepared to supply the telephone company with the FCC information printed on the FCC or Industry Canada label located
on the IPC/CSG.
CAUTION: Do not direct-connect the IPC/CSG to a coin telephone or party line. Be sure that the telephone lines that you are connecting
the IPC/CSG to are standard analog lines and not digital (PBX), party, or coin telephone lines. The line must not have any Telephone
Company (TELCO) features such as Call Waiting.
page 11 579-1463 Rev. C
2050 / 2250 Panels IP Communicator / Connected Services Gateway Module Installation Guide

8 Mounting the module in a 2050-9101 / 2250-9101 FACU
Mount the IPC/CSG internally in the 2050-9101 / 2250-9101 with supplied studs. The following sections describe the installations.
Alternatively, you can mount the IPC/CSG remotely in the external box. Refer to IP Gateway External Box Installation Guide (579-1249).
1. At the breaker, remove AC power from the control unit. Unlock the panel enclosure, remove the safety cover and disconnect the
battery.
2. Disconnect all harnesses attached to main system board.
3. At the top, unscrew the two #4-40 screws that attach the main system board chassis to the panel enclosure, then remove the main
board chassis assembly and place it at a secure location.
4. Unpack the gateway PCA packaging. It consists of a circuit board, a power cable, a serial cable, four #4-40 screws and four #6-32
screws. You can use the #6-32 screws to mount the gateway circuit board assembly in an external enclosure. You can use the #4-40
screws to mount the gateway circuit board assembly inside the panel.
5. Use the four #4-40 screws to mount the gateway circuit board inside the panel enclosure as shown in Figure 3.
6. Connect one end of the power harness to the connector labeled P1 on the main system board assembly and the other end to the
connector labeled P2 on the gateway board.
7. Connect one end of the serial communication cable to the connector labeled P2 on the main system board and the other end to P1
on the gateway board. Then install the main system board chassis assembly above the gateway board using top two #4-40 screws.
8. After assembly, connect the battery, attach the safety cover, and then at the breaker, apply AC power to verify the gateway installation.
Figure 3: Gateway module mounting location
page 12 579-1463 Rev. C
2050 / 2250 Panels IP Communicator / Connected Services Gateway Module Installation Guide

9 Field wiring
This section describes how to connect to building LAN and telephone lines in order to connect to the central station or the Enterprise
server. Connecting to a service PC to configure the IPC/CSG is also described in this section. For cellular connections, refer to IP Gateway
Cellular Module Installation Guide (579-1248).
9.1 Connecting to the LAN
The LAN Ethernet port on the IPC/CSG are auto-crossover and compatible with 802.3u, 100Base-TX type standard RJ45 type connections.
You do not require crossover cables. Cable requirements are as follows:
• Use Category 5 (CAT5) cable or greater for 100Mbit operation. Using lower grade cables such as Category 3, can result in slower link
speeds, or shorter distances which may affect the performance of your connection.
• The maximum distance from the IPC to the next Ethernet termination, such as the router or switch, is 328 feet (100 meters) with CAT5
cable.
• Cables must conform to the TIA/EIA-568-B standard.
The IPC/CSG can connect to the central station or Enterprise server, through an Ethernet connection to the building LAN. To connect to the
LAN, do the following:
1. Insert an Ethernet cable into port 3 of the IPC/CSG.
2. Insert the other end of the Ethernet cable into an Ethernet port connected to the building LAN.
NOTICE: Do not connect the LAN to port 1 or port 2. Connecting to port 1 or port 2 is a security risk. It will also cause disruption to the
building LAN.
LAN configuration is DHCP by default. If you require static IP configuration, refer to the 2050 and 2250 Foundation Series Fire Alarm Control
Units Programming Manual (579-1421) and 2050 and 2250 Foundation Series Fire Alarm Control Unit Operation Guide (579-1405).
9.2 Connecting to the telephone lines
For installations where the IPC/CSG shares the telephone line with telephones on the premises or other equipment, make the connection
to the RJ-31X jacks through the modular jack. Use 2080-9047 harnesses for this connection. The harnesses are not included.
Note: The telephone company must install the telephone lines before installation. See Installing the telephone lines for more information.
To connect to the central station using a telephone line (IP Communicator only), complete the following steps:
1. Connect the 2080-9047 harness to the screw terminals on the IPC/CSG.
2. Use cable tie-wraps to provide strain relief for the two telephone line harnesses. Secure the cables to any standoff, or metal fixture
along the cable run between the IPC/CSG and the FACU exit.
Note: The two telephone line harnesses take separate paths from the host FACU to the RJ-31X blocks.
3. Connect one harness to each RJ-31X jack.
Note: TELCO wiring is supervised.
Table 6: PCB reference designators and descriptions
Pin Name Description / Connection
8 T1 Line Tip Connection to POTS Line 1
7 R1 Return Ring Connection to POTS Line 1
6 T2 Line Tip Connection to POTS Line 2
5 R2 Return Ring Connection to POTS Line 2
4 T1A N.C.
3 R1A N.C.
2 T2A N.C.
Figure 4: Telephone connection terminal block on the module
1 R2A N.C.
To configure with a 2050 or 2250 panel, refer to 2050 and 2250 Foundation Series Fire Alarm Control Unit Operation Guide (579-1405).
page 13 579-1463 Rev. C
2050 / 2250 Panels IP Communicator / Connected Services Gateway Module Installation Guide

10 Confirming connection and additional operations
The LED behavior, enabling Manual Configuration Mode, and resetting the IPC/CSG are explained in this section.
After installing the IPC/CSG, consult the LEDs on the IPC/CSG, cellular module, and any Ethernet ports in use to confirm that the
connections are successful. See Figure 5 for the locations of the LEDs and Ethernet ports.
Note: If a CSG is mounted externally, the LEDs are visible and the reset switch is accessible. If mounted inside a 2250 or 2050 panel, it is
not required to use them.
10.1 Consulting the LEDs
To confirm the IPC/CSG is connected and operating correctly consult the following tables:
Table 7 System Status LEDs
Table 8 Panel (FACU) Communications LEDs
Table 9 Central Station Communications LEDs
Table 10 Phone line LEDs
Table 11 Cellular LEDs
Table 12 Ethernet port LEDs
Figure 5: Location of LEDs on the module
Table 7: System Status LEDs
Status Green LED Red LED
No power Off Off
Power connected: software not running On On
Power connected: software booting On Off
IPC/CSG application running Blinking Off
Software controlled restart On Off
Manual reset On On
Complete system failure, IPC/CSG application is not running On On
page 14 579-1463 Rev. C
2050 / 2250 Panels IP Communicator / Connected Services Gateway Module Installation Guide

Table 8: Panel (FACU) Communications LEDs
Status Green LED Yellow LED
Normal: connected to the FACU On Off
Not connected with the FACU: communication failure with FACU Off On
Mismatch Off Blinking
Table 9: Central Station LEDs
Status Green LED,
primary path
indicator
Yellow LED,
secondary path
indicator
Primary path, Secondary path both up On On
Primary up, Secondary path down On Off
Primary down, Secondary path up Off On
Primary up, Secondary path as none On On
Primary down, Secondary Path as none Off On
Both paths down Off Off
Table 10: Phone Line LEDs
Status Green LED Yellow LED
Normal On Off
Telephone line in use Blinking Off
Telephone line is not connected, or not functional. Off Blinking
Hardware fault Off On
Disabled Off Off
Note: The function of the LEDs for both telephone lines is identical.
Table 11: Cellular LEDs
Status Green LED #11 Green LED #14 Yellow LED #15
High quality signal On On Off
Moderate quality signal On Blinking Off
Low quality signal On Off Off
Very poor quality signal Blinking Off Off
Not connected Off Off Blinking
Fault / error Off Off On
Disabled Off Off Off
Table 12: Ethernet port LEDs
Status LED behavior
Link up On
Activity Blinking
Not connected Off
page 15 579-1463 Rev. C
2050 / 2250 Panels IP Communicator / Connected Services Gateway Module Installation Guide

10.2 Resetting the module
Use the reset button to perform software and hardware resets for the IPC/CSG. See Figure 6 to locate the reset button. To perform a reset,
do one of the following:
1. To perform a software reset, momentarily press the reset button.
2. To perform a hardware reset, press and hold the reset button for three seconds.
Figure 6: Location of reset button on the module
10.3 Accessing Connected Service Gateway
1. Connect the Gateway's panel interface Ethernet port, named Panel P1-2 port with the local PC by an Ethernet cable.
2. Apply power to the CSG from a suitable 24 V power supply from Panel P1 (PWR).
3. Set the Personal Computer's / Laptop's IP address to DHCP as shown in the following image.
Figure 7: IPv4 properties
page 16 579-1463 Rev. C
2050 / 2250 Panels IP Communicator / Connected Services Gateway Module Installation Guide

4. Open browser Mozilla Firefox or Google Chrome and enter CSG URL tgm-x1x2x3.local/ to load the gateway's webpage. The URL is
labeled (Name : tgm -AAAAAA.local ) on the Gateway board as in the following image.
Figure 8: Label
10.4 Configuring the APN for a cellular network
1. Click on the Network tab and select Cellular modem configuration, see the following figure.
Figure 9: Cellular modem configuration
2. Select or enter the new correct APN for the SIM used in the CSG.
3. Click on the Apply button, restart the CSG
page 17 579-1463 Rev. C
2050 / 2250 Panels IP Communicator / Connected Services Gateway Module Installation Guide

10.5 Configuring the DNIS
1. Click on the Network tab and select DNIS configuration, see the following figure.
Figure 10: DNIS configuration
2. Enter the new DNIS value for Primary and Secondary Path.
3. Click on the Save button.
4. Reconfiguration CSG or restart the CSG
10.6 CSG build upgrade
1. Click on the Update tab, see the following figure.
Figure 11: Update CSG firmware
2. Click on the Choose File button and select the new CSG build files.
3. Click on the Submit button.
4. CSG updates and restarts automatically.
page 18 579-1463 Rev. C
2050 / 2250 Panels IP Communicator / Connected Services Gateway Module Installation Guide
Other manuals for 2050
2
This manual suits for next models
3
Table of contents