4
Use Figure 2 and the notes below to wire the 24-Point I/O card.
REMOTE
PWR
+++C
24C
+24V
1+
1RET
2+
2RET
SHLD
SHLD
++--
N2 COMM
TB5 TB2 TB3 TB1
TB4
P2
P1
SW1
SW2
ADDRESS
N2
DR1 DR2 DR3 DR4 DR5 DR6 DR7 DR8 DR9 DR10 DR11 DR12 DR13 DR14 DR15 DR16 DR17 DR18 DR19 DR20 DR22DR21 DR23 DR24
1
226
1
2
I/O
TYPICAL LED
OUTPUT
TYPICAL LAMP
OUTPUT
Figure 2. 24-Point I/O Wiring
Wiring
24-Point I/O Wiring
24V (C)
24V (+)
Remote Power (C)
Remote Power (+)
See Notes 3 and 11
N2 Comm (-)
N2 Comm (+) See Note 7
See Note 4
See Note 10
Notes:
1. All wiring to be 18AWG minimum or to local
code.
2. Conductors must test free of all grounds.
3. Voltage input 18.9VDC min. to 32VDC max.
4. Maximum current is 75mA per output.
5. Drawing depicts typical wiring. All output
zones may not be wired. Supervision for the
unused inputs are by-passed in software.
6. Wiring is supervised and Power-Limited.
7. For N2 Comms wired in a “bus” fashion, the
maximum line distance is 4000 ft. For N2
Comms wired in a T-Tapped configuration,
the maximum distance to any N2 device is
2500 ft, with maximum total wire distance
not to exceed 10,000 ft on the T-tapped lines.
If the 24 Point I/O is the last device on the N2
bus (Non-T-Tapped), or the furthest device
(T-Tapped) terminate across N2+ and N2-
using a 733-974 (100
:
:
, 1/2W) resistor
harness.
8. Total current = 60mA base controller current.
Add current for each output used.
9. Wiring to I/O terminals must not be run with
AC wiring.
10. Alternate Ribbon Cable for TB4:
TB4-1 P2-1 TB4-13 P2-13
TB4-2 P2-2 TB4-14 P2-14
TB4-3 P2-3 TB4-15 P2-15
TB4-4 P2-4 TB4-16 P2-16
TB4-5 P2-5 TB4-17 P2-17
TB4-6 P2-6 TB4-18 P2-18
TB4-7 P2-7 TB4-19 P2-19
TB4-8 P2-8 TB4-20 P2-20
TB4-9 P2-9 TB4-21 P2-21
TB4-10 P2-10 TB4-23 P2-22
TB4-11 P2-11 TB4-23 P2-23
TB4-12 P2-12 TB4-24 P2-24
11. Allowable power supplies: 4010-9101, -9102,
-9201, -9202, -9813, and -9814 or any
regulated Power-Limited supply that is UL
Listed for Fire Protective Signal Use.