HOW TO RESET THE SYSTEM
1. When the alarm condition has been cleared, restore or
replace all affected devices in accordance with the
instructions provided with each device (smoke detector,
motion sensor, etc.).
2. Reset the system.
• FIREALARMCondition:Pressthe<SYSTEMRESET>
key.
• PRIORITY 2 ALARM Condition: Open the Operator
Interface Panel access door and press the <PRIORITY
2 ALARM RESET> key on the programmable CON-
TROL Key Panel. (The CONTROL Key Panel is located
on the far left of the Operator Interface Panel.)
After a short delay, the system will return to normal and dis-
play the following message.
SYSTEM IS NORMAL
9:27:40SAT 27 SEP 97
© 1997 Simplex Time Recorder Co., Gardner, MA01441-0001 U.S.A.
574-026Rev. A
All specifications and other information shown were current as of publication, and are subject to change without notice.
4100+ OPERATING INSTRUCTIONS FOR FIREFIGHTER’S AUDIO SYSTEM
(SINGLE CHANNEL AUDIO)
HOW TO OPERATE MIKE
ON =UP NORMAL=CENTER OFF=DOWN
(SPEAKER SELECT SWITCH OPERATION)
ALL
SPEAKERS
EVAC
SELECTIVE
EVAC
ALL
SPEAKERS
TALK
LOCAL
SPEAKER
PHONE PIEZO
SILENCE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
4100+ MAIN CONTROL PANEL
ALARM
SILENCE
TALK
LED
MIKE TALK
SWITCH
OPERATION SELECT
SWITCHES SPEAKER SELECT
SWITCHES PHONE SELECT
SWITCHES PHONE SELECT
SWITCHES
EVAC
LOCAL
SPEAKER
ALERT
FLR 1
FLR 2
FLR 3
FLR 4
FLR 5
FLR 6
FLR 7
FLR 8
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
1
2
3
7
6
5
4
8
9
10
11
12
13
14
15
KEY
ALARM SILENCED
LED
HOW TO SILENCE FIRE ALARM SIGNALS
CAUTION
Pressing ALARM SILENCE key silences evacuation tone/
message and lights the ALARM SILENCED LED.
1. To silence alarm evacuation signals, press Main Panel’s
ALARM SILENCE key.
HOW TO INITIATE AN EVACUATION SIGNAL
1. TO EVACUATE ALL AREAS: Flip up ALL SPEAKERS
EVAC switch.
TO EVACUATE SPECIFIC AREAS: Flip up all desired
Speaker Select Switches; then flip up SELECTIVE EVAC
switch.
2. To make an announcement over mike, see HOW TO
OPERATE MICROPHONE instructions shown above.
3. When finished, flip down ALL SPEAKERS EVAC switch.
HOW TO OPERATE MICROPHONE
1. To make an announcement with mike:
TO ALL AREAS: Flip up ALL SPEAKERS TALK switch.
TO SPECIFIC AREAS: Flip up all desired Speaker Select
Switches.
TO AREA IN ALARM: Go to step 2.
2. Remove mike from enclosure and press Mike Talk Switch.
• Turns off any active tone or message.
3. Wait for Talk LED to go on.
4. Make appropriate announcement.
• Releasing Mike Talk Switch restarts tone or message if
alarm exists.
5. When finished, flip down ALL SPEAKERS TALK switch
and all activated Speaker Select Switches. Then replace
the mike.
HOW TO USE LOCAL SPEAKER SWITCH
(Plays active tone/message on panel speaker)
1. Flip up LOCAL SPEAKER switch.
2. When finished, flip down LOCAL SPEAKER switch.
NOTE:
IF YOUR SYSTEM SWITCH CONFIGURATION DOES NOT
MATCHTHISSHEET, CONSULTSIMPLEXFOR SPECIFIC
OPERATIONS. SIMPLEX IS LISTED IN THE YELLOW
PAGES.
PHONE OPERATION
1. When remote phone is plugged in or remote handset is
lifted:
• Ring signal is heard on handset.
• Phone LED flashes at panel.
• Tone sounds at panel.
2. Pick up master phone.
3. To connect phone, flip up Phone Select Switch next to
flashing LED.
• Handset ring signal goes off.
• Flashing LED turns on steady.
• Panel tone is turned off.
4. Use master phone as required.
5. Repeat steps 3 and 4 if another remote handset is lifted
or phone is plugged in.
To silence the tone without connecting the remote phone,
flip up PHONE PIEZO SILENCE switch.
6. When finished, hang up master phone and flip down
Phone Select Switches.
• Remote phone must be unplugged or remote handset
replaced. (If remote phone is off hook more than 10 sec-
ond, panel tone re-sounds and LED flashes.)
THESE INSTRUCTIONS ARE INTENDED TO BE FRAMED AND
MOUNTED ADJACENT TO THE CONTROL PANEL FOR READY REFERENCE
See Operator’s Instruction Manual for detailed operation
IN CASE OF TROUBLE, NOTIFY:
NAME:
ADDRESS:
PHONE NO.:
TITLE:
YOUR SAFETY AND THE SAFETY OF
Actions taken during a fire depend upon local practices.
Be sure you know what to do.
HOW TO OPERATE PHONE
FIRE
FIRE
RED FIRE ALARM LED
FIRE ALARM
ACKNOWLEDGE
KEY
THOSE AROUND YOU ALWAYS COMES FIRST!
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

HOW TO RESET THE SYSTEM
1. When the alarm condition has been cleared, restore or
replace all affected devices in accordance with the
instructions provided with each device (smoke detector,
motion sensor, etc.).
2. Reset the system.
• FIREALARMCondition:Pressthe<SYSTEMRESET>
key.
• PRIORITY 2 ALARM Condition: Open the Operator
Interface Panel access door and press the <PRIORITY
2 ALARM RESET> key on the programmable CON-
TROL Key Panel. (The CONTROL Key Panel is located
on the far left of the Operator Interface Panel.)
After a short delay, the system will return to normal and dis-
play the following message.
SYSTEM IS NORMAL
9:27:40SAT 27 SEP 97
© 1997 Simplex Time Recorder Co., Gardner, MA01441-0001 U.S.A.
574-026Rev. A
All specifications and other information shown were current as of publication, and are subject to change without notice.
4100+ OPERATING INSTRUCTIONS FOR FIREFIGHTER’S AUDIO SYSTEM
(DUAL CHANNEL AUDIO)
HOW TO OPERATE MIKE
UP =ON/EVAC DOWN=ON/TALK/ALERT CENTER=OFF/AUTO
(SPEAKER SELECT SWITCH OPERATION)
ALL
SPEAKERS
EVAC
SELECTIVE
EVAC
ALL
SPEAKERS
TALK
LOCAL
SPEAKER
PHONE PIEZO
SILENCE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
PHONE
4100+ MAIN CONTROL PANEL
ALARM
SILENCE
TALK
LED
MIKE TALK
SWITCH
OPERATION SELECT
SWITCHES SPEAKER SELECT
SWITCHES PHONE SELECT
SWITCHES PHONE SELECT
SWITCHES
EVAC
LOCAL
SPEAKER
ALERT
FLR 1
FLR 2
FLR 3
FLR 4
FLR 5
FLR 6
FLR 7
FLR 8
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
CIRCUIT
1
2
3
7
6
5
4
8
9
10
11
12
13
14
15
KEY
ALARM SILENCED
LED
HOW TO SILENCE FIRE ALARM SIGNALS
CAUTION
Pressing ALARM SILENCE key silences evacuation tone/
message and lights the ALARM SILENCED LED.
1. To silence alarm evacuation signals, press Main Panel’s
ALARM SILENCE key.
HOW TO INITIATE AN EVACUATION SIGNAL
1. TO EVACUATE ALL AREAS: Flip up ALL SPEAKERS
EVAC switch.
TO EVACUATE SPECIFIC AREAS: Flip up all desired
Speaker Select Switches; then flip up SELECTIVE EVAC
switch.
2. To make an announcement over mike, see HOW TO
OPERATE MICROPHONE instructions shown above.
3. When finished, flip down ALL SPEAKERS EVAC switch
and flip to center position all activated Speaker Select
Switches. Then replace mike.
HOW TO OPERATE MICROPHONE
1. To make an announcement with mike:
TO ALL AREAS: Flip up ALL SPEAKERS TALK switch.
TO SPECIFIC AREAS: Flip down all desired Speaker
Select Switches.
2. Remove mike from enclosure.
3. Press Mike Talk Switch.
• Wait for Talk LED to go on.
4. Make appropriate announcement; then release Mike Talk
Switch.
5. When finished, flip down ALL SPEAKERS TALK switch
and flip to center position all activated Speaker Select
Switches. Then replace the mike.
HOW TO USE LOCAL SPEAKER ALERT SWITCH
(Plays active tone/message on panel speaker)
1. Flip up LOCAL SPEAKER ALERT switch.
2. When finished, flip down LOCAL SPEAKER ALERT
switch.
HOW TO USE LOCAL SPEAKER EVAC SWITCH
(Primary audio channel to panel speaker)
1. Flip up LOCAL SPEAKER EVAC switch.
2. When finished, flip down LOCAL SPEAKER EVAC switch.
PHONE OPERATION
1. When remote phone is plugged in or remote handset is
lifted:
• Ring signal is heard on handset.
• Phone LED flashes at panel.
• Tone sounds at panel.
2. Pick up master phone.
3. To connect phone, flip up Phone Select Switch next to
flashing LED.
• Handset ring signal goes off.
• Flashing LED turns on steady.
• Panel tone is turned off.
4. Use master phone as required.
5. Repeat steps 3 and 4 if another remote handset is lifted
or phone is plugged in.
To silence the tone without connecting the remote phone,
flip up PHONE PIEZO SILENCE switch.
6. When finished, hang up master phone and flip down
Phone Select Switches.
• Remote phone must be unplugged or remote handset
replaced. (If remote phone is off hook more than 10 sec-
onds, panel tone re-sounds and LED flashes.)
THESE INSTRUCTIONS ARE INTENDED TO BE FRAMED AND
MOUNTED ADJACENT TO THE CONTROL PANEL FOR READY REFERENCE
See Operator’s Instruction Manual for detailed operation
IN CASE OF TROUBLE, NOTIFY:
NAME:
ADDRESS:
PHONE NO.:
TITLE:
YOUR SAFETY AND THE SAFETY OF
Actions taken during a fire depend upon local practices.
Be sure you know what to do.
HOW TO OPERATE PHONE
FIRE
FIRE
RED FIRE ALARM LED
FIRE ALARM
ACKNOWLEDGE
KEY
NOTE:
IF YOUR SYSTEM SWITCH CONFIGURATION DOES NOT MATCH THIS SHEET, CONSULT SIMPLEX
FOR SPECIFIC OPERATIONS. SIMPLEX IS LISTED IN THE YELLOW PAGES.
THOSE AROUND YOU ALWAYS COMES FIRST!