VENTING REQUIREMENTS
If the boiler vent is to be installed into a natural draft
masonry chimney or Type “B” venting, it must be in
accordance with Part 7, Part 11 and Appendix G, of the
National Fuel Gas Code, ANSI Z223.1 and CSA B149.1-00 for
natural gas and propane.
For a masonry vitreous tile-lined chimney which is not
exposed to the outdoors, use Table 1 in this Slant/Fin
manual for venting requirements. DO NOT install this
system into an unlined masonry chimney.
If a masonry chimney is exposed to the outdoors on one or
more sides below the roof line (exposed chimney), it must
be re-lined with a UL listed metallic liner system. See Table
2 in this Slant/Fin manual for venting requirements of
metallic re-lined chimneys.
If a Type “B” vent system is used, it must NOT be exposed
to the outdoors below the roof line. See Table 2 in this
Slant/Fin manual for venting requirements. Vent
connectors serving appliances vented by natural draft shall
NOT be connected into any portion of mechanical draft
systems operating under positive pressure. Single or
multiple appliance venting is shown in Figures 13 and 14.
The 76mm to 127mm (3” to 5”) vent adapter MUST be used
on the vent collar of ALL models of the Concept boiler for
these installations. In some cases, the vent connector
diameter must be upsized further to 152mm or 178mm (6”
or 7”). Refer to Table 1 and 2 for installations requiring this
increased size.
Standard vent connector materials such as galvanized or
stainless steel are allowed for these installations. NO types
of plastic material can be used as a part of the venting
system in any installation.
All Concept boilers require a condensate drain and drain
trap. Vent connectors must be liquid tight.
The condensate drain should be installed as close to the
boiler as possible and must be equipped with a trap formed by
attaching 9mm (3/8") I.D. clear plastic tubing to the drain
assembly, making a loop approximately 102mm (4") diameter
and securing with cord or a tie wrap where the loop crosses
over itself. This loop should then be filled with water to form a
liquid filled trap. DO NOT OPERATE THE BOILER WITHOUT
INSTALLING THIS TRAP AND FILLING WITH WATER. Periodic
inspection should be made of this assembly for deterioration
of the tubing and to insure that the trap is filled with water, but
not plugged. If it is plugged or appears to have excessive
sediment in it, it should be removed from the drain assembly,
straightened out to clear the obstruction, reformed, filled with
water and reinstalled as before. The drain should extend to a
floor drain or to a plastic container which may require
emptying periodically.
Category I Venting Requirements
BOILER ROOM AIR SUPPLY AND VENTILATION
An ample supply of air is required to obtain combustion
and ventilation. When buildings are insulated, caulked and
weather-stripped, now or later on, direct openings to
outside may be required and should be provided. If the
boiler is not near an outside wall, air may be ducted to the
installation area from outside wall openings.
Provisions for combustion and ventilation air must be made
in accordance with section 5.3, Air for Combustion and
Ventilation,of the National Fuel Gas Code, ANSI Z223.1 and
CSA B149.1-00 for natural gas and propane, or applicable
provisions of the local building codes. The following
recommendation applies to buildings of energy-saving
construction, fully caulked and weather stripped:
Provide one GRILLED opening near the floor and one near th
ceiling on an outside wall near the boiler (or duct from suc
openings to the boiler), EACH opening to be a minimum o
645 mm2 (one square inch) per 586w (2000 Btuh) input to AL
APPLIANCES in the area. For a total appliance input of 58,620w
(200,000 Btuh), each opening will be 64 516mm2 (100 squar
inches). A grilled opening 254mm x 254mm (10"X10") ha
64 516mm2(100 square inches) of area. If fly screen must b
used over openings, double the area and inspect and clea
the screen frequently.
Openings must never be reduced or closed. If doors o
windows are used for air supply, they must be locked open
Protect against closure of openings by snow and debris
Inspect frequently.
No mechanical draft exhaust or supply fans are to be used
in or near the boiler area.
The flow of combustion and ventilating air to the boile
must not be obstructed.
The air inlet passage hole located on the top of the boile
jacket should be left covered with the plate provided, to
prevent debris from falling into the air intake.
On all Category I installations, the air pressure switch provided
on the boiler must be replaced with the switch provided in ven
kit 665194. This switch is set to prevent the boiler from
operating below the approved Category I input rate.
12