NOTICE: INSTALLATION AND SERVICE MUST BE
PERFORMED BY A QUALIFIED HEATING CONTRACTOR
The installation must conform to the requirements of
the National Fuel Gas Code ANSI Z223.1 and CSA
B149.1-00 for natural gas and propane for Gas Burning
Appliances and Equipment, and the requirements of the
authority having jurisdiction as well as the requirements
in this instruction manual. In addition, where required by
the authority having jurisdiction, installation must
conform to the Standard for Controls and Safety Devices
for Automatically Fired Boilers, ANSI/ASME CSD-1. If
there is any conflict in the above requirements, then the
more stringent requirement will apply.
BOILER LOCATION
Structure through which venting will pass must be free
and clear for opening (i.e. no hidden conduit, telephone
cables or other obstructions).
Boiler location should be such that the gas ignition
system components are protected from water (dripping,
spraying, rain, etc.) during appliance operation and
service (circulator replacement, condensate trap, control
replacement, etc.).
For a closet installation, ventilation openings must be
provided through a door or wall to prevent excessive
heat build-up. Two openings, one near the floor and one
near the ceiling, should be sized to assure sufficient air
circulation in the closet (minimum 64,516mm2[100 sq.
inches] each).
WARNING
LIQUEFIED PETROLEUM (L.P.) PROPANE FIRED
GAS BOILER LOCATION
REQUIRES SPECIAL ATTENTION
Liquefied Petroleum (L.P.) propane gas is heavier than
air. Therefore, propane boilers, piping, valves must NOT
be installed in locations where propane leaking from
defective equipment and piping will "pool" in a basement
or other space below the leak.
A spark or flame from the boiler or other source may
ignite the accumulated propane gas causing an
explosion or fire.
Provide a level, solid foundation for the boiler. Location
should be as near the chimney as possible so that the
flue pipe from boiler to the chimney is short and direct.
The UNIFORM MECHANICAL CODE may be in effect
in your geographic area.
The following precautions are cited by the 1994
UNIFORM MECHANICAL CODE, section 304.6 or CSA
B149.1-00 for natural gas and propane.
“LPG Appliances. Liquefied petroleum gas-burning
appliances shall not be installed in a pit, basement
or similar location where heavier-than-air-gas might
collect. Appliances so fueled shall not be installed in
an above-grade under-floor space or basement
unless such location is provided with an approved
means for removal of unburned gas.”
Consult Chapter 5 of the 1994 UNIFORM MECHANICAL
CODE for design criteria of the "approved" means for
removal of unburned gas.
SAFETY—
KEEP THE BOILER AREA CLEAR AND FREE FROM
COMBUSTIBLE MATERIALS, GASOLINE AND OTHER
FLAMMABLE VAPORS AND LIQUIDS.
BOILER FOUNDATION
A. Provide a solid, level foundation, capable of
supporting the weight of the boiler filled with water,
and extending at least 51mm (2") past the jacket on
all sides. See dimensions of boilers, page 2.
B. Boiler can be installed on both combustible and non-
combustible floors, but must NOT be installed on or
above carpeting.
C. If boiler is to be located over buried conduit
containing electric wires or telephone cables, consult
local codes or the National Board of Fire Underwriters
for specific requirements.
MINIMUM CLEARANCES
A. Minimum clearances to the exterior surfaces of the
boiler shall be as follows:
MINIMUM ALCOVE AND CLOSET CLEARANCE.
B. Provide 457mm (18") on sides used for passage.
For Combustible Recommended
Surface Construction for Service
Front 51mm (2") 457mm (18")
Rear 51mm (2") 203mm (8")
Left Side 51mm (2") 457mm (18")
Right Side 51mm (2") 457mm (18")
Top 254mm (10") 254mm (10")
Flue Connector 76mm (3") 152mm (6")
C. All minimum clearances shown above must be met.
This may result in increased values of some
minimum clearances in order to maintain the
minimum clearances of others.
D. Clearance from hot water pipes shall be
25mm (1") **.
** At points where hot water pipes emerge from a
floor, wall or ceiling, the clearance at the opening
through the finished floor boards or wall or ceiling
boards may not be less than 13mm (1/2"). Each
such opening shall be covered with a plate of
noncombustible material.
3
INSTALLATION REQUIREMENTS