INSTALLATION INSTRUCTIONS
MALIBUOIL FIRED CAST IRON BOILER
MODELS M-100THROUGH M.250.
LOCATION: Mount the baler near tho ch~mneyto keep the
flue plpec js short as poss~ble.Bo~lermust be mounted
on a level Il?ur,dat~onInstall on non-combust~blefloor
only
3.
Removeobstructions.
4
Replace worn sections of metal stacks.
5.
Seal bad masonry jolnts.
6
Repa~rdamaged linings
AIR SUPPLY: C. Where more than one appliance vents into a com-
monchimney, the area of the common flue should
A.
Enclosed boiler room having normal tight
construe-
at least equal the area of the largest flue plus 50%
tlon requlres two unobstructedopenings for passage of the add~tionalflueareas.
of air into the boiler room. D. Ch~mneyheight shall extend at least
3
feet above
1.
Air drawn vertically from outdoors; One openlng
on floor and one opening on ceiling each w~tha where
~t
passes through the roof of a building, and
minimum free air passagearea of 1square Inch at least 2 feet above any r~dgewithin 10 feet of the
per
4000
Btuh of total system ~nput. Ch~mney.
2.
Air drawn
horizontally
from outdoors through an
outslde wall; One louvredopenlng near the floor
(below burner air ~nlet)and one louvredopening
near the ceiling (abovethe highest draft regula
tor or draft hood rellef open~ngs),each opening
with a minimum free air passage area of 1
square inch per
2000
Btuh of total system input.
3.
Alr drawn from Insidethe bu~ldlng;One opening
near the floor (below burner air inlet)and one
openlngnear the celling (abovethe highest draft
regulator or draft hood relief open~ngs),each
openlng with a mlnlmum free air passage area of
1square inch per 1000 Btuh of total system
input
B.
If
boilers are installed adjacent to other fuel burning
equipment, the area of free openings must
be
appropriately increased to accommodate the addi.
tional load
E. Vent connector lnto chimney must be same size as
breeching outlet.
F. Vent connector should be Inserted into, but not
beyond Inside of chimney liner.
Q.
CAUTION-UNIT SHALL BE CONNECTEDTO A
FLUE HAVING SUFFICIENT DRAFT AT ALL TIMES,
TO ASSURE SAFE PROPER OPERATION OF THE
UNIT.
ELECTRICALSUPPLY: Electrical wlring and equ~pment
should be installed in accordance with CSA Standard
C22.1,
and Canadian
Electrical
Code, part 1and any
local codes having jur~sdiction
FUEL OIL SUPPLY:
011
piping should be a minimum of
tube A manual shut-off valve must be installed as
close as posslble to the oil storage tank. An oil filter of
C. Unless properly controlled, avo~dthe use of forced capaclty larger than the fir~ngrate of the burner should
ventilation, since it can create an undesirable pres-
be
Installed
011
plplng should be protected
:rcv
k~nk~ng
sure differentla1between boiler room and air source. or other damage
'For further details refer to C.G.A.Standard B 149.1
InstallationCode For Gas.
FLUE CONNECTION: Connect flue p3pebetween top of
the boiler and chimney.
Horizontal
sectlons of the flue
pipe must
be
pltched upward to the ch~mneyat least
'/r"
per foot. The breech~ngshould not exceed 10 ft. of how
zontal length The flue pipe should be cemented lnto the
thimble uslng asbestos shorts The thlmble should be
flush with the lns~desurfaceof the flue l~nerand the
flue pipe should not extend beyond th~spolnt Install
the draft regulator In the fluep~pe.as shown In the
separate ~nstructlonssheet lnslde the draft regulator
carton
CHIMNEY REOUIREMENTS
6
DIMENSIONS:Refer to
data on page
2
of
this
manual
A.
A vitreous tile lined ch~mneyof the slze shown on
Page
2
is recommended Local codes apply.
B.
Check ch~mneycond~tron
Exist~ngch~mneysand stacks may have deterlorat.
ed; without repalrs the11use would be hazardous
Before
connecting
to an oid ch~mneyor stack
1 Clean
11
2.
Inspect
~t
thorodgh!y
If the oil tank
IS
~nstalledabove or on level with the
burner,a one pipe s~nglestage o~lsystem may be used.
If the
011
tank
IS
~nslalledbelow the burner,a two pipe
s~nglestage
011
system may have to be used. If the total
lift is more than
8
feet, a two plpe,two stage fuel system
must be used.
If
a boosler pump
IS
used care should be taken to see
that the pressure orr the Inlet s~deofthe burner fuel un~t
does not exceed
8
PS I
G
FLOW CONTROL VALVE: When domest~chot water
tankless healer
IS
used a flow control valve should be
Installed In the supplv plplng as shown In the ~llustra-
t~on
MINIMUM CLEARANCES: Above
30"
Front
24"
Rear
18"
S~des
18"
Flue Plpe 18 inches
AOUASTAT SETTINGS: Low
ltrnlt
should be set at least
20" below
Ihe
htgh llmlt sett~ng
PRESSURE CONTROL SETTING: Recommended h~gh
l1m11sett~ng1s
10
P
S
I
G
The h~ghl~m~tsett~ngshould
never exceed
15
P
S
I
G
3