RS485 Surge Protection Kit for HD-Wave Installation Guide - MAN-01-00476-1.0
RS485 Surge Protection Kit for Single Phase HD-Wave
Inverter - Installation Guide
This document describes how to install the RS485 Surge Protection Kit in the SolarEdge single phase HD-Wave inverter.
Kit Contents
Surge protection board
Standoff
Installation Procedure
1Turn the inverter ON/OFF switch to OFF. The LCD display should indicate that the string voltage is in the safety voltage
range (< 50V).
2Disconnect the AC to the inverter by turning OFF the circuit breakers on the distribution panel.
3Open the cover’s six Allen screws and carefully remove the cover.
4Do one of the following:
For a new RS485 connection installation, disconnect the 6-pin connector from the surge protection board, and connect the
RS485 wires to the G, A, and B terminals to the 6-pin connector (see Figure 1).
Figure 1: RS485 6-Pin Connector
If RS485 connection is already installed in the inverter, disconnect the 6-pin connector from the RS485 socket on the
inverter communication board (see Figure 2), leaving the RS485 wires intact.
Figure 2: RS485 Connection in the inverter