Sontex Supercal 5 I User manual

Instruction for use
Supercal 5 I

2Instruction for use | Supercal 5
Read this manual thoroughly before using the calculator.
Be sure to read the “Safety” section (page 10) to ensure proper use of the
calculator.
After reading this manual, keep it in an easily accessible place so that it is ready
for future reference.
Legal Provisions
The information contained in this document is the property of Sontex SA. Publication, in
whole or in part, requires the written consent of Sontex SA. Any internal reproduction in-
tended for evaluation of the product or its proper use is permitted and not subject to au-
thorisation.
Warranty
Please contact your local Sontex representative for warranty information.
Trademark
M-Bus is a European standard (EN 13757-2/3) for reading heat meters.
Modbus® is a registered trademark of Schneider Electric and is licensed by the Modbus
Organiza-tion, Inc.
BACnet® is a registered trademark of the American Society of Heating, Refrigerating and
is availa-ble at the following link:
http://www.bacnetinternational.net/btl/index.php?m=269

3Instruction for use | Supercal 5
Table of Contents
1. Notes on This Document 7
1.1 Scope of Validity 7
1.2 Target Groups 7
1.3 Storage of Document 7
1.4 Further Information 7
1.5 Symbole 8
2. Security 9
2.3.2 Operational safety 10
2.3.3 Product Safety 10
3. Description 11
3.1.1 Nameplate 11
3.1.1 Scope of Delivery 13
3.3.1 CE-Symbol 13
4. Installation 14
4.1 Acceptance of Goods 14
4.2 Transporting and Storing the Calculator 14
4.3 Checking the Scope of Deliver 14
4.4 Structure and Components of the Calculator 14
4.4.1 Calculator Upper Part 15
4.4.2 Calculator Lower Part 15
4.5 Dimensions 16
4.6 Mounting 16
4.6.1 Before Mounting 16
4.6.2 Wall Mounting 17
4.6.3 Top Hat Rail Mounting 18
4.7 Installation Instructions For Temperature Sensors 18
4.7.2 Connection of 4-Wire Temperature Sensor 20
4.7.2.1 Wire Cable Sensor with 2-Wire Calculator 20
4.7.3 Installation Guidelines for Temperature Sensors According to EN1434 21
4.7.3.1 Compliance With the Operating Conditions According to MID for the
Temperature Sensors 21
4.8 Installation Check 21
5. Wiring 23
5.1 Wiring Requirements 23
5.2 Opening the Calculator 23
5.3 Wiring 23
5.4 Power Supply at the Calculator 24
5.4.1 Power Supply Modules 24
5.5 Connecting Sensors 24
5.5.1 Pulse Input for Volume Counting 24

4Instruction for use | Supercal 5
5.5.1.1 Technical Characteristics of The Pulse Input for Volume Counting 24
5.5.2 Two Additional Pulse Inputs 25
5.6 Connecting Outputs 25
5.6.1 Two Open Collector Pulse Outputs 25
5.6.1.1 Technical Characteristics of the Two Open-Collector Pulse Outputs 26
5.7 M-Bus Communication 27
5.7.1 Timing M-Bus Communication 27
5.7.1.1 Technical Characteristics of embedded M-Bus 27
5.8 Radio Modules (Ex Factory) 28
5.8.1 Radio Telegram 28
6. Operation 29
6.4 Menus 30
6.5 Comminssioning 30
6.6 Main Menu 31
6.7 Overview Menu 34
6.8 Metrological Setup 34
6.11 Service 40
6.12 Sealing 42
6.13 Nowa / Unicon 42
6.14 Save Operating Data 42
6.14.1 Data Backup 42
7. Commissioning 44
7.1 Commissioning of the Supercal 5 44
7.1.1 Checking Date and Time 44
7.1.2 Flow Control 44
7.1.3 Checking the Temperatures 44
7.2 Uses 44
7.2.1 Flow Calculation 44
7.2.1.1 Reaction time and Accuracy of the Flow Calculation 45
7.3 Software Superprog Windows and Superprog Android. 45
7.3.1 Download the Superprog Windows and Superprog Andorid. 45
7.3.1.1 Solar and Refrigeration Systems 45
7.3.1.2 Tariff Functions and/or Status Message Signal 45
7.3.1.3 Power Supply 46
7.3.1.4 Error Output 46
8. Maintenance 46
8.1 Cleaning 46
9. Troubleshooting 46
10. Decommissioning 48
10.1 Exchange and Return 48
10.2 Disposal 48
10.2.1 Disposal 48

5Instruction for use | Supercal 5
11. Technical Information 49
11.2 Power Supplies 50
11.2.1 Mains Modules 50
11.2.2 Battery Modules 50
11.2.3 Estimating the Battery Life of an M-Bus Application 50
11.3 Measurement concept 50
11.4 Arithmetic Logic Unit 51
11.5 Flow Sensors 51
11.6 Flow Measurement 51
11.7 Flow Calculation 52
11.7.1 Calculation of the Flow Rate with Conventional Flow Sensors 52
11.7.2 Calculation of the Flow Rate with Fast Flow Sensors 52
11.8 Temperature Measurement 52
11.8.1 General Information 52
11.8.2 Permissible Errors and Limit Values 53
11.10 Calibration and Measurement Data 54
11.11 Nowa 54
12. Notes on Project Planning 56
12.1 Safety and Security 56
12.2 Local Regulations 56
12.3 Power Supply 56
12.4 Lightning protection 56
12.5 Bus Facilities 56
12.6 Refrigeration Plants 57
12.7 Assembly 57
12.8 Lead Sealing 57
12.10 Installation Information 57
12.11 Minimum Distances 57
13. Appendix 58
13.1 Extra Information for Supercal 5 S 58
13.1.1 Cut off Function of the Superstatic 440 58
13.4 Technical Data Flow sensor Superststic 440 62
13.5 Optional Communication Modules Overview 63
13.6 Software 63
14. Return of good Form 64
15. Declaration of Conformity 65
16. Declaration of Conformity 65

6Instruction for use | Supercal 5

7Instruction for use | Supercal 5
1. Notes on This Document
This manual provides all the information required for the correct use of the equipment: From
disposal.
1.1 Scope of Validity
This documentation is valid for the Sontex Supercal©5 I and Supercal©5 S.
-
ual's different sections.
1.2 Target Groups
This documentation is intended for the system operator and the installer of the calculator
or heat meter.
1.3 Storage of Document
The system operator must ensure that this documentation is accessible to the responsible
persons at all times. If the original document is lost, you can download an up-to-date version
of this document from our extranet (https://extranet.sontex.ch/index/).
1.4 Further Information
Links to further information can be found at www.sontex.ch.

8Instruction for use | Supercal 5
1.5 Symbols
Symbol Signicance
DANGER
DANGER!
Warning, the non-observance of which leads directly to death or
serious injury.
WARNING
WARNING!
Warning, the non-observance of which may result in death or serious
injury.
CAUTION
CAUTION!
Warning, the non-observance of which may result in minor or
moderate injury.
NOTICE
NOTICE!
Warning, non-observance of which may result in damage to
property.
Reference
relevant to security.
Documentation
Reference to documentation.
?Help
Help in case of problems.
Visual check
Check that the item is in order.
CE-Marking
The calculator meets the requirements of the European
directives 2014/32/EU (MID) and RED 2014/53/EU.
Disposal
This symbol indicates that electrical and electronic equipment must
be disposed of separately. Do not dispose of the calculator with
household waste.

Instruction for use | Supercal 5
2. Security
Safe and harmless operation of the calculator can only be guaranteed if the operating in-
structions have been read and the safety instructions contained therein have been observed.
Further information and data can be found in the products' catalogues and data sheets,
through your local representative, and on the Sontex homepage at www.sontex.ch.
All technical data without guarantee.
Subject to technical changes at any time.
In case of doubt, the text of the English Instructions For Use applies.
2.1 Personnel Qualication
The personnel responsible for installation, commissioning, diagnosis and maintenance must
meet the following conditions:
Authorized by the plant operator.
Knowledge of the relevant standards and directives and familiar with national
regulations
Before starting work: Read and understand instructions and additional documentation
Follow instructions and general conditions.
Training in the handling of hazards and risks during the installation and operation
of electrical devices and systems.
The operating personnel must meet the following conditions:
Instructed and authorized by the plant operator in accordance with the task
requirements.
Follow the instructions in this document.
2.2 Intended Use
It can be used universally in industry, district heating and building services engineering.
and changes to the device must not be made.
regulations as well as the manufacturer’s instructions are to be observed. The manu-
facturer assumes no responsibility for changes to the data relevant for calibration and
measurement if the factory seal has been broken.
If several heat meters are used in one billing unit, the same device types and installa-
tion positions should be selected to ensure that heat consumption is measured as fairly
as possible.
The feature of the calculator Supercal 5 for cooling applications with cooling liquids
water mixtures is exclusive to be used with the flow sensor Superstatic 440 (Not to be
used with mechanical flow sensors). If the feature cooling liquid (Glycol) water mixture
is enabled with the Superprog Windows and Superprog Android
2.3 Safety Instructions
2.3.1 Occupational Safety
When working on and with an electronic device:
Wear the necessary personal protective equipment under national
regulation.

10 Instruction for use | Supercal 5
2.3.2 Operational safety
Risk of injury!
Operate the device only in a technically perfect and safe condition.
The operator is responsible for the trouble-free operation of the device.
Modications to the device
dangers:
Sontex SA.
Repair
To ensure continued operational safety:
Only if repair is expressly permitted, carry it out on the electronic device.
Observe the national regulations concerning the repair of an electrical, electronic de-
vice.
Only use original Sontex spare parts and accessories.
Environmental requirements
If the plastic housing of the Supercal 5 is permanently exposed to certain vapour-air mix-
tures, the housing may be damaged.
For use in areas subject to approval: See the information on the nameplate.
2.3.3 Product Safety
The Supercal 5 has been built and tested in accordance with the state of the art and good
engineering practice to ensure safe operation and has left the factory in a technically per-
fect condition.
It meets the general safety requirements and legal requirements. It also conforms to the EC

11Instruction for use | Supercal 5
3. Description
3.1 Identication
3.1.1 Nameplate
The following data according to PTB/MID can be found on the nameplate:
Data on the nameplate
Manufacturer or customer logo Sontex
Product designation Supercal 5*
CE marking
Item number SC5Ixxxxx
Serial number/Year S/N xxxxxxxx
QR Code
Enviroment class according to OIML or EN 1434 C
Electrical/Mechanical class according to OIML or EN 1434 E1/M1
Protection class according to OIML or EN 1434 IP65
Temperature range (Θ)1..200 °C
Temperature difference (ΔΘ) 3..150 K
Temperature range cooling (ΘK) 1..200 °C
Temperature difference cooling (ΔΘK) 3..150 K
Pulse factor See Display
Installation See Display
Resistor Pt500
Approval mark
Flowmeter parameter: qp, qi, qs, DN, PN. See Display
M-Bus Interface EN 13757-2
Standard optical interface EN 60870-5
Optional Radio Interfaces Sontex radio 433MHz wM-Bus 868MHz No Radio
NFC Chip Location NFC )))
Sontex Address Rue de la Gare 27, 2605 Sonceboz. Switzerland
** According to production year.

12 Instruction for use | Supercal 5
EN1434
Pt 500
E1 / M1
IP65
EN 6070-5
Type: SC5I
S/N: 26277017 2021
Pulse value, installation,
flowmeter parameters:
See display
M-Bus
wM-Bus 868MHz
Sontex SA
Rue de la Gare 27
2605 Sonceboz
Switzerland
NFC
Calculator
Heating/Cooling
θ: 1...200°C
∆θ: 3...150K
θK: 1...200°C
∆θK: 3...150K
M21 1259
DE-21-MI004-PTB002

13Instruction for use | Supercal 5
3.2 Scope of Delivery
The scope of delivery of the Supercal 5 include:
Installation guide
Stickers (seals)
Modules (on demand)
3.3 Certicates and Approvals
The Supercal 5 and the optionally available pair of temperature sensors meet the require-
20.4.2016) (Meas-urement Instruments Directive, MID), as well as OIML R75 and EN-1434.
also have a type approval (incl. conformity assessment) in accordance with MID.
3.3.1 CE-Symbol
The product meets the requirements of the harmonized European standards. Thus it meets
-

14 Instruction for use | Supercal 5
4. Installation
Installation and commissioning of a heat measuring point should only be carried out by
authorised specialist personnel in compliance with valid standards and local safety and
installation regulations.
According to EN 1434-2 and EN 1434-6, the installation guidelines must be followed. Only
in compliance with the local regulations for electrical installations and the manufacturer's
4.1 Acceptance of Goods
After receiving the goods, check the following points:
Are the packaging or contents damaged?
Is the delivered product complete?
Compare the scope of delivery with your order details.
4.2 Transporting and Storing the Calculator
be found in the chapter Technical Information.
Observe the following points:
For storage (and transport) the device must be packed shockproof. The original
packaging offers optimum protection for this.
ranges is limited in time (maximum 48 hours).
4.3 Checking the Scope of Deliver
Check the scope of delivery for completeness and possible damage. Contact your dealer or
Sontex SA in case of faulty delivery.
4.4 Structure and Components of the Calculator
The Supercal 5 calculator consists of:
Measuring and calibrating-relevant upper part
Lower part
The calculator's modular design enables low storage costs and simple and effective meter
replacement after calibration validity has expired.
Only the upper part of the calculator is replaced, while the lower part of the calculator with
on site.

15Instruction for use | Supercal 5
4.4.1 Calculator Upper Part
4.4.2 Calculator Lower Part
1Sontex or customer logo
2Dot-Matrix Display
3Brackets for Housing opening/closing
4Two Status LED
5Two operating buttons
6Optical interface
7NFC Interface
8External mains / battery supply
9Connection terminal block
10 Rubber gommets (IP65)
11 Strain reliefs for connection cable and earthing
12 Two slots for optional communication modules
13 Wall mounting sliders
The following elements are located in the upper and lower part of the calculator:
1
2
3
4
7
12
5
6
8
9
10
13
11

16 Instruction for use | Supercal 5
4.5 Dimensions
159.6
163.6
136.3
138.3
49
5.5
23.2
175.1
95.08
143
158
53.5
3.9
4.6 Mounting
4.6.1 Before Mounting
All cables must be laid at a minimum distance of 300 mm from power
and high-frequency cables.
calculator must be avoided.
The calculator must generally be mounted separately from the heat or
cold pipe.
It must be ensured that no condensation water can run into the
calculator along the connected lines.
If there is a risk of vibrations in the piping system, the calculator should
be mounted separately on the wall.
mounted separately.
that there are no foreign bodies in the pipeline.
The lines must be vented during commissioning. Air in the system or in
Only use suitable new sealing material.
The tightness of the various connections must be checked.
the house installation.

17Instruction for use | Supercal 5
Check the design data of the plants.
The permissible ambient temperature for the calculator is 5 ... 55°C.
The installation and project planning regulations must be observed.
The readability of the calculator and all nameplates must be observed.
The complete heat meter consists of the following three subunits:
Flow sensor
Calculator Supercal 5
Temperature sensor (2- or 4-wire technology) with or without pockets
temperature sensor and calculator must be matched to each other.
The Supercal 5 calculator offers the following mounting options:
4.6.2 Wall Mounting

18 Instruction for use | Supercal 5
4.6.3 Top Hat Rail Mounting
Monté
Installation
4.7 Installation Instructions For Temperature Sensors
When selecting and installing temperature sensors, the greatest care must be taken. Errors
committed here can no longer be compensated even by the best calculator
CAUTION
Take care when installing the temperature sensors!
Incorrect removal of directly immersing temperature sensors may result in an acci-
persons.
NOTICE
Shielding of the cables against electromagnetic interference!
If there is a danger of electrical or electromagnetic interference, temperature sensors
in 2- and 4-wire technology with shielded cables or shielded cables at the connection
heads must be used. The shielding should be connected to the appropriate electrical
ground in the calculator. The possibility of interference increases with the length of
The connection cables must not be separated, extended or shortened!
The sensors are exactly computer paired in the factory and may only be used in the
original pairing!
Installation with cable lengths over 3 m
For installations with cable lengths over 3 m or with unequal cable lengths,
we recommend the use of 4-wire temperature sensors. The maximum cable
length of the 4-wire temperature sensors is 50 m

Instruction for use | Supercal 5
Only platinum temperature sensors with type approval in the Pt500 version are recommend-
ed. These must be paired and used in two-wire technology up to a cable length of 3 m. The
connecting cables must not be separated, extended, or shortened.
For lengths of more than 3 m, we recommend the use of carefully shielded cable lines of the
same length. The approval of the Supercal 5 allows 2-wire temperature sensors to be used
up to a maximum length of 15 m and 4-wire temperature sensors up to a maximum cable
length of 50 m. Su-percal 5 can be used with a maximum cable length of 50 m.
The temperature sensors should preferably be installed directly and without thermowell for
low-temperature heating systems due to the minimum temperature spread. This allows even
the smallest temperature differences to be determined without delays and heat dissipation
errors.
In pipelines up to DN 150, the temperature sensors are installed directly or employing ther-
mowell. The dynamic measuring range of the sensor tip is located as far as possible in the
middle of the pipeline.
Extensive information on the subject of temperature sensors can be found in our Sontex
temperature sensor overview at: www.sontex.ch/downloads/ under the heading tempera-
ture sensor 460.
4.7.1 Installation Instructions For Temperature Sensors
5678
5/6
Temperature high
7/8
Temperature low
r w r w
Since it is not the absolute temperature but the exact temperature difference that is im-
portant when measuring the heat quantity, both sensor cables must be the identical length
(resistance). The sen-sors are very accurately computer paired in the factory and may only
be used in the original pairing.
EN1434-2 2004 prescribes the following maximum cable lengths for 2-wire temperature
sensors:
Wire cross-section Maximum cable length
Pt500
0,22 mm212,5 m
0,50 mm225,0 m
0,75 mm237,5 m
1,50 mm275,0 m

20 Instruction for use | Supercal 5
4.7.2 Connection of 4-Wire Temperature Sensor
For installations with cable lengths over 3 m or with unequal cable lengths, we recommend
the use of 4-wire temperature sensors. The maximum cable length of the 4-wire tempera-
ture sensors is 50 m.
The connection cable must have four wires, the wire cross-section should be at least 0,5 mm2
The insulation of the temperature sensor cables can be made of PVC or silicone. Sontex
recommends the use of silicone as insulator.
1
5
2
6
3
7
4
8
wrr wwr w
1/5 and 2/6
Temperature high
3/7 and 4/8
Temperature low
r
1
5
2
6
r
r
w
w
3
7
4
8
r
r
w
w
4.7.2.1 Wire Cable Sensor with 2-Wire Calculator
12
rw
34
rw
5/6
Temperature high
7/8
Temperature low
5/6
Temperature high
7/8
Temperature low