
safety shutdown, the #3 LED will start
blinking. (See Figure 2 on Page 5 and point 3
on page 15)
1. The High Limit switch. This sensor will
sense if the unit reaches temperatures that are
too high for normal operation. If this happens
the Auger will quit feeding and the #2 and #3
LED lights will flash simultaneously. (See
Figure 2 on Page 5 and point 4 on page 16)
2. The Vacuum Switch - For the stove to
operate, the Firebox needs to be sealed.
During the first 30 seconds after the stove has
been turned on the Control Board will check
if the switch senses negative pressure
(Vacuum) in the Firebox of the stove. If there
is no negative pressure, the stove will shut
down and the #2 LED will start blinking.
(See Figure 2 on Page 5 and point 2 on page
15).
“Power Reset”. If the board becomes
unresponsive you must unplug the stove, wait 10
seconds and plug the stove back in to reset the
board.
“Internal Alarm”. When the control board
becomes unresponsive, the control board is in
Internal Alarm. The control board has sensed one
of the Safety sensors. This may cause the stove to
go out. In some cases, after waiting
approximately 45 seconds the stove will start
responding to the control board again. Many
times, the cause of this is a change in the vacuum
inside the stove. This may be caused by excessive
wind, opening the Firebox door or opening the
Ash Pan door. The control board will monitor the
vacuum switch and resume normal operation if
the vacuum returns to normal.
Safety Features
York Operations Manual
WARNING: These safet
features are
designed to protect life and propert
.
B
passin
these features voids all warranties
and the safety listing of the stove.
1. ”High Limit” switch”, an overheat
safety switch will shut off the fuel feed if the
Stove reaches temperatures above normal
operating temperature. This is a “Normally
Closed” switch and is part of the Fan limit
control. If the High limit switch trips several
times, the problem in the Stove must be
diagnosed before the Stove is put back in
service, (Defective Room Fan, dirty Room
Fan, dirty Return Air Filter, defective Fan
Limit Control or possibly a bad Control
Board)
2. Proof of Fire switch also called the P.O.F.
This senses the temperature rise in the exhaust
system. The switch is “Normally Open” and
closes the circuit at 110 degrees. The Stove will
shut down if temperatures above 110 degrees F
are not sensed during start up or if the
temperature drops below 110 degrees during
normal operation.
3. Vacuum switch also called the Negative
pressure switch. When the stove is turned on
the Exhaust fan will create a negative pressure in
the firebox. The control board continually
checks to see if Negative Pressure (vacuum) is
present during operation of the Stove. If the
exhaust venting system becomes clogged or
obstructed, the firebox door or ash pan door are
left open or the exhaust fan quits working the
control board will go into “Safety shutdown”.
There is a 60 second window to allow for
cleaning the glass and removing the clinker
before then Stove shuts down. This is sufficient
for the Daily Maintenance
The St. Croix Pellet Stove has been Safety Tested
by an accredited, independent laboratory.
Damper Adjustment
When burning pellets make sure to check for the
formation of creosote in the unit and venting
system. Constantly running the stove on a low
setting with too much combustion air may cause
creosote to form. Burn pot temperatures can be
“too cool” when burning on low with too much
draft.
Adjusting the Damper may take a little time and
patience, but only needs to be done once. After the
damper has been adjusted to the venting system in
your home, the control board will do the rest.
The purpose of this damper is to adjust combustion
airflow to match the characteristic of each specific
air inlet and chimney configuration. The damper has
been preset at the factory and is about 80% closed.
This setting will work with most installations. Tall
Page 7