
Shutting The Stove Off (Refer to Figure 2)
1. Press the On/Off switch (2) once; the lights
will go off and the fire will go out in a few
minutes. The board essentially goes into “Safety
shutdown”.
2. As long as the Exhaust Temperature within
the stove remains above 110°F, the Room Air
Fan and the Combustion Exhaust Fan will
continue to run. Once the P.O.F. switch drops out
the Combustion Fan will run for another 10
minutes and finally the stove will shut down
completely.
3. NEVER unplug the stove to shut it off. Doing
so may cause a significant amount of smoke to
enter the room.
Diagnostic Features of the Control Board
The #2 LED and the #3 LED lights on the LED Light
bar as show in Figure 2 will flash to give a diagnostic
code to help in diagnosing problems that may occur.
These conditions fall into 2 categories:
a. Heat related issues.
b. Vacuum related issues.
The Diagnostic Lights flash as follows:
1. The Proof of Fire switch. This switch will
sense the temperature of the Exhaust rising
during start up. If the Exhaust temperature
does not reach 110 degrees F, or if during use
the temperature drops below 110 degrees F,
the Stove will go into “Internal Alarm” and
the Auger will quit feeding fuel. Once the
stove completes the safety shutdown, the #3
LED will start blinking. (See Figure 2 on
Page 6 and point 4 on page 20)
2. The High Limit switch. This sensor will
sense if the unit reaches temperatures that are
too high for normal operation. If this happens
the Auger will quit feeding and the #2 and #3
LED lights will flash simultaneously. (See
Figure 2 on Page 6 and point 6 on page 21)
3.
The Vacuum Switch - For the stove to operate,
the Firebox needs to be sealed. During the first
30 seconds after the stove has been turned on the
Control Board will check if the switch senses
negative pressure (Vacuum) in the Firebox of the
stove. If there is no negative pressure, the stove
will shut down and the #2 LED will start
blinking. (See Figure 2 on Page 6 and point 5 on
page 21)
“Power Reset”. If the board becomes unresponsive you
must unplug the stove, wait 10 seconds and plug the stove
back in to reset the board.
“Internal Alarm”. When the control board becomes
unresponsive, the control board is in Internal Alarm. The
control board has sensed one of the Safety sensors. This
may cause the stove to go out. In some cases, after
waiting approximately 45 seconds the stove will start
responding to the control board again. Many times, the
cause of this is a change in the vacuum inside the stove.
This may be caused by excessive wind, opening the
Firebox door or opening the Ash Pan door. The control
board will monitor the vacuum switch and resume normal
operation if the vacuum returns to normal.
Safety Features
1. ”High Limit” switch”, an overheat safety
switch will shut off the fuel feed if the Stove
reaches temperatures above normal operating
temperature. This is a “Normally Closed” switch
and is part of the Fan limit control. If the High
limit switch trips several times, the problem in
the Stove must be diagnosed before the Stove is
put back in service, (Defective Room Fan, dirty
Room Fan, dirty Return Air Filter, defective Fan
Limit Control or possibly a bad Control Board)
2. Proof of Fire switch also called the P.O.F. This
senses the temperature rise in the exhaust
system. The switch is “Normally Open” and
closes the circuit at 110 degrees. The Stove will
shut down if temperatures above 110 degrees F
are not sensed during start up or if the
temperature drops below 110 degrees during
normal operation.
3. Vacuum switch also called the Negative
pressure switch. When the stove is turned on
the Exhaust fan will create a negative pressure in
the firebox. The control board continually checks
to see if Negative Pressure (vacuum) is present
during operation of the Stove. If the exhaust
venting system becomes clogged or obstructed,
the firebox door or ash pan door are left open or
8
Lancaster Operations & Maintenance Manual